Design Guide
HEV-HEH SEriES
Heat Controller
18
18
Engineering Design Guide
HEV/H SERIES
Heat Controller, LLC
Performance Data
HEV/H 048 - Full Load
1500 CFM Rated Air
ow
Performance capacities shown in thousands of Btuh
EWT
°F
GPM
WPD
Cooling - EAT 80/67°F
Heating - EAT 70°F
PSI FT
TC
SC
KW
HR
EER HWG
HC
KW
HE
LAT
COP HWG
20
Operation Not
Recommended
Operation Not Recommended
Operation Not Recommended
12.0
7.7 17.8
32.4
2.9
22.6
88.0
3.3
3.5
30
6.0
2.0
4.6
54.4
36.2
2.2
62.0
24.3
2.1
35.2
2.9
25.1
89.6
3.5
3.6
9.0
4.0
9.2
54.0
36.1
2.2
61.5
24.7
1.9
36.5
3.0
26.4
90.5
3.6
3.7
12.0 6.5 15.1
53.6
35.9
2.2
61.0
24.7
1.9
37.2
3.0
27.0
90.9
3.7
3.8
40
6.0
1.9
4.4
54.1
36.1
2.4
62.2
22.8
2.5
39.7
3.0
29.4
92.5
3.9
3.9
9.0
3.8
8.7
54.4
36.2
2.3
62.1
24.0
2.2
41.4
3.1
30.9
93.5
4.0
4.0
12.0 6.0 13.9
54.4
36.2
2.2
62.0
24.4
2.1
42.3
3.1
31.8
94.0
4.0
4.1
50
6.0
1.7
4.0
53.0
35.6
2.6
61.8
20.5
3.2
44.6
3.1
33.9
95.4
4.2
4.2
9.0
3.4
7.9
53.8
36.0
2.4
62.1
22.2
2.7
46.5
3.2
35.7
96.6
4.3
4.4
12.0 5.5 12.7
54.1
36.1
2.4
62.2
22.9
2.5
47.6
3.2
36.7
97.3
4.4
4.5
60
6.0
1.6
3.7
51.3
34.9
2.9
61.0
17.9
4.0
49.5
3.2
38.5
98.5
4.5
4.6
9.0
3.2
7.5
52.5
35.4
2.7
61.6
19.7
3.4
51.8
3.3
40.7
99.9
4.7
4.8
12.0 5.3 12.2
53.0
35.6
2.6
61.8
20.6
3.1
53.0
3.3
41.8
100.7
4.7
4.9
70
6.0
1.4
3.3
49.1
34.0
3.2
60.0
15.3
5.0
54.6
3.3
43.2
101.6
4.8
5.0
9.0
3.0
6.9
50.6
34.7
3.0
60.7
17.1
4.3
57.2
3.4
45.6
103.2
5.0
5.3
12.0 4.9 11.3
51.3
34.9
2.9
61.0
18.0
4.0
58.6
3.4
46.9
104.1
5.0
5.4
80
6.0
1.4
3.3
46.5
33.0
3.6
58.9
12.8
6.2
59.7
3.4
47.9
104.7
5.1
5.5
9.0
2.9
6.7
48.2
33.7
3.3
59.6
14.4
5.4
62.5
3.5
50.5
106.5
5.2
5.8
12.0 4.8 11.1
49.1
34.0
3.2
60.0
15.3
5.0
64.0
3.5
51.9
107.4
5.3
6.0
90
6.0
1.3
3.1
43.8
31.9
4.1
57.8
10.7
7.6
64.7
3.6
52.5
107.8
5.3
6.0
9.0
2.8
6.5
45.6
32.6
3.8
58.5
12.0
6.6
67.7
3.6
55.3
109.7
5.5
6.4
12.0 4.7 10.9
46.5
33.0
3.6
58.9
12.8
6.2
69.3
3.7
56.8
110.7
5.5
6.6
100
6.0
1.3
3.0
41.0
30.7
4.7
57.0
8.8
9.2
Operation Not Recommended
9.0
2.7
6.1
42.8
31.5
4.3
57.5
9.9
8.1
12.0 4.5 10.4
43.7
31.8
4.1
57.8
10.6
7.6
110
6.0
1.2
2.8
38.3
29.5
5.3
56.5
7.2
11.0
9.0
2.6
5.9
40.0
30.3
4.9
56.7
8.2
9.8
12.0 4.4 10.1
40.9
30.6
4.7
56.9
8.7
9.2
120
6.0
1.2
2.8
9.0
2.6
5.9
12.0 4.3 10.0
38.2
29.5
5.4
56.4
7.1
11.1
†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certi
ed conditions are 86°F EWT, 80.6°F DB / 66.2°F WB
EAT in cooling and 68°F DB / 59°F WB EAT in heating.
Interpoaltion is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating
All performance data is based upon the lower voltage of dual voltage rated units
See performance correction tables for operating conditions other than those listed above.
Operation below 60°F EWT requires optional insulated water circuit.
Operation below 40°F EWT is based upon 15% antifreeze solution.