Appendix
0020206382_02 Capriz 2 Operating instructions
15
Appendix
A Operator level
–
overview
Setting level
Values
Unit
Increment, select
Default set-
ting
Min.
Max.
Heating installation
Pressure in the heating in-
stallation
Current value
bar
0.1
1
1.5
Heating flow temperature
Current value
℃
1
60
10
Preset
in the
system
Hot water generation
Hot water temperature
Current value
℃
1
55
35
60
Eco hot water temperature
Current value
℃
1
35
50
B Troubleshooting
Fault
Cause
Measure
Product does not
start up:
–
No hot water
–
Heating does
not heat up
The gas isolator cock installed on-site
and/or the gas isolator cock on the
product is closed.
Open both gas isolator cocks.
The cold water stop cock is closed.
Open the cold water stop cock.
The power supply in the building is dis-
connected.
Check the fuse in the build-
ing. The product automatically
switches on after the power
supply is restored.
The product is switched off.
Switch on the product (
→
"Switch-
ing on the product" section).
The heating flow temperature or hot
water temperature has been set too
low.
Set the heating flow temperat-
ure and hot water temperature (
→
"Setting the heating flow temper-
ature" section/
→
"Setting the hot
water temperature" section).
The system pressure is insufficient.
Low water pressure in the heating in-
stallation (fault code: F.22).
Fill the heating installation (
→
"Filling the heating installation"
section).
If the pressure drops frequently,
contact your competent person
about this.