4
SR468SE 27-06-13
build up of soot or debris on the top from the flue pipe. Remove the baffle and check the flue spigot and
connector is fully clear at regular intervals. The chimney and flue connector must be swept at least annually,
more often when used with sooty fuels or damp wood. Any loose, broken or leaking joints or flue ways
MUST be repaired immediately.
Fuels
Only use recommended fuels. The appliance can be damaged by burning petroleum coke; liquid fuels or
general rubbish and this will invalidate your warranty and risk your personal safety.
The appliance must
not be used as a rubbish incinerator
.
Maintenance
Annual checking and servicing of the appliance and flue by a competent engineer is recommended.
Ventilation
No purpose provided ventilation is normally required for stoves rated under 5KW. However for
newer build properties or properties that have been modified so that the design air permeability is less than
5m
3
/h.m
2
a permanent ventilator will need to be fitted. Approved document J of the building Regulations
gives more detailed information. For each KW above 5KW, 550 sq mm of fixed ventilation is required – i.e.
a stove rated at 8KW would require 3 x 550 sq mm = 1650 sq mm of fixed ventilation. If more than one
appliance is installed in the same room, the ventilation requirements for each appliance must be added
together.
There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit
fumes into the room.
4.0
Installation Information
Chimney
The chimney height and the position of the chimney terminal should conform to Building Regulations.
Minimum chimney height is 4.5m. Check that the chimney is in good condition, dry, free from cracks and
obstructions. The diameter of the flue should not be less than 150mm and not more than 200mm. If any of
these requirements are not met, the chimney should be lined by a suitable method. The chimney must be
swept before connection to the stove.
Where the chimney is believed to have previously served an open fire installation, it is possible that the
higher flue gas temperature from the stove may loosen deposits that were previously firmly adhered, with
the consequent risk of flue blockage. It is therefore recommended that the chimney be swept a second time
within a month of regular use after installation.
If you have any doubts about the suitability of your chimney, consult your local dealer/stockist or chimney
specialist. If there is no existing chimney then either a solid fuel compatible prefabricated block chimney or
a twin-walled insulated stainless steel flue to BS 1856-1 can be used. These chimneys must be fitted in
accordance with the manufacturer‟s instructions and also please refer to the current issues of British
Standards BS EN 15287-1:2007 for design, installation and commissioning of chimneys.
Ventilation
No purpose provided ventilation is required for stoves rated under 5KW. For each KW above 5KW, 550 sq
mm of fixed ventilation is required – i.e. a stove rated at 8KW would require 3 x 550 sq mm = 1650 sq mm
of fixed ventilation. If more than one appliance is installed in the same room, the ventilation requirements
for each appliance must be added together.
Flue Draught
A flue draught of minimum 1.2mm to a maximum 2.5mm water gauge (12 to 25 Pascals) is required for
satisfactory appliance performance. The flue draught should be checked under fire at high output and, if it