Heat Controller HTD Series Installation, Operation & Maintenance Manual Download Page 23

23

Installation, Operation & Maintenance 

HTV/HTD/HTH SERIES

 

Heat Controller, Inc.

Electrical - Thermostat Wiring

Figure 24: Units With Optional ECM Fan.

Figure 25: Typical Thermostat 2 Heat/1 Cool (PSC Fan)

Thermostat Installation

The thermostat should be located on an interior wall in a 
larger room, away from supply duct drafts. DO NOT locate 
the thermostat in areas subject to sunlight, drafts or on 
external walls. The wire access hole behind the thermostat 
may in certain cases need to be sealed to prevent erroneous 
temperature measurement. Position the thermostat back 
plate against the wall so that it appears level and so the 
thermostat wires protrude through the middle of the back 
plate. Mark the position of the back plate mounting holes 
and drill holes with a 3/16” (5mm) bit. Install supplied 
anchors and secure plate to the wall. Thermostat wire must 
be 18 AWG wire. Wire the appropriate thermostat as shown 
in Figures 24 and 25 to the low voltage terminal strip on the 
CXM (units with PSC motor) or ECM control board (units 
with ECM motor).  Practically any heat pump thermostat will 
work with these units, provided it has the correct number of 
heating and cooling stages. 

ATP32U04 Thermostat

Connection to ECM Control

Compressor

Compressor Stage 2

Reversing Valve

Fan

24Vac Hot

24Vac Common

Fault LED

ECM

Board

Y1
Y2

W

DH

O
G
R
C

AL1

Y1
Y2

W

DH

O
G
R
C

L

Dehumidification

Units with CXM or DXM board and ECM fan motor, utilizing ECM dehumidification
mode (without ClimaDry option)

Notes:
1)  Units with whole house dehumidification option have slightly different

thermostat wiring.Terminal DH at the thermostat is connected to terminal H at
the DXM board

2)  ECM dehumidification mode slows down fan speed in the cooling mode when

dehumidification output from thermostat is active. Normal heating and cooling fan
speeds are not affected.

3)  ECM board DIP switch SW9 must be in dehumid. mode for

ECM dehumidification mode.

Auxiliary Heat

ATM21U01 Thermostat

Connection to CXM Control

Compressor

Heating Stage 2

Reversing Valve

Fan

24Vac Hot

24Vac Common

Fault LED

Y

Y2/W

O
G
R
C

L

Y

W

O
G
R
C

AL1

CXM

NOTICE:

 Units with ClimaDry whole house dehumidi

Ä

 cation 

option require a separate humidistat or thermostat part 
number ATP32U04 (See ClimaDry AOM for more details).

ѥ

CAUTION!

ѥ

ѥ

CAUTION!

ѥ

CAUTION!

 Refrigerant pressure activated water regulating 

valves should never be used with ClimateMaster 
equipment.

CAUTION!

 Many units are installed with a factory or 

¿

 eld 

supplied manual or electric shut-off valve. 

DAMAGE

WILL OCCUR

 if shut-off valve is 

closed

during unit 

operation. A high pressure switch must be installed on 
the heat pump side of any 

¿

 eld provided shut-off valves 

and connected to the heat pump controls in series with 
the built-in refrigerant circuit high pressure switch to 
disable compressor operation if water pressure exceeds 
pressure switch setting. The 

¿

 eld installed high pressure 

switch shall have a cut-out pressure of 300 psig and a 
cut-in pressure of 250 psig. This pressure switch can 
be ordered from ClimateMaster with a 1/4” internal 

À

 are 

connection as part number 39B0005N02.

Manufacturer

Manufacturer

Units with CXM or DXM board and ECM fan motor, utilizing ECM dehumidifi cation mode

Notes:

1) ECM dehumidifi cation mode slows down fan speed in the cooling mode when 

dehumidifi cation output from thermostat is active. Normal heating and cooling fan 
speeds are not affected.

2) ECM board DIP switch SW9 must be in dehumid. mode for ECM dehumidifi cation mode.

Summary of Contents for HTD Series

Page 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com INSTALLATION OPERATION MAINTENANCE MANUAL HTV HTD HTH Series Two Stage Geothermal Heat Pumps 2 to 6 Tons...

Page 2: ...ated Air Coil TABLE OF CONTENTS Model Nomenclature 2 Storage 4 Pre Installation 4 Horizontal Installation 5 Field Conversion of Air Discharge 7 Duct System Installation 8 Condensate Piping Installatio...

Page 3: ...of refrigerants If a compressor is removed from this unit refrigerant circuit oil will remain in the compressor To avoid leakage of compressor oil refrigerant lines of the compressor must be sealed a...

Page 4: ...th each unit Horizontal equipment is designed for installation above false ceiling or in a ceiling plenum Other unit configurations are typically installed in a mechanical room The installation site c...

Page 5: ...electrical and duct connection s If the unit is located in a confined space such as a closet provisions must be made for return air to freely enter the space by means of a louvered door etc Any access...

Page 6: ...RZHU LULQJ QVXODWHG VXSSO GXFW ZLWK DW OHDVW RQH GHJ HOERZ WR UHGXFH DLU QRLVH 5HWXUQ LU 6XSSO LU 8QLW DQJHU PP WKUHDGHG URGV 8QLW 3RZHU OH LEOH XFW RQQHFWRU 2SWLRQDO RZ 3UHVVXUH URS DWHU RQWURO 9DOYH...

Page 7: ...n Figure 4 to free top panel and discharge panel 2 Lift out the access panel and set aside Lift and rotate the discharge panel to the other position as shown being careful with the blower wiring 3 Che...

Page 8: ...this may cause poor drainage for all units on the line WHEN A VENT IS INSTALLED IN THE DRAIN LINE IT MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION OF THE CONDENSATE FLOW CAUTION Duct System Install...

Page 9: ...be difficult to remove after the unit is installed should be removed prior to setting the unit Refer to Figures 7 and 8 for typical installation illustrations Refer to unit specifications catalog for...

Page 10: ...ions Figure 10b illustrates the internal trap for a typical vertical heat pump Each unit must be installed with its own individual vent where necessary and a means to flush or blow out the condensate...

Page 11: ...n testing Do not exceed the pipe pressure rating Test entire system when all loops are assembled Flushing the Earth Loop Once piping is completed between the unit Flow Controller and the ground loop F...

Page 12: ...piping insulation etc Then perform final flush and pressurize the loop to a static pressure of 50 75 psi 345 517 kPa winter or 35 40 psi 241 276 kPa summer After pressurization be sure to loosen the...

Page 13: ...Other water quality issues such as iron fouling corrosion prevention and erosion and clogging should be referenced in Table 3 Pressure Tank and Pump Use a closed bladder type pressure tank to minimize...

Page 14: ...ow rate On occasion flow control devices may produce velocity noise that can be reduced by applying some back pressure from the ball valve located on the discharge line Slightly closing the valve will...

Page 15: ...wable at maximum water temperature Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm...

Page 16: ...f the HWG is field selectable to 125 F or 150 F The 150 F set point allows more heat storage from the HWG For example consider the amount of heat that can be generated by the HWG when using the 125 F...

Page 17: ...BELOW 150 F THE 150 F HWG SETPOINT MUST ONLY BE USED ON SYSTEMS THAT EMPLOY AN APPROVED ANTI SCALD VALVE PART NUMBER AVAS4 AT THE HOT WATER STORAGE TANK WITH SUCH VALVE PROPERLY SET TO CONTROL WATER T...

Page 18: ...tem 2 Insulate all HWG water piping with no less than 3 8 10mm wall closed cell insulation 3 Open both shut off valves and make sure the tank drain valve is closed Water Tank Refill 1 Close valve 4 En...

Page 19: ...M Fan Motor TT Units ECM Standard TT Units ECM with ClimaDry Model Compressor HWG Pump FLA Ext Loop Pump FLA Fan Motor FLA Total Unit FLA Min Circuit Amps Max Fuse HACR 2 ClimaDry Pump FLA Total Unit...

Page 20: ...units are shipped on the medium speed tap Consult specifications catalog for specific unit airflow tables Typical unit design delivers rated airflow at nominal static 0 15 in w g 37Pa on medium speed...

Page 21: ...ter ow rate temperature is affecting the refrigeration circuit The factory setting for FP1 is for systems using water 30 F 1 1 C refrigerant temperature In low water temperature extended range applica...

Page 22: ...raw approximately 25 35 VA through the Y signal of the thermostat Note This valve can overheat the anticipator of an electromechanical thermostat Therefore only relay or triac based thermostats should...

Page 23: ...nal H at the DXM board 2 ECM dehumidification mode slows down fan speed in the cooling mode when dehumidification output from thermostat is active Normal heating and cooling fan speeds are not affecte...

Page 24: ...is used for residential units with internal electric heat When auxiliary electric heat is energized i e compressor and electric heat the greater of the auxiliary emergency or heating setting will be u...

Page 25: ...U RZ 9ROWDJH RQQHFWRU 6SDGH RQQHFWLRQV WR 0 RU 0 RDUG RPSUHVVRU LVFKDUJH 6HQVRU 5 RW DWHU 6HQVRU 5 2 6 6 6 6 6 6 6 6 6 2 21 6 6 6 3XPS 5HOD 0 RXQWHU IODVK SHU 0 2 5 3 6ZLWFKHV 7KHUPRVWDW RQQHFWLRQV HK...

Page 26: ...0 1500 Maximum 2000 1500 1600 1200 2000 1500 2000 2000 Minimum 1200 900 1100 825 1200 900 600 1350 064 0 7 1 Default 1750 1300 1400 1050 1875 1450 875 1875 Maximum 2300 1900 2000 1500 2300 1900 2300 2...

Page 27: ...should only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable provides field selection to disable the UPS feature On Enabled Off Disabled DIP switch...

Page 28: ...initial 120 seconds of a compressor run cycle FP1 is set at the factory for one try Therefore the control will go into lockout mode once the FP1 fault has occurred FP1 lockout code 4 Air coil low tem...

Page 29: ...ge 3 heating 1 Stage 3 heating 3 N A G W Emergency heat Emergency heat Emergency heat G Y or Y1 O Stage 1 cooling 2 Stage 1 cooling 4 Cooling 6 G Y1 Y2 O Stage 2 cooling 2 Stage 2 cooling 4 N A 1 Stag...

Page 30: ...24 8 40 15 66 150 8 2 01 3 26 6 38 11 67 152 6 1 94 2 28 4 36 18 68 154 4 1 88 1 30 2 34 37 69 156 2 1 81 0 32 0 32 65 70 158 0 1 75 1 33 8 31 03 71 159 8 1 69 2 35 6 29 50 72 161 6 1 64 3 37 4 28 05...

Page 31: ...th AHRI Standard 110 Table 8b Building Commissioning Limits Cooling Heating mits mbient air DB 45 F 7 C 39 F 4 C ambient air DB 80 6 F 27 C 68 F 20 C mbient air DB 130 F 54 C 85 F 29 C tering air DB W...

Page 32: ...ng slag and strong chemical cleaning agents Some antifreeze solutions may require distilled water Flow Controller pump s Verify that the pump s is wired purged of air and in operating condition System...

Page 33: ...p across the heat exchanger versus the data in Tables 9a through 9b Heat of extraction HE can be calculated and compared to submittal data capacity pages The formula for HE for systems with water is a...

Page 34: ...5 0 986 0 986 1 009 0 917 0 974 1 360 Ethylene Glycol 5 0 998 0 998 1 002 0 993 0 998 1 040 15 0 994 0 994 1 004 0 980 0 994 1 120 25 0 988 0 988 1 008 0 966 0 990 1 200 Antifreeze Correction Table Ta...

Page 35: ...9 25 96 106 100 110 105 115 322 342 326 346 331 351 10 15 10 15 10 15 17 22 17 22 17 22 12 2 14 2 9 3 11 3 6 4 8 4 23 29 24 30 24 30 70 1 5 2 25 3 136 146 135 145 135 145 302 322 283 303 265 285 9 14...

Page 36: ...19 13 18 12 17 19 21 14 16 9 11 20 26 20 26 20 26 Based on 15 Methanol antifreeze solution HT060 TE072 Full Load Cooling without HWG active Full Load Heating without HWG active Entering Water Temp F...

Page 37: ...65 5 2 23 6 98 5 15 7 3 2 4 5 1 2 2 7 730 27 1 19 1 1 32 20 6 31 6 14 3 2 0 4 5 1 2 2 7 820 30 4 1 73 5 1 24 4 104 3 59 1 3 5 4 5 1 2 2 7 850 27 6 20 5 1 37 20 2 32 3 14 3 2 0 4 5 1 2 2 7 950 30 8 1 6...

Page 38: ...3 5 4 5 1 5 3 4 1250 44 8 2 39 5 5 36 6 103 2 16 3 4 3 6 8 2 7 6 3 1080 41 7 26 6 1 91 21 8 48 2 14 6 2 8 6 8 2 7 6 3 1080 46 5 2 53 5 4 37 8 109 8 58 8 4 7 6 8 2 7 6 3 1250 42 4 28 6 1 98 21 4 49 2 1...

Page 39: ...0 57 7 3 46 4 9 45 9 102 4 15 3 4 7 9 0 2 0 4 5 1330 52 9 36 2 2 55 20 8 61 6 14 0 3 1 9 0 2 0 4 5 1430 60 0 3 66 4 8 47 6 108 9 59 4 5 1 9 0 2 0 4 5 1550 53 9 38 9 2 64 20 4 62 9 14 0 3 1 9 0 2 0 4 5...

Page 40: ...2050 77 0 4 41 5 1 61 9 104 8 16 5 5 4 11 3 2 3 5 2 1590 68 6 46 4 3 43 20 0 80 4 14 6 3 8 11 3 2 3 5 2 1750 80 1 4 67 5 0 64 2 112 4 58 6 5 8 11 3 2 3 5 2 1850 69 8 49 9 3 56 19 6 82 0 14 6 3 8 11 3...

Page 41: ...64 8 107 6 15 2 7 9 12 8 3 0 6 8 1590 75 0 47 4 3 98 18 9 88 6 14 2 5 8 12 8 3 0 6 8 1750 86 0 5 68 4 4 66 6 115 5 59 6 8 6 12 8 3 0 6 8 1850 76 3 50 9 4 12 18 5 90 4 14 2 5 9 12 8 3 0 6 8 2050 87 3 5...

Page 42: ...to obtain maximum performance Filters should be inspected every month under normal operating conditions and be replaced when necessary Units should never be operated without a filter Washable high eff...

Page 43: ...ing a voltmeter The fan signal is passed through the board to the external fan relay units with PSC motors only The alarm relay can either be 24VAC as shipped or dry contacts for use with DDC controls...

Page 44: ...her help Check Main power see power problems Check fault LED code on control board Yes No No No No No Yes No Yes See HP Fault See LP LOC Fault See FP1 Fault See FP2 Fault See Condensate Fault See Over...

Page 45: ...e away from unit Check slope of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air filter x X Restricte...

Page 46: ...on and air flow restrictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Check water flow Adjust to p...

Page 47: ...7 5 5 5 3 6 6 1 27 5 6 2 75 5 3 4 1 5HIULJHUDQW 7 SH HDW RI WUDFWLRQ EVRUSWLRQ RU HDW RI 5HMHFWLRQ ________ IORZ UDWH GLII IDFWRU BBBBBBBBBBBBB WX KU 6XSHUKHDW 6XEFRROLQJ 6XFWLRQ WHPSHUDWXUH VXFWLRQ V...

Page 48: ...01 2013 97B00 97B00...

Reviews: