15
‘V’ Series
InverterFlex
Multi-Zone Ductless Mini-Split HeatPumps
Mix and match indoor units up to the maximum BTUHs for each
system. The chart on the right shows the various combinations.
Note that outdoor and indoor units are ordered separately; “A”
indicates outdoor unit, “B” indicates indoor unit.
For instance, to order a 33,000 BTUH tri-zone, you’ll specify one
A-VMH36QC, two B-VMH12FC, and one B-VMH09FC.
Outdoor Units
FEATURES
A-VMH18DC-1 A-VMH27TC-1 A-VMH36QC-1
Power Supply
208/230-1-60 208/230-1-60 208/230-1-60
System Cooling Capacity (BTUH)
18,000
27,000
36,000
SEER
16.0
16.0
15.0
Cooling Amps
7.5
11.0
15.0
System Heating Capacity (BTUH)
19,000
28,000
38,000
Heating Amps
7.6
11.2
15.0
HSPF
7.7
7.7
8.5
OUTDOOR UNIT DIMENSIONS
Width (inches)
33
1
/
4
33
1
/
4
39
Height (inches)
27
3
/
8
27
3
/
8
37
Depth (inches)
13
3
/
16
13
3
/
16
13
Net Wt/Shipping Wt (lbs.)
117.9/125.7 125.7/133.4 189.6/198.4
ELECTRICAL DATA OUTDOOR UNIT*
Main Power Connection
Outdoor Unit Outdoor Unit Outdoor Unit
Min. Circuit Ampacity
10.5
16.0
15.4
Max. Fuse/HACR Circuit Breaker
15
20
20
Recommended Indoor/Outdoor
Connecting Cable (SJOW)
Line Voltage
per NEC*
Line Voltage
per NEC*
Line Voltage
per NEC*
LINE SETS O.D. (inch) / REFRIGERANT
Refrigerant
R-410A
R-410A
R-410A
Liquid (flare) (inch)
1/4
1/4
1/4
Suction (flare) (inch)
3/8
3/8
3/8
Maximum Line Set Length
1
49.2 feet
49.2 feet
49.2 feet
Maximum Elevation (outdoor)
2
32.8 feet
32.8 feet
32.8 feet
InverterFlex Outdoor/Indoor Combinations
OUTDOOR UNIT
ZONES
INDOOR UNITS
TOTAL BTUH
A-VMH18DC-1
Dual
9K + 9K
18,000
A-VMH27TC-1
Dual
9K + 12K
21,000
Dual
12K + 12K
24,000
Tri
9K + 9K + 9K
27,000
A-VMH36QC-1
Tri
9K + 9K + 12K
30,000
Tri
9K + 12K + 12K
33,000
Tri
12K + 12K + 12K
36,000
Quad
9K + 9K + 9K +9K
36,000
Indoor Units
FEATURES
B-VMH09FC-1 B-VMH12FC-1
INDOOR UNIT
Cooling Capacity BTUH
9,000
12,000
Heating Capacity BTUH
10,000
13,000
Air flow (CFM)
335/283/206
412/306/247
Dehumidification (Pts/Hr)
2.3
2.5
Fan Speeds
3
3
AIR DIRECTION
Vertical Adjustment
Manual
Manual
Horizontal Modulating
Yes
Yes
Random Swing
Yes
Yes
INDICATOR LAMPS
ON/OFF
Yes
Yes
24 Hr. Timer/Sleep Mode
Yes
Yes
Defrost
Yes
Yes
Temperature Setting
On Remote: 62° F – 88° F
INDOOR UNIT DIMENSIONS
Width (inches)
31
5
/
16
33
1
/
4
Height (inches)
10
5
/
8
11
1
/
4
Depth (inches)
6
1
/
4
6
1
/
4
Net Wt/Shipping Wt (lbs)
22/26.5
22/26.5
Liquid (flare) (inch)
1/4
3/8
Suction (flare) (inch)
1/4
1/2*
C US
*Always follow local, state and national electrical codes. Main power connection is 208-230V.
1 Min. 15 ft. line set recommended
2 Oil trap should be installed every 16.5 to 23 feet (5-7m).
Design, specifications and performance data subject to change without notice.
Ambient Operating Temperature: 5° - 122° F (cooling); 5° - 93.2° F (heating)
*Adapter included with indoor section
* 9K = Model No. B-VMH09FC-1, 12K = Model No. B-VMH12FC-1
Warranty—6 years on compressor, 2 year on parts
(Some limitations apply; see printed warranty for details.)
TM