Heat Controller EKTC07-1G Owner'S Manual Download Page 4

Packaged Terminal A/C

 

 OwnEr’s Manual 

 

Heat Controller, Inc.

3

This unit has many exciting features which are different than those found on 

standard PTAC models. The owner must be familiar with these features in order to 

fully understand the operation and capability of the unit.

• 

sElf DIaGnOsITICs

—The unit has an onboard computer that utilizes real-

time diagnostics to prolong the life of your unit. There is an LED indicator on 

the control board located behind the front panel, that will flash an error code 

if the unit has detected some kind of fault condition. In many cases, the unit 

will automatically clear the fault condition and continue operating with no 

interruption. In some cases, the condition cannot be cleared and the unit will 

require service. In those cases, an “Fx” failure mode will be displayed on the 

digital display. For a detailed list of all error codes and “Fx” conditions, 

see 

Table 6—Status LED Indicator Definitions 

for further details

.

• 

auTO rEsTarT

—If power is lost, all of the control settings (setpoint, mode, 

fan speed, on/off and configuration) are stored. So when power is restored, the unit will start back up in the mode (and con-

figuration) it was in when power was lost.

• 

QuIET OPEraTIOn

—The unit has 2 fan motors and a tangential blower wheel to reduce noise. The indoor fan will always run 

a minimum of 10 seconds before the compressor, to help reduce any compressor starting noise.

• 

ranDOM COMPrEssOr rEsTarT

—To help prevent power surges after a power outage (from many of your PTAC/HPs starting 

at the same time), the compressor is equipped with a 2:45 to 3:15 minute random restart delay feature.Whenever the unit is 

plugged in, or power has been restarted, a random compressor restart will occur between the random restart time frame.

• 

COMPrEssOr PrOTECTIOn

—To prevent short cycling of the compressor and maximize it’s life, there is a random start--up 

delay of 3 minutes on the compressor and a minimum compressor run time of 3 minutes.

auTOMaTIC rOOM  frEEZE PrOTECTIOn

—The unit will automatically will keep the temperature in the room from getting 

too cold, where water pipes might freeze. If the unit is configured for the freeze protection feature to be active (which is the 

default condition), and while power is supplied to the unit, if the unit senses temperature below 40°F, the fan motor and 

electric heater are turned on and will warm the room to 50°F. If Freeze protection is not required, change the configuration 

switch to turn the feature off (see section on unit configuration).

• 

auTOMaTIC DEfrOsT PrOTECTIOn (fOr HEaT PuMP MODEls OnlY)

—When the outdoor temperature gets too cold (ap-

prox. 35°F) and the unit can no longer effectively heat with the compressor, the unit will automatically switch to electric heat-

ing. The unit will then heat with electric heat until the outside temperature rises enough (approx. 40°F), so the compressor 

can be used to effectively heat again.

• 

auTOMaTIC QuICk warM-uP (fOr HEaT PuMP MODEls OnlY)

—If the room temperature falls to 5°F below the set point 

temperature, the reverse cycle heat is shut off and the electric strip heat is turned on for one cycle, until heating is satisfied.

lED InDICaTOr’s anD buTTOns

—The touch pad has buttons for MODE, FAN SPEED, ON/OFF, SETPOINT UP and SETPOINT 

DOWN. It also has LEDs that correspond to the mode, fan speed and setpoint operation, to indicate the unit’s status. The 

LEDs below the mode button, FAN, COOL, and HEAT, indicate which operating mode is active. The LEDs below the Fan button, 

Low, Med and Hi, indicate the fan speed that is selected. The LED located in the lower right corner is the unit On/Off status 

LED. If the unit is in ON mode, the LED will be green. If the unit is OFF, the LED will be red.

• 

COnfIGurE fan TO OPTIMIZE sElECTED aPPlICaTIOn

—This unit can be optimized to specific applications by configuring 

the fan to run in a continuous mode or to cycle on and off with the compressor and electric heater (can be different for both 

heating and cooling modes). In cycle mode, fan will continue to run after compressor or electric heater stops in order blow off 

any residual heat or cool left on coil. In continues mode, the fan remains on at all times even when the compressor is off.

Table 6—STATUS LED Indicator Definitions

1 Indoor air temp sensor open/short 7

Segment display ‘F1’, with STATUS light flash 1 time,off 2 seconds

2 Indoor coil sensor open/short 7

Segment display ‘F2’, with STATUS light flash 2 times and off 2 seconds

3 Outdoor coil sensor open/short 7

Segment display ‘F4’, with STATUS light flash 4 times and off 2 seconds

4 Freeze Guard protection 7

Segment display ‘FP’

5 Thermostat wiring error

STATUS light flash 9 times and off 3 sec, repeat

6 Indoor coil high temp protection

STATUS light flash 8 times and off 3 sec, repeat

7 Defrost (heat pump type)

STATUS light flash 7 times and off 3 sec, repeat

8 Outdoor coil high temp protection

STATUS light flash 6 times and off 3 sec, repeat

9 Indoor coil freeze protection

STATUS light flash 5 times and off 3 sec, repeat

nOTE

: When status light is flashing, it will be ON for 0.5 seconds and OFF for another 0.5 seconds.

UNIT FEATURES

Fig. 2

Summary of Contents for EKTC07-1G

Page 1: ...OWNER s MANUAL Packaged Terminal Air Conditioners Heat Pumps 7 000 15 000 BTUH Cooling with Electric Heat Heat Pump with Electric Heat EKTC07 2G EKTC09 2G EKTC12 2G EKTC15 2G EKTC07 1G EKTC09 1G EKTC12 1G EKTC15 1G EKTH07 1G EKTH09 1G EKTH12 1G EKTH15 1G EKTH07 2G EKTH09 2G EKTH12 2G EKTH15 2G ...

Page 2: ...n this manual may be different with the material objects please refer to the material objects for reference SYSTEM CONFIGURATION HOW TO CONNECT SAFETY CONSIDERATIONS GENERAL INFORMATION UNIT FEATURES ELECTRICAL DATA INSTALLATION OPERATION CARE AND CLEANING PREVENTATIVE MAINTENANCE TROUBLESHOOTING Table of Contents Safety Considerations 2 General Information 2 Unit Features 3 Electrical Data 5 Inst...

Page 3: ...lation Instructions before it is used Immediately repair or replace all electric service cords that have become frayed or otherwise damaged Unplug or disconnect the unit at the fuse box or circuit breaker before making any repairs WARNING GENERAL INFORMATION Heat Controller Inc package terminal air conditioners and heat pumps provide a high standard of quality in performance work manship durabilit...

Page 4: ... to turn the feature off see section on unit configuration Automatic defrost protection for heat pump models only When the outdoor temperature gets too cold ap prox 35 F and the unit can no longer effectively heat with the compressor the unit will automatically switch to electric heat ing The unit will then heat with electric heat until the outside temperature rises enough approx 40 F so the compr...

Page 5: ...ails Limit the Setpoint Range The unit can be configured to limit the controlling setpoint range The display will always show the complete setpoint range but the controlling setpoint will be limited to the configured minimum and maximum setpoint selected See section on unit configuration for more details Energy Management Sometimes known as Front Desk Control an input is provided so that the unit ...

Page 6: ...S NAMEPLATE AMPS AWG WIRE SIZE 7 0 to 12 14 12 1 to 16 12 16 1 to 24 10 Grounding For safety and protection the unit is grounded through the service cord plug or through separate ground wire provided on hard wired units Be sure that the branch circuit or general purpose outlet is grounded VOLTAGE SUPPLY Check voltage supply at outlet For satisfactory results the voltage range must always be within...

Page 7: ...il leaving air from mixing with the outdoor incoming air known as air recirculation INSTALLATION CAUTION UNIT DAMAGE AND OR OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation For retrofit applications foam seals on outdoor coil tube sheets must make a seal between the coil and the grille or loss of performance and premature damage to the major comp...

Page 8: ...fects in sleeve or for improper installation WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect all power to unit to avoid possible electrical shock during installation NOTE See installation instructions included with wall sleeve for information on installation NOTE Wall sleeves with a depth of 13 75 to 13 88 can be used in combinatio...

Page 9: ...2 Remove shipping screw from the vent door if present See Fig 6 3 Remove front panel See Fig 7 4 Lift unit level and slide unit into wall sleeve until foam seal rests firmly against front of wall sleeve 5 Secure with four screws supplied through the unit flange holes See Fig 8 6 Reinstall front panel See Fig 9 Fig 5 Shipping Tape Location Fig 7 Removing Front Panel Fig 8 Securing Unit Fig 9 Replac...

Page 10: ...ng out top rear and side screws See Fig 10 3 Connect accessory power supply cord or hard wire connector to unit connector See Fig 11 Units must be installed using the appropriate power supply kit See Table 4 POWER CONNECTION CHART These connections must be followed 4 Reinstall junction box and cover S Use wire clamp to attach power cord to basepan Secure with screws included See Fig 12 S Relace ju...

Page 11: ...ting or cooling efficiency Energy Tip Keep the vent control at CLOSE Room air will be filtered and circulated ADJUSTING AIR DIRECTION To adjust air direction from outward default to upward 1 Remove front panel See Fig 7 2 Remove louver screws that hold louver insert in place from back side of front panel See Fig 13 3 Turn louver insert and rotate 180 See Fig 14 4 Replace louver insert 5 Replace sc...

Page 12: ...e setting has been satisfied This switch helps to maintain the room temperature closer to the thermostat setting CYC Cycle This setting allows the fan to cycle on and off with the compressor or electric heater The fan stops a short time after the temperature setting is satisfied Setpoint Temperature Limits Provides a restricted range of temperature control Room Freeze Protection If unit senses a r...

Page 13: ...s F Indoor Air Temperature Sensor Biasing for Cooling mode Sometimes known as an anticipator the air temperature sensor bias is used to adjust the room air temperature reading when in cooling mode Not normally required Indoor Air Temperature Sensor Biasing forHeating mode Sometimes known as an anticipator the air temperature sensor bias is used to adjust the room air temperature reading when in he...

Page 14: ... elements for one cycle in order to reach the new requested temperature quickly MODE FAN For fan only operation ON OFF Turns the unit on or off NOTE The LED above the ON OFF button will be green when unit is ON and red when the unit is OFF All other LEDs will be off when unit is set to OFF mode NOTE Power remains connected to unit even when the unit is in the OFF mode IMPORTANT When unit is first ...

Page 15: ...ure to follow this caution may result in equipment damage or improper operation Do not operate unit without filters in place If a filter becomes torn or damaged it should be replaced immediately Operating without filters in place or with damaged filters will allow dirt and dust to reach indoor coil and reduce cooling heating airflow and efficiency of unit Airflow restriction may cause damage to un...

Page 16: ...intenance follow the guidelines below Clean both sides of outdoor coil Never use high pressure spray on coils Clean basepan and outdoor vent filter Clean outdoor orifice and fan Clean indoor coil Never use high pressure spray on coils Clean indoor fan wire screen and front panel Clean or install new indoor air inlet filter s Clean wall sleeve and outdoor grille Inspect cord and receptacle Secure e...

Page 17: ...or to start DISPLAY HAS STRANGE NUMBERS CHARACTERS ON IT The unit may be in a diagnostic condition Check Intelligent Self checking Control section to determine if unit has had a failure The unit may be set for _C instead of _F see the keypad configuration section UNIT MAKING NOISES Clicking gurgling and whooshing noises are normal during operation of unit WATER DRIPPING OUTSIDE If a drain kit has ...

Page 18: ...04 2009 03 2010 ...

Reviews: