background image

Heat & Glo  •  VRT-AUB  •  2123-980_R14  •  12/14

31

Step 2. 

For  installations  using  a  round  support  box/wall  thimble 

(check pipe manufacturer's instructions), mark the wall for 

a  9 in. x 9 in. (229 mm x 229 mm) square hole. The center 

of the square hole should line up with the center line of 

the horizontal pipe. Cut and frame the hole in the exterior 

wall  where  the  flue  will  be  terminated.  If  the  wall  being 

penetrated is constructed of noncombustible material, i.e. 

masonry block or concrete, a 7 in. (178 mm) diameter hole 

is acceptable.

Step 3. 

Position the horizontal termination cap in the center of the 9 

in. x 9 in. (229 mm x 229 mm) square hole and run a bead 

of non-hardening mastic around its outside edges, to make 

a seal between it and the wall. Attach termination cap to the 

exterior wall with the four wood screws provided. The arrow 

on the flue cap should be pointing up.

Figure 7.13 

Figure  7.12   

Note:  Align seams to engage pipe, 

then rotate counterclockwise to lock

Step 1.

Balanced flue pipe is designed with a locking connection. 

To connect the flue system to the gas stove flue outlet:

•  Lock the flue components into place by sliding the pipe 

section onto the collar.

•    Align the seam of the pipe and seam of collar to allow 

engagement. Rotate the flue component to lock into place. 

Use this procedure for all flue components. See Figure 

7.12.

•    Continue  adding  flue  components,  locking  each 

succeeding component into place.

•    Ensure that each succeeding flue component is securely 

fitted and locked into the preceding component.

90 DEGREE

ELBOW

PIPE LENGTH

PIPE LENGTH

WALL THIMBLE 

COVER

 

WALL THIMBLE

TERMINATION CAP

E.  Flue Pipe Assembly

F.  Horizontal Penetration Framing

WARNING

!

Fire Risk.
Explosion Risk.
Combustion Fume Risk.
Use flue run supports per installation instructions. 
Connect flue sections per installation instructions.
•  Maintain all clearances to combustibles.  
•  Do  NOT  allow  flue    to  sag  below  connection 

point to gas stove.

•  Maintain specified slope (if required).
Improper support may allow flue to sag or separate.

Summary of Contents for VRT-BK-N-AUB

Page 1: ...intenance instructions included Read understand and follow these instructions for safe installation and operation VRTIKL AUB FREESTANDING STOVE MODELS VRT BZ N AUB VRT BZ P AUB VRT GY N AUB VRT GY P A...

Page 2: ...ny local authorities requirements for gas electrical and building regulations This appliance and its components are tested and safe when installed in accordance with this Installation Manual Report to...

Page 3: ..._________ Dealership purchased from ________________________________ Dealer Phone ___________________________ Notes ____________________________________________________________________________________...

Page 4: ...8 5 Framing and Clearances A Selecting Appliance Location 19 B Optional Stone Surround Installed 20 6 Termination Locations A Vent Termination Minimum Clearances 21 Table of Contents 7 Flue Informatio...

Page 5: ...IntelliFire PlusTM Ignition System Wiring 55 C Optional Accessories Requirements 56 D Blower 56 E Control Module Operation 57 13 Troubleshooting A IntelliFire Plus Ignition System 65 14 Reference Mat...

Page 6: ...o the purchase price of the product This warranty is subject to conditions exclusions and limitations as described below Warranty coverage begins on the date of original purchase In the case of new ho...

Page 7: ...d under warranty Damage to printed plated or enamelled surfaces caused by fingerprints accidents misuse scratches melted items or other external sources and residues left on the plated surfaces from t...

Page 8: ...r weather damage which is the result of but not limited to improper chimney or venting installation HOW TO CLAIM To make a claim against this warranty contact your local distributor during regular bus...

Page 9: ...sk of Explosion An in line regulator MUST be installed if the gas pressure exceeds 3 7 kPa Failure to install a regulator could damage valve D High Altitude Installations NOTICE If the heating value o...

Page 10: ...n and that the integral barrier is in place WARNING Risk of Fire or Asphyxiation DO NOT operate fireplace with fixed glass assembly removed This appliance is not intended for use by persons including...

Page 11: ...iance Hot while in operation DO NOT touch Keep children clothing furniture gasoline and other liquids having flammable vapors away DO NOT operate the appliance with fixed glass assembly removed cracke...

Page 12: ...emote control RC300AU is programmed to the control module Note that the control module will always ignite the fireplace on HI and remain so for the initial 10 seconds of operation If the HI LO is swit...

Page 13: ...may release an odor for the first several hours This is caused by the curing of materials from manufacturing Odor may also be released from finishing materials and adhesives used near the fireplace Th...

Page 14: ...y maintained your fireplace will give you many years of trouble free service We recommend annual service by a qualified service technician Doors Surrounds Fronts Frequency Annually By Homeowner Tools...

Page 15: ...r to Section 9 G for log placement instructions Verify correct log placement and no flame impingement causing sooting Correct as necessary Firebox Frequency Annually By Qualified Service Technician To...

Page 16: ...carryover to all ports Verify that there is no ignition delay Inspect for lifting or other flame problems Verify air shutter setting is correct See Section 9 for required air shutter setting Verify ai...

Page 17: ...N 8 C VERTICAL TERMINATION CAP SECTION 10 L VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS SECTION 8 FRAMING HEADED OFF IN CEILING JOISTS SECTION 8 C GAS LINE SECTION 11 VENT PIPE...

Page 18: ...rts could impair safe operation DO NOT install damaged incomplete or substitute components Keep appliance dry C Tools and Supplies Needed Before beginning the installation be sure that the following t...

Page 19: ...uld be located out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Ac...

Page 20: ...Risk Odor Risk Tipping Risk Install gas stove on a stable level platform floor strong enough to support gas stove without tipping USE wood flooring ceramic tile brick hearth or high pressure laminate...

Page 21: ...ion with both gas and wood or fuel oil terminations the wood or fuel oil termination cap must be higher than the gas termination cap Minimum Height From Roof To Lowest Discharge Opening H MIN MINIMUM...

Page 22: ...up to 50 MJ h input 12 300 Appliances over 50 MJ h input 20 1 2 500 b From the ground or above a balcony 12 300 c From a return wall or external corner 20 1 2 500 d From a gas meter M 39 1000 e From...

Page 23: ...th the flueing for installation of these items 7 Flue Information Fire Hazard Explosion Risk Asphyxiation Risk Do NOT connect this gas stove to a chimney flue serving a separate solid fuel or gas burn...

Page 24: ...L FLUE V 38 ft 11 58 m Maximum STRAIGHT OUT HORIZONTAL FLUE H 2 ft 610 mm Maximum For Natural Propane and Butane Gases For Natural Propane and Butane Gases Note For this type of installation the verti...

Page 25: ...Maximum 1 1 2 ft 457 mm 3 ft 914 mm 3 ft 914 mm 6 ft 1 83 m 4 1 2 ft 1 37 m 9 1 2 ft 2 88 m 6 ft 1 83 m 12 ft 3 66 m V H Max 38 ft 11 58 m H Max 12 ft 3 66 m Propane One 90 Elbow System V Minimum H M...

Page 26: ...o 90 Elbows System V Minimum H Maximum H1 H2 Max 1 1 2 ft 457 mm 15 in 390 mm 2 1 4 in 690 mm 3 ft 914 mm 30 in 750 mm 4 1 2 ft 1 37 m 4 1 2 ft 1 37 m 3 1 2 ft 1 07 m 7 ft 2 13 m 6 ft 1 83 m 5 ft 1 52...

Page 27: ...4 57 m Propane Two 90 Elbows System V Minimum H Maximum H1 H2 Max 1 1 2 ft 457 mm 15 in 390 mm 2 1 4 in 69 cm 3 ft 914 mm 30 in 750 mm 4 1 2 ft 1 37 m 4 1 2 ft 1 37 m 3 1 2 ft 1 07 m 7 ft 2 13 m 6 ft...

Page 28: ...mm 2 ft 610 mm 4 ft 1 22 m 3 ft 914 mm 6 ft 1 83 m 4 ft 1 22 m 8 ft 2 44 m 5 ft 1 52 m 10 ft 3 05 m V1 V2 H Max 36 ft 10 97 m H Max 10 ft 3 05 m Propane Two 90 Elbows System V Minimum H1 H2 Maximum 2...

Page 29: ...ee 90 Elbows System V Minimum H Maximum H1 H2 Max 1 1 2 ft 457 mm 1 ft 305 mm 2 1 4 in 690 mm 3 ft 914 mm 2 ft 610 mm 4 1 2 ft 1 37 m 4 1 2 ft 1 37 m 3 1 2 ft 1 07 m 7 ft 2 13 m 6 ft 1 83 m 6 ft 1 83...

Page 30: ...90 Elbows System V Minimum H Maximum H1 H2 Max 1 1 2 ft 457 mm 1 ft 305 mm 1 3 4 ft 530 mm 3 ft 914 mm 2 ft 610 mm 3 1 2 ft 1 07 m 4 1 2 ft 1 37 m 3 1 2 ft 1 07 m 5 1 2 ft 1 68 m 6 ft 1 83 m 6 ft 1 83...

Page 31: ...to engage pipe then rotate counterclockwise to lock Step 1 Balanced flue pipe is designed with a locking connection To connect the flue system to the gas stove flue outlet Lock the flue components in...

Page 32: ...F PIPE INTERIOR WALL 2 in 51 mm clearance from rear of stove WALL THIMBLE MINIMUM OF 6 in 152 mm OF PIPE THROUGH THE WALL PIPE LENGTH PIPE LENGTH TRIM RING 90 ELBOW O Place m ark where protrudes throu...

Page 33: ...res A B and C on the next page CAUTION Risk of Cuts Abrasions or Flying Debris Wear protective gloves and safety glasses during installation Sheet metal edges are sharp 1 Assembling Slim Line Trim Rin...

Page 34: ...TO WALL STRAP WALL STRAP TWO 45 DEGREE ELBOWS METAL STRAP Step 2 Set the gas stove in its desired location Drop a plumb bob down from the ceiling to the position of the gas stove flue exit and mark t...

Page 35: ...otruding through the roof Secure the base of the flashing to the roof with roofing nails Ensure the roofing material overlaps the top edge of the flashing as shown in Figure 7 23 Verify that the chimn...

Page 36: ...rtical Flue Restrictor If the fireplace installation requires a vertical flue off the top of the unit with no horizontal flue or elbows the vertical flue restrictor must be added Reinstall heat shield...

Page 37: ...top must be placed on each side of an interior wall A minimum 1 1 2 inch 38 mm overlap of attached heat shields must be maintained See Section 10 H for information for regarding the installation of a...

Page 38: ...mm x 229 mm whenever the vent penetrates a ceiling floor see Figure 8 3 Frame the area with the same sized lumber as used in ceiling floor joist The ceiling firestop may be installed above or below t...

Page 39: ...n from getting between the shield and vent pipe and to maintain air space clearance Vaulted Ceiling Installation Remove one shield from box NOTICE Cut previously installed batt insulation to make room...

Page 40: ...driver to remove the two screws in the front of the bottom plate and the two screws holding the metal strap across the back of the gas stove Refer to Figure 9 2 for locations Figure 9 2 C Leveling and...

Page 41: ...Rear Flue Conversion KIT CONTENTS Top cover without hole Back panel with hole 1 Remove the front door assembly by pulling bottom of front away from gas stove and lifting it off of the hooks on top of...

Page 42: ...the four screws from the cover plate on rear of gas stove Set cover plate aside Retain screws See Figure 9 8 Attach DV adapter collar in its place Install the inner extension collar Figure 9 8 Figure...

Page 43: ...r gas stove Figure 9 13 Place log 1 into the cradle in the burner Lean the log back towards right corner of firebox Figure 9 14 Locate log 2 over the pin in log 1 and into notch in log 1 Lean the log...

Page 44: ...7 Position the four flat 6 mm spacer washers on the front door so that the four mounting screws pass through them Position the glass over the front door Install the four protective barrels into the gl...

Page 45: ...orange ignitor wire I and white sensor wire S from module Unscrew the pilot assembly bracket and remove the pilot assembly along with silicone sealant grommet M Parts Replacement Fan Unplug the fan f...

Page 46: ...tted and locked into the preceding component Commercial Multi family Multi level exceeding two stories or High Rise Applications For Installation into a commercial multi family multi level exceeding t...

Page 47: ...the outer flue of the slip section over the outer flue of the pipe section See Figure 10 3 Slide together to the desired length Figure 10 3 Slip Section Pilot Holes Figure 10 4 Screws into Slip Secti...

Page 48: ...system on the ceiling and drill a small hole through the ceiling and roof at this point Locate the hole and mark the outline of the cathedral ceiling support box on the outside roof Remove shingles or...

Page 49: ...for horizontal runs Place the pipe supports around the flue pipe Nail the pipe supports to the framing members For Vertical Runs The flue system must be supported every 8 ft 2 44 m above the fireplace...

Page 50: ...hield 38 mm min overlap Outer Flue H Flue Termination For Horizontal Terminations using the SLP TRAP To attach and secure the termination to the last section of horizontal flue The rear flue heat shie...

Page 51: ...at shield if the finished wall thickness is greater than 7 1 4 in 184 mm The extended heat shield may need to be cut to length maintaining sufficient length for a 1 1 2 in 38 mm overlap between heat s...

Page 52: ...ocate and mark the flue center point on the underside of the roof and drive a nail through the center point Make the outline of the roof hole around the center point nail The size of the roof hole fra...

Page 53: ...sk Check all fittings and connections Do not use open flame After the gas line installation is complete all connections must be tightened and checked for leaks with a commercially available non corros...

Page 54: ...ire or Explosion Support control when attaching pipe to prevent bending gas line A small amount of air will be in the gas supply lines WARNING Risk of Fire or Explosion Gas build up during line purge...

Page 55: ...6V DC C X 4 BROWN TO OPTIONAL COMPONENTS AUX300CE MODULE OPTIONAL 240V FAN OPTIONAL FAN AUX 1 AUX 2 S I GROUND TO CHASSIS TO AUX300CE TO JUNCTION CORD 220 240 VAC TO CORD ASSEMBLY 120VAC WALL SWITCH...

Page 56: ...ns OPTIONAL ACCESSORY Figure 12 2 Blower Diagram C Optional Accessories Requirements This appliance may be used with a wall switch wall mounted thermostat and or a remote control Wiring for optional H...

Page 57: ...remote control RC300AU is programmed to the control module Note that the control module will always ignite the fireplace on HI and remain so for the initial 10 seconds of operation If the HI LO is sw...

Page 58: ...hnician This remote control is tested and safe when installed in accordance with this installation manual Do not install any components that may be damaged Do not modify disassemble or substitute any...

Page 59: ...n the room temperature and set temperature portion Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules and EN298 f...

Page 60: ...nce 5 seconds later when ready See Figure 12 10 Using a small item such as a paper clip press and release the LEARN button located near the ON OFF REMOTE switch See Figure 12 10 Control module will be...

Page 61: ...off Use MENU button to display the menu functions Only functions that can be activated will be displayed For example Flame Height will not be displayed when the remote status is OFF Use the SELECT but...

Page 62: ...er the previous FLAME HEIGHT setting and will automatically adjust after 10 seconds Adjusting Fan Speed Press the MENU button to activate the menu Using the UP and DOWN arrows highlight the FAN icon a...

Page 63: ...child lock feature Notice No functions will be usable until child lock feature is disabled Power Outage If fireplace battery backup system IS installed at time of power outage fireplace operation wil...

Page 64: ...r button is pressed verify that the control module is plugged in the fire place junction box located in the controls area Also verify that the batteries are installed in the battery pack Fan does not...

Page 65: ...or 1 8 in 3 mm 2 Pilot won t light there is no noise or spark A No power transformer installed incorrectly or depleted batteries Verify that transformer is installed and plugged into module Check vol...

Page 66: ...sense lead is at least 0 14 microamps Verify correct pilot orifice is installed and gas inlet is set to pressure specifi cations Polish flame sensing rod with fine steel wool to remove any contaminan...

Page 67: ...e actual appliance dimensions Use for reference only For framing dimensions and clearances refer to Section 5 Figure 14 1 Appliance Dimensions A B G F H E Hearth Pad D C I Height includes 9 5 mm heart...

Page 68: ...h Pad B Appliance Dimension with Stone Surround Diagram Figure 14 2 Appliance Dimensions with Stone Surround Height includes 9 3 mm hearth pad Height includes 9 53 mm hearth pad A B C D E F G Inches 3...

Page 69: ...nspect for paint condition warpage corrosion or perforation Sand and repaint as necessary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly s...

Page 70: ...ective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 6 51 152 SLP12A 2 12 51 305 Effective Height Length SLP PIPE SLP WS Wall Shield F...

Page 71: ...in 384 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 10...

Page 72: ...nufacturing Date Active 1 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17 13 19 20 18 Part number list on following page Log Set Assembly Vertical Stove DV 12 14 VRT GY P AUB VRT BZ P AUB Ending Manufacturing Da...

Page 73: ...e collar SLP SA 4 DV Starting Collar 2189 002 5 Adapter Gasket 460 0610 6 Side Assembly Left Gray 2123 027 Black 2123 027 BK 7 Firebox Assembly 2123 004 8 Latch Assembly Upper 7003 006 9 Heat Shield 2...

Page 74: ...T0021039 2198 014 Post T0021039 2090 012 Pilot Assembly P Pre T0021039 2198 015 Post T0021039 2098 013 14 3 Pilot Bracket 2123 140 14 4 Burner Support 7031 279 14 5 3 Hole Grommet 2118 420 14 6 Valve...

Page 75: ...vice parts from your dealer or distributor ITEM DESCRIPTION COMMENTS PART NUMBER AUX300 CE 2166 340 Blower 240V 100 505A Blower Bracket 7031 194 Front Glass Gray PAL GLS GY Bronze PAL GLS BZ Flue Rest...

Page 76: ..._______________________________________________________________________________ ________________________________________________________________________________ _______________________________________...

Reviews: