Heat & Glo  •  ST-36TVB-IPI  •  2134-900 Rev. i  •  3/13

21

7

7

Vent Information and Diagrams 

 

B.  Vent System Confi guration

CAUTION! Risk of Fire! ALL vent confi guration  speci-
fi cations MUST be followed. This product is tested and 
listed to these specifi cations. Appliance performance will 
suffer if specifi cations are not  followed.

Rise to Run Ratio = 2:1

Maximum Total Horizontal Run = 15 ft.

Minimum Total Vertical Rise for 0-2 elbows = 12 ft.

Maximum Total Vertical Rise = 50 ft.

Maximum Number of Elbows:  four 90º or six 45º

Minimum Total Vertical Rise for four 90º or six 45º 
elbows=16 ft.

See Figures 7.1, 7.2, 7.3.

Figure 7.1 Minimum Total Vertical Rise

A. Vent Guidelines

WARNING! Fire Risk/Asphyxiation! This appliance re-
quires the specifi ed pipe for operation. Incorrect pipe may 
cause spillage, condensation and overheating.

Figure 7.2 Rise to Run Ratio

This model require the following size B-Vent double wall.

METAL

PLUMBERS' STRAP

MAXIMUM HORIZONTAL RUN IS 50%

OF VERTICAL. HORIZONTAL RUN

CANNOT BE MORE THAN 15 FT.

VENT SUPPORTS 

ARE PER VENT 

MANUFACTURER'S 

SPECIFICATIONS.

METAL 

PLUMBER’S

STRAP 

12 FEET
MINIMUM
50 FEET
MAXIMUM

VENT SUPPORTS ARE PER 

VENT MANUFACTURER’S 

SPECIFICATIONS

MINIMUM CLEARANCES

ARE PER VENT

 MANUFACTURER’S

SPECIFICATIONS

•  Follow pipe manufacturer’s installation guidelines when 

installing the appliance.

WARNING! Risk of Fire, Explosion or Asphyxiation! 
DO NOT 
connect this gas appliance to a chimney fl ue 
serving a separate solid-fuel or gas burning appliance.

•  Vent this appliance directly outside.

•  Use separate vent system for this appliance. 

May impair safe operation of this appliance or other appli-
ances connected to the fl ue.

WARNING! Risk of Fire or Explosion! Insulation and 
other combustibles must not infringe on clearances.

•  ALWAYS maintain specifi ed clearances around venting 

and fi restop systems.

• Install fi restops as specifi ed.

Failure to keep insulation or other material away from vent 
pipe may cause fi re.

Figure 7.3 Proper Use of Elbows

45 DEGREES

ELBOW

90 DEGREES

ELBOW

OFFSETS EXCEEDING

45 DEGREES ADAPT 

HORIZONTAL LIMITATIONS

MAXIMUM

HORIZONTAL

15 FEET

MINIMUM

VERTICAL

9 FEET

Note:

 Maximum horizontal 

distance is 50% vertical vent 
height.

Models

Pipe Size

ST-36TVB-IPI

5 inches

Summary of Contents for ST-36TVB-IPI

Page 1: ...use and operation DO NOT DISCARD WARNING Important operating and maintenance instructions included Read understand and follow these instructions for safe installation and operation In the Commonwealth...

Page 2: ...e utilise avec avec un un combustible combustible solide solide This This appliance appliance must must be be installed installed in in accordance accordance with with local local codes codes if if an...

Page 3: ...pplies Needed 15 D Inspect Appliance and Components 15 E Negative Pressure 16 5 Framing and Clearances A Selecting Appliance Location 17 B Constructing the Appliance Chase 18 C Clearances 18 D Mantel...

Page 4: ...VB IPI 2134 900 Rev i 3 13 4 Contains updated information 15 Troubleshooting A Intellifire Ignition System 40 16 Reference Materials A Appliance Dimension Diagram 42 B Service Parts List 45 C Contact...

Page 5: ...ase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer dis...

Page 6: ...ED ABOVE WARRANTY EXCLUSIONS This warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surf...

Page 7: ...n Materials made of or surfaced with wood compressed pa per plant fibers plastics or other material that can ignite and burn whether flame proofed or not or plastered or unplastered shall be considere...

Page 8: ...help is needed to properly install one HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow childre...

Page 9: ...event direct contact with the fixed glass panel DO NOT operate the fireplace with the barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to...

Page 10: ...r because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building...

Page 11: ...utes Odor from fireplace When first operated this fireplace may release an odor for the first several hours This is caused by the curing of materials from manufacturing Odor may also be released from...

Page 12: ...servicing When properly maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surrounds Fronts Frequency Annua...

Page 13: ...ese areas Screw tips that have penetrated the sheet metal are sharp and should be avoided Remove all foreign objects Verify unobstructed air circulation Burner Ignition and Operation Frequency Annuall...

Page 14: ...S ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS SECTION 8B FRAMING HEADED OFF IN CEILING JOISTS SECTION 8B GAS LINE SECTION 11 MANTEL AND MANTEL LEG SECTION 5 D SURROUND HEARTH EXTENSION VENT PIPE SE...

Page 15: ...ce any part of the control system and or gas control which has been under water Improper installation adjustment alteration service or maintenance can cause injury or property damage For as sistance o...

Page 16: ...appliances and exhaust equipment Ensure furnace and air conditioning return vents are not located in the immediate vicinity of the fireplace Avoid installing the fireplace near doors walkways or smal...

Page 17: ...Burns Provide adequate clearance around air openings and for service access Due to high temperatures the appliance should be locat ed out of traffic and away from furniture and draperies NOTICE Illust...

Page 18: ...aces extending full width and depth DO NOT install directly on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to applianc...

Page 19: ...ll Combustible Mantel Legs or Wall Projections Figure 5 6 Non Combustible Zone SHEETROCK AIR SPACE REQUIRED 3 1 4 in D Mantel and Wall Projections WARNING Risk of Fire Comply with all minimum clear an...

Page 20: ...insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire WARNING VERTICAL WALL LISTED B VENT TERMINATION CAP 12 X ROOF PITCH IS X...

Page 21: ...UPPORTS ARE PER VENT MANUFACTURER S SPECIFICATIONS METAL PLUMBER S STRAP 12 FEET MINIMUM 50 FEET MAXIMUM VENT SUPPORTS ARE PER VENT MANUFACTURER S SPECIFICATIONS MINIMUM CLEARANCES ARE PER VENT MANUFA...

Page 22: ...instructions to provide adequate clear ances Use same size framing materials as those used in the wall or ceiling construction Firestop spacers must be used in wall and ceiling penetrations per the B...

Page 23: ...may result Remove and discard cover plate or knockout from side of appliance Open air kit damper slightly Locate door hinge toward back of appliance see Figure 9 1 9 9 Appliance Preparation Figure 9...

Page 24: ...ppliance into position making sure to maintain proper clearance to combustibles 2 Level the appliance from side to side and front to back It is acceptable to use wood shims under the appliance 3 Faste...

Page 25: ...Shield WARNING Fire Risk DO NOT allow loose materials or insulation to touch vent Hearth Home Technologies Inc requires the use of an attic shield The National Fuel Gas Code ANSI Z223 1 and NFPA 54 re...

Page 26: ...flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Exp...

Page 27: ...verride IPI safety lockout Refer to Figures 12 1 and 12 2 Intellifire Pilot Ignition IPI Wiring Diagram This appliance is equipped with an Intellifire control valve which operates on a 3 volt system P...

Page 28: ...lifire Ignition Wiring Diagram with Wall Switch RED VALVE TRANSFORMER 3V BLACK B R O W N WIRE ASSEMBLY GROUND TO FIREPLACE CHASSIS TEMP SENSOR BATTERY PACK ORG GREEN B R O W N PLUG IN BLACK BLACK WHIT...

Page 29: ...Ignition Wiring Diagram with Remote Receiver RED VALVE TRANSFORMER 3V BLACK B R O W N GROUND TO FIREPLACE CHASSIS TEMP SENSOR BATTERY PACK ORG GREEN B R O W N PLUG IN BLACK BLACK REMOTE RECEIVER PLUG...

Page 30: ...rough the knockout making sure to use a Romex connector to fasten the electrical wires to the unit Pull enough wire into the valve compartment to easily reach the junction box location Remove the scre...

Page 31: ...the appliance during the installation process before finishing work on the whole hearth is complete Splatter guards may be factory installed or accompany the door of the unit depending on the fire pla...

Page 32: ...and fold up the panel as shown in Figure 13 8 Disengage the tabs on left and right bottom of splatter guard and fit them into the square holes The tabs are now inside the front of the splatter guard c...

Page 33: ...8 7 6 1 2 3 4 5 6 12 32 MAX MIN TO CEILING Figure 13 13 Minimum Vertical and Maximum Horizontal Dimensions of Non Combustibles C Facing Material Metal front faces may be covered with non combustible m...

Page 34: ...7 Inside Any 13 18 Halston Overlap 1 inch 13 17 Inside 1 inch 2 inch 13 19 Chateau Overlap 1 inch 13 17 Inside Any 13 18 Valencia Overlap 1 inch 13 17 Inside Any 13 18 Galleria Overlap 1 inch 13 17 In...

Page 35: ...See Note 2 KENWOOD MANTEL AFKDMPB 0 See Note 3 0 27 3 8 in KENWOOD MANTEL W BASE AFKDMPB W HTKDMPB 9 1 4 in 235 mm 29 3 8 in LAURENT SURROUND LAURENT 36 1 1 2 in 38 mm N A CAMDEN SURROUND CAM36PG 0 N...

Page 36: ...r material annually Improperly placed embers interfere with proper burner operation Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over...

Page 37: ...nside of the fireplace See Figure 1 Remove the microfoam and inspect the logs for damage Inspect the four factory installed logs for damage Locate the pilot in order to verify your position in relatio...

Page 38: ...top of the end of log C STEP 4 Log 3 SRV2128 707 The bottom end of log 3 should come in contact with the far left grate tine Mate the bottom of log 3 with the indentations on Log D and the top of Log...

Page 39: ...er Figure 14 2 Fixed Glass Assembly G Fixed Glass Assembly WARNING Risk of Asphyxiation Handle fixed glass assembly with care Inspect the gasket to ensure it is undamaged and inspect the glass for cra...

Page 40: ...parker wire or cracked insulator around electrode Replace pilot if necessary 2 Pilot won t light there is no noise or spark a No power or transformer installed incorrectly Verify that transformer is i...

Page 41: ...hould glow shortly after ignition Verify cor rect pilot orifice is installed and gas inlet is set to pressure specifications c Module is not grounded Verify module is securely grounded to metal chassi...

Page 42: ...g dimensions and clearances refer to Section 5 Figure 16 1 Appliance Dimensions Location Inches Millimeters I 4 1 4 108 J 24 610 K 12 305 L 21 5 16 541 M 5 127 N 38 965 O 1 25 Location Inches Millimet...

Page 43: ...________________________ ________________________________________________________________________________ ________________________________________________________________________________ _____________...

Reviews: