- 11 -
INDOOR UNIT
HEAT
EXCHANGER
(EVAPORATOR)
HEAT
EXCHANGER
(CONDENSER)
REVERSING
VALVE
COMPRESSOR
COOLING
HEATING
GAS SIDE
CAPILLARY TUBE
CHECK VALVE
LIQUID SIDE
OUTDOOR UNIT
• Cooling & Heating Models
MODEL
9K, 12K
(Cooling & Heating)
18K
(Cooling & Heating)
24K
(Cooling & Heating)
Pipe size(Diameter:ø)
Piping length
Elevation
Gas
Liquid
Rated
Max
Rated
Max
1/2"
1/4"
7.62m(25ft)
15m(50ft)
5m(16ft)
8m(26ft)
5/8"
1/4"
7.62m(25ft)
15m(50ft)
5m(16ft)
8m(26ft)
5/8"
3/8"
7.62m(25ft)
15m(50ft)
5m(16ft)
8m(26ft)
For installation over rated, *a proper quantity of refrigerant should be added for each 3.3ft (1m).
Ex) 18K: When installed at a distance of 50ft(15m),
10.6Oz(295g) of refrigerant should be added.
(50-25)
1.4
3.3 = 10.6 Oz (295g) of refrigerant
to add
Unit precharged for 25ft. line sets.
a proper quantity of refrigerant
9k, 12k
0.7 Oz (20g)
18k, 24k
1.4 Oz (40g)