Heat & Glo SL350TRSI-N-CE Owner'S Manual Download Page 44

Heat & Glo  •  SL350TRSI-N-CE, SL350TRSI-PB-CE  •  2033-980 Rev. J  •  3/13

44

Figure 9.17  Fixed Glass Assembly

GLASS

ASSEMBLY

LATCHES

(BOTH BOTTOM 

AND TOP)

E.  Covers Removal For Servicing

Control Compartment Access Door

•  Lift the lower door up and out to access the gas controls.

Trim Door and Glass Door

•  Lift the front trim door up and out away from the appliance 

side  surrounds.  Replace  the  door  when  servicing  is 

complete.

•  Noting carefully how the brackets fit on the glass, release 

the two spring latches at the top and two at the bottom 

of the glass door. Carefully lift the glass up and out away 

from the appliance. See Figure 9.17.

Pilot Assembly/Ignition System

•  Remove the log set, log grate and burner assembly.
•  Disconnect the gas supply tube from the outlet side of 

valve.

•  Disconnect the orange ignitor wire (I) and white sensor 

wire (S) from module.

•  Unscrew  the  pilot  assembly  bracket  and  remove,  the 

pilot assembly along with silicone sealant grommet.  

G.  Parts Replacement

Fan

•  Unplug the fan from the AUX300CE and slide the fan out 

the front of the lower controls compartment.

•  Fan can be operated at 3 speed levels using RC300CE 

remote and AUX300CE.  Refer to RC300CE section.

•  The fan will automatically turn on after 3 minutes and will 

stop 12 minutes after unit has been turned off.

Glass Panel

•  To replace the glass door, place the bottom edge into 

the lower holders, push glass against unit and secure 

the two spring latches at the top and bottom.

H.  Adjustments And Replacement Parts

Adjustments  and  replacement  parts  for  this  appliance 

should only be done by a qualified service person.  A wir-

ing diagram for the appliance is shown in Section 12.  A 

service parts list is shown in Section 16 of this manual.

I.  Install Trim and/or Surround

•  Install  optional  trim  kits  and/or  surrounds  using  the 

instructions included with the accessory.

•  Use non-combustible materials to cover the gap between 

the sheet rock and the appliance (when applicable to the 

model).

J.  Air Shutter Setting

Figure 9.18

F.   Components Removal For Service

•  Release  the  screws  at  the  base  of  the  log  grate  and 

carefully lift up and remove the logs and log grate.

•  Remove the base pan.
•  Unscrew the brackets at both ends of the burner and 

the top two screws locating the pilot bracket (see Figure 

9.18). Slide the burner away from the burner orifice.

NOTICE: 

All screws which were removed must be replaced.

PILOT BRACKET

RETAINING SCREWS

Fixed Glass Assembly

WARNING!  Risk  of  Asphyxiation! 

Handle  fixed  glass 

assembly  with  care.  Inspect  the  gasket  to  ensure  it  is 

undamaged  and  inspect  the  glass  for  cracks,  chips  or 

scratches. 

• 

DO NOT

 

strike, slam or scratch glass.

• 

DO NOT

 

operate fireplace with glass removed, cracked, 

broken or scratched.

 

• 

Replace as a complete assembly.

Removing Fixed Glass Assembly

•  Pull the four glass assembly latches out of the groove on 

the glass frame. Remove glass door from the appliance 

(see Figure 9.17).

Replacing Fixed Glass Assembly

•  Replace the glass door on the appliance. Pull out and 

latch the four glass assembly latches into the groove on 

the glass frame.

Natural Gas Propane

Butane

SL350TRSI-N-CE

1/4 in.

(0,64 cm)

N/A

N/A

SL350TRSI-PB-CE

N/A

3/8 in.

(0,95 cm)

7/16 in.

(1,11 cm)

Summary of Contents for SL350TRSI-N-CE

Page 1: ... or help is needed to properly install one HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other ...

Page 2: ... and any local authorities requirements for gas electrical and building regulations This appliance and its components are tested and safe when installed in accordance with this Installation Manual Report to your dealer any parts damaged in shipment specifically check glass condition The gas logs and flue system components are in separate packages Read all instructions before starting installation ...

Page 3: ...ion contained in this owner s manual unless noted otherwise applies to all models and gas control systems Your new Heat Glo gas fireplace will give you years of durable use and trouble free enjoyment Welcome to the Heat Glo family of fireplace products We recommend that you record the following pertinent information about your fireplace Serial Number Type of Gas The model information regarding you...

Page 4: ... D Inspect Appliance and Components 19 5 Framing and Clearances A Selecting Appliance Location 20 B Constructing the Appliance Chase 21 C Clearances 21 D Mantel and Wall Projections 23 6 Termination Locations A Vent Termination Minimum Clearances 24 7 Vent Information and Diagrams A Approved Pipe 26 B Vent Table Key 26 C Use of Elbows 26 D Measuring Standards 26 E Vent Diagrams 26 8 Vent Clearance...

Page 5: ...pliance Setup A Remove Fixed Glass Assembly 64 B Remove the Shipping Materials 64 C Clean the Appliance 64 D Accessories 64 E Log Placement Instructions 65 15 Troubleshooting A IntelliFire Plus Ignition System 68 16 Reference Materials A Appliance Dimension Diagram 70 B Maintenance Tasks 71 C Vent Components Diagrams 72 D Service Parts 77 E Contact Information 80 ...

Page 6: ...se of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier The warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupancy date The warranty period for parts ...

Page 7: ...s in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enameled surfaces caused by fingerprints accidents misuse scratches melted items or other external sources and residues left on the plated surfaces from the use of abrasive c...

Page 8: ... Guide have been tested to certification standards and listed by the applicable laboratories This appliance must be installed in accordance with the rules in force NOX Class 5 for G20 NOX Class 5 for G31 B Additional Related Standards The installation must comply with these installation instruc tions and all relevant parts of Local and National Building Standards Regulations and those relevant rec...

Page 9: ...g entirely of steel iron brick tile concrete slate glass or plasters or any combination thereof Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC and UL763 shall be considered non combustible materials F Combustible Materials Specification Materials made of or surfaced with wood compressed pa per plant fibers plast...

Page 10: ...r is not present or help is needed to properly install one HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite cl...

Page 11: ...ng materials have been removed from inside and or underneath the firebox Review proper placement of logs ember material and or other decorative materials Check the wiring Check the air shutter adjustment Ensure that there are no gas leaks Ensure that the glass is sealed and in the proper position and that the integral barrier is in place WARNING Risk of Fire or Asphyxiation DO NOT op erate firepla...

Page 12: ... the flame output will automatically drop to the lowest setting after the flame has been established for 10 sec After this 10 second period the flame can be adjusted from HI to LO with the switch 3 The control module has safety feature that automatically shuts down the fireplace after 9 hours of continuous operation without receiving a command from the RC300CE remote 4 If you intend to use both an...

Page 13: ... TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT LINE VOLT AGE 110 120 VAC OR 220 240 VAC TO THE CONTROL VALVE Improper installation adjustment al teration service or maintenance can cause injury or property damage Re fer to the owner s information manual provided with this appliance This appliance needs...

Page 14: ...replace may release an odor for the first several hours This is caused by the curing of materials from manufacturing Odor may also be released from finishing materials and adhesives used near the fireplace These circumstances may require additional curing related to the installation environment Film on the glass This is a normal result of the curing process of the paint Glass should be cleaned wit...

Page 15: ...d your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surrounds Fronts Frequency Annually By Homeowner Tools needed Protective gloves stable work surface Assess condition of screen and replace as necessary Inspect for scratches dents or other damage and repair as necessary Check that louvers are not blocked Vacuum and...

Page 16: ...es sary Refer to Section 14 for log placement instructions Verify correct log placement and no flame impingement causing sooting Correct as necessary Firebox Frequency Annually By Qualified Service Technician Tools needed Protective gloves sandpaper steel wool cloths mineral spirits primer and touch up paint Inspect for paint condition warped surfaces corrosion or perforation Sand and repaint as n...

Page 17: ...and ignition carryover to all ports Verify that there is no ignition delay Inspect for lifting or other flame problems Verify air shutter setting is correct See Section 9 for required air shutter setting Verify air shutter is clear of dust and debris Inspect orifice for soot dirt and corrosion Verify orifice size is correct See Service Parts List for proper orifice sizing Verify manifold and inlet...

Page 18: ... CEILING JOISTS SECTION 8 C GAS LINE SECTION 11 MANTEL AND MANTEL LEG SECTION 5 D SURROUND HEARTH EXTENSION VENT PIPE SECTIONS 7 8 OPTIONAL WALL SWITCH SECTION 12 C STORM COLLAR SECTION 10 K NON COMBUSTIBLE ROOF FLASHING MAINTAINS MINIMUM CLEARANCE AROUND PIPE SECTION 10 J FRAMING HEADER SECTION 5 C ATTIC INSULATION SHIELD NOT SHOWN MUST BE USED HERE TO KEEP INSULATION AWAY FROM VENT PIPE IF ATTIC...

Page 19: ...sion Damaged parts could impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry C Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Manometer Hammer Phillips screwdriver Gloves Framing square Voltmeter Electric drill and bits 1 4 in Plumb...

Page 20: ...nd are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 5 1 Appliance Locations REAR FLUE HORIZONTAL TERMINATION TWO 90º ELBOWS REAR FLUE NO ELBOWS REAR FLUE ONE 90º ELBOW ALCOVE INSTALLATION TOP FLUE ONE 90º ELBOW A B J C K E B B B I D D F G H 7 6 cm N D A L M NOTE THE REAR STANDOFF MAY NEED TO BE REMOVE...

Page 21: ...all directly on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to appliance and vent pipe Insulation and other materials must be secured to prevent accidental contact The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney Failure to...

Page 22: ...Models A B C D E F G H I J DVP Pipe SLP Pipe Rough Opening Height DVP Pipe SLP Pipe Rough Opening Width Clearance to Ceiling Combustible Floor Combustible Flooring Behind Appliance Sides of Appliance Front of Appliance Rough Opening Width Rough Opening Width Rough Opening Depth Rough Opening Depth SL350TRSI N CE SL350TRSI PB CE in 10 8 5 8 32 3 4 16 1 4 16 1 4 34 32 0 0 1 2 1 2 36 cm 25 4 21 9 83 ...

Page 23: ...tible zone Figure 5 7 7 6 15 2 17 8 20 3 22 9 27 9 30 5 5 1 7 6 10 2 12 7 30 5 27 9 25 4 22 9 20 3 17 8 15 2 5 1 10 2 12 7 25 4 TOP FRONT EDGE OF FIREPLACE NON COMBUSTIBLE BOARD If joints between the finished walls and the fireplace sur round top and sides are sealed a 150º C minimum seal ant material must be used These joints are not required to be sealed Only non combustible material using 150 c...

Page 24: ...nstructions supplied with the decorative cap cover In a staggered installation with both gas and wood or fuel oil terminations the wood or fuel oil termination cap must be higher than the gas termination cap A B 15 2 cm minimum up to 50 8 cm 45 7 cm minimum 50 8 cm and over 0 mm minimum Figure 6 1 Minimum Height From Roof To Lowest Discharge Opening Angle H Min cm 0 26 6 30 26 6 30 3 38 30 3 33 7 ...

Page 25: ...ing and soffits 1 There must be 91 m minimum between termination caps 2 All mechanical air intakes within 3 m of a termination cap must be a minimum of 91 m below the termination cap 3 All gravity air intakes within 91 m of a termination cap must be a minimum of 30 m below the termination cap See Note 1 See Note 2 Note 3 Local codes or regulations may require different clearances Note 4 Terminatio...

Page 26: ...asuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards Pipe measurements are shown using the effective length of pipe see Figures 7 2 and 7 3 Measurements are made from the appliance outer wrap not from the standoffs Horizontal terminations are measured to the outside mounting surface flange of termination cap Vertical termination...

Page 27: ...venting and firestop systems Install wall shield and ceiling firestops as speci fied Failure to keep insulation or other material away from vent pipe may cause fire WARNING Example DVP pipe 3 ft 91 4 cm min vertical 11 ft 3 35 m max horizontal SLP pipe 7 ft 2 13 m min vertical 11 ft 3 35 m max horizontal V1 Minimum H1 Maximum Elbow only NOT ALLOWED 1 ft 30 5 cm 2 ft 61 0 cm 2 ft 61 0 cm 4 ft 1 22 ...

Page 28: ...5 2 cm 1 ft 30 5 cm 1 ft 30 5 cm 2 ft 61 0 cm 2 ft 61 0 cm 4 ft 1 22 m 3 ft 91 4 cm 6 ft 1 83 m 4 ft 1 22 m 8 ft 2 44 m 5 ft 1 52 m 10 ft 3 05 m 30 ft 9 14 m 10 ft 3 05 m V1 H1 H2 30 ft 9 14 m Maximum H1 H2 10 ft 3 05 m Maximum INSTALLED HORIZONTALLY H1 H2 V1 USE SLP SERIES COMPONENTS ONLY Note A 15 2 cm section of straight flue must be attached to the fireplace before a 90 elbow ...

Page 29: ...t 61 0 cm 2 ft 61 0 cm 2 ft 61 0 cm 3 ft 91 4 cm 4 ft 1 22 m 3 ft 91 4 cm 3 ft 91 4 cm 4 ft 1 22 m 6 ft 1 83 m 4 ft 1 22 m 4 ft 1 22 m 5 ft 1 52 m 8 ft 2 44 m 5 ft 1 52 m 6 ft 1 83 m 6 ft 1 83 m 12 ft 3 66 m H1 6 ft 1 83 m Maximum H1 H2 12 ft 3 66 m Maximum V1 V2 32 ft 9 75 m Maximum V1 V2 H1 H2 36 ft 10 97 m Maximum H2 H1 V2 V1 USE SLP SERIES COMPONENTS ONLY Note A 15 2 cm section of straight flu...

Page 30: ...s Comply with all minimum clearances to combustibles as specified in this manual Overlapping material could ignite and will in terfere with proper operation of doors and louvers Horizontal sections 3 inches 7 62 cm from the top of the pipe Horizontal sections 2 1 2 inches 6 35 cm at wall shield firestops Horizontal sections 1 inches 2 54 cm from sides and bottom of the pipe Vertical sections 1 inc...

Page 31: ...horizontal run in flue configurations using 90 elbows MUST BE strictly adhered to The rise to run relationships are shown in the flueing drawings and tables on the next few pages WARNING Risk of Fire This gas appliance and flue as sembly must flue directly to the outside and must never be attached to a chimney serving a separate solid fuel burning appliance Each gas appliance must use a sepa rate ...

Page 32: ...ction of straight flue must be attached to the fireplace before a 90 elbow V1 H1 Maximum V2 V1 V2 Min Elbow only Not allowed 6 in 15 2 cm 2 ft 61 0 cm 1 ft 30 5 cm 4 ft 1 22 m 2 ft 61 0 cm 6 ft 1 83 m 3 ft 91 4 cm 8 ft 2 44 m 4 ft 1 22 m 12 ft 3 66 m 5 ft 1 52 m 16 ft 4 87 m V1 V2 H1 36 ft 10 97 m Maximum No specific restrictions on this value EXCEPT V1 V2 cannot exceed 32 ft 9 75 m ...

Page 33: ...61 0 cm 2 ft 61 0 cm 1 ft 30 5 cm 2 ft 61 0 cm 2 ft 61 0 cm 2 ft 61 0 cm 4 ft 1 22 m 4 ft 1 22 m 3 ft 91 4 cm 6 ft 1 83 m 6 ft 1 83 m 4 ft 1 22 m 8 ft 2 44 m 8 ft 2 44 m 5 ft 1 52 m 12 ft 3 66 m 12 ft 3 66 m H1 H2 12 ft 3 66 m Maximum V1 V2 H1 H2 32 ft 9 75 m Maximum INSTALLED HORIZONTALLY H1 H2 V1 V2 USE SLP SERIES COMPONENTS ONLY Note A 15 2 cm section of straight flue must be attached to the fi...

Page 34: ... Vent Horizontal Termination Figure 7 13 No Elbow One 45º Elbow H1 H1 Minimum H1 Maximum 6 1 2 in 16 5 cm 18 in 45 7 cm Do not use a 45º elbow in corner installations Use two 90º elbows instead Figure 7 12 H USE DVP SERIES COMPONENTS ONLY USE DVP SERIES COMPONENTS ONLY ...

Page 35: ... 22 m 4 ft 1 22 m 6 ft 1 83 m 10 ft 3 05 m V1 H1 H2 30 ft 9 14 m Maximum H1 4 ft 1 22 m Maximum H1 H2 10 ft 3 05 m Maximum H1 Maximum V1 Minimum H2 H3 H1 H2 H3 Max 0 ft 0 cm Back to Back 90º Elbows 1 ft 30 5 cm 1 ft 30 5 cm 6 in 15 2 cm 6 in 15 2 cm 1 ft 30 5 cm 1 1 2 ft 45 7 cm 1 ft 30 5 cm 1 ft 30 5 cm 1 ft 30 5 cm 2 ft 61 0 cm 2 ft 61 0 cm 2 ft 61 0 cm 2 ft 61 0 cm 4 ft 1 22 m 3 ft 91 4 cm 3 ft...

Page 36: ... ft 2 44 m 4 ft 1 22 m 11 ft 3 35 m 5 ft 1 52 m 12 ft 3 66 m V1 H1 36 ft 10 97 m Maximum H1 12 ft 3 66 m Maximum V1 Minimum H1 H2 Maximum 2 ft 61 0 cm Back to Back 90º Elbows 1 ft 31 0 cm 3 ft 91 5 cm 2 ft 61 0 cm 4 ft 1 22 m 3 ft 91 4 cm 8 ft 2 44 m 4 ft 1 22 m 10 ft 3 05 m V1 H1 32 ft 9 75 m Maximum H1 H2 9 ft 2 74 m Maximum V1 H1 INSTALLED HORIZONTALLY H1 H2 V1 USE DVP SERIES COMPONENTS ONLY US...

Page 37: ...5 m 8 ft 2 44 m V1 H1 H2 H3 32 ft 9 75 m Maximum No specific restrictions on this value EXCEPT V1 H1 H2 H3 cannot exceed 32 ft 9 75 m Maximum H1 H2 H3 8 ft 2 44 m Maximum H1 Maximum V1 Minimum H2 H1 H2 Maximum 6 in 15 2 cm 6 in 15 2 cm 6 in 15 2 cm 1 ft 30 5 cm 1 ft 30 5 cm 1 ft 30 5 cm 1 ft 30 5 cm 2 ft 61 0 cm 2 ft 61 0 cm 2 ft 61 0 cm 3 ft 91 4 cm 4 ft 1 22 m 3 ft 91 4 cm 3 ft 91 4 cm 6 ft 1 83...

Page 38: ...med If wall thickness is greater than 7 5 8 in 19 4 cm a DVP HSM B will be required DVP SLP Pipe Shown 3 in 7 6 cm top clearance 1 in 2 5 cm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 7 6 cm top clearance 1 in 2 5 cm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 7 6 cm top clearance 1 in 2 5 cm clearance around vertical sections B ...

Page 39: ...25 4 cm by 25 4 cm whenever the vent penetrates a ceiling floor see Figure 8 3 SLP pipe only Frame opening 9 in x 9 in 22 9 cm x 22 9 cm whenever the vent penetrates a ceiling floor see Figure 8 3 Frame the area with the same sized lumber as used in ceiling floor joist The ceiling firestop may be installed above or below the ceiling joists when installed with a attic insulation shield It must be u...

Page 40: ...t blown insulation from getting between the shield and vent pipe and to maintain air space clearance Figure 8 5 Attic Insulation Shield Vaulted Ceiling Installation Remove one shield from box NOTICE Cut previously installed batt insulation to make room for the attic insulation shield Cut the attic insulation shield if application is for vaulted ceiling to fit your ceiling pitch Snip cut edge to re...

Page 41: ...on as shown above The heat shield must remain in the vertical position Figure 9 4 Remove the seal cap Figure 9 5 Remove the insulation basket and white insula tion from the center vent pipe Figure 9 1 For top vent remove the two screws holding the top heat shield in place For rear vent see Section 9 B Note Actual unit may look different than the fireplace shown in this section 2 SCREWS 2 SCREWS Fi...

Page 42: ...ve the seal cap Figure 9 11 Discard the seal cap remove and discard the insulation basket Note Once the seal cap has been removed it CANNOT be reattached Figure 9 12 Attach the first vent section it will snap into place Slide the insulation gasket onto the vent section up against the appliance and over the tabs Use two self tapping screws to secure gasket to outer wrap Figure 9 7 To attach the fir...

Page 43: ...otch the framing around the appliance standoffs Failure to maintain air space clearance may cause overheating and fire The diagram shows how to properly position and secure the appliance see Figure 9 16 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing Level the appl...

Page 44: ... Adjustments and replacement parts for this appliance should only be done by a qualified service person A wir ing diagram for the appliance is shown in Section 12 A service parts list is shown in Section 16 of this manual I Install Trim and or Surround Install optional trim kits and or surrounds using the instructions included with the accessory Use non combustible materials to cover the gap betwe...

Page 45: ...les DO NOT penetrate inner pipe For 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 1 3 cm If predrilling screw holes DO NOT penetrate inner pipe Commercial Multi family Multi level exceeding two sto ries or High Rise ...

Page 46: ...e slip section elbow and cap outer flues shall be sealed in this manner unless otherwise stated Figure 10 5 Adding Venting Components WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when remov ing termination cap from slip pipe If slip section seals are broken during removal of the termination cap vent may leak Note Align seams to engage pipe then rotate cou...

Page 47: ...f SLP pipe must be supported every 8 ft 2 44 m Horizontal sections must be supported every 5 feet 1 52 m Vent supports or plumbers strap spaced 120º apart may be used to support vent sections See Figures 10 8 and 10 9 Wall shield firestops may be used to provide horizontal support vent sections SLP ceiling firestops have tabs that may be used to provide vertical support WARNING Risk of Fire Explos...

Page 48: ...lace the pipe supports around the flue pipe Nail the pipe supports to the framing members For Vertical Runs The flue system must be supported every eight feet 2 44 m above the fireplace flue outlet by wall brackets To install support brackets for vertical runs Attach wall brackets to the flue pipe and secure the wall bracket to the framing members with nails or screws For Vertical Runs One firesto...

Page 49: ...d 3 8 cm min overlap Outer Flue H Flue Termination For Horizontal Terminations using the DVP TRAP To attach and secure the termination to the last section of horizontal flue The rear flue heat shield MUST be placed one inch 2 54 cm above the top of the flue between the wall shield and the base of the termination cap One section of the heat shield is attached to the wall shield The other is attache...

Page 50: ...on is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 10 17 If the wall thickness does not allow the required 1 1 2 in 3 8 cm heat shield overlap when installed an extended heat shield must be used If the wall thickness is less than 4 in 10 2 cm DVP or 4 3 8 in 11 1 cm SLP the heat shields on the cap and wall shield firestop must be tricmed ...

Page 51: ...Vertical Termination Cap Locate and mark the flue center point on the underside of the roof and drive a nail through the center point Make the outline of the roof hole around the center point nail The size of the roof hole framing dimensions depend on the pitch of the roof There MUST BE a 1 inch 2 5 cm clearance from the vertical flue pipe to combustible materials Mark the roof hole accordingly Co...

Page 52: ...or could damage valve WARNING Fire Risk Explosion Risk High pressure will damage valve Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 60 mbar Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 60 mbar Columns highlighted in gray The gas control valve supplied with this product is approved for a maximum inle...

Page 53: ...leak check solution following testing DO NOT USE AN OPEN FLAME Notice the gas supply line should be purged of any trapped air prior to the first firing of the unit Refer to Reference Section 16 for location of gas line access in appliance Gas line may be run through knockout s provided The gap between supply piping and gas access hole may be caulked with high temperature caulk 150 C minimum contin...

Page 54: ...to the appliance wall switch In correct wiring will damage controls NOTICE The mains supply to the appliance must have isolation of a minimum 3 mm contact separation in both poles WARNING Risk of Injury The gas supply shall be shut off prior to disconnecting the electrical power and remov ing batteries if installed before proceeding with any maintenance to the appliance B IntelliFire Plus Ignition...

Page 55: ...y installed be connected to 230 VAC service before per manently enclosing the fireplace The access hole for connecting the service wires is found on the right exterior side of the unit See Figure 12 3 for wire connection de tail Note if any of the original wire as supplied with the appliance must be replaced it must be replaced with type 105º C rated wire Wires must have high temperature insulatio...

Page 56: ...ervice technician This remote control is tested and safe when installed in accordance with this installation manual Do not install any components that may be damaged Do not modify disassemble or substitute any of the com ponents included with this kit Installation of this unit must be done by a qualified service technician Placement of this remote control may affect performance An assessment of th...

Page 57: ...matically change the indicators on the room temperature and set temperature portion Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules and EN298 for multi functional control These limits are designed to provide reasonable protection against harmful inter ference in a residential installation This equipment gener...

Page 58: ... the control module will beep once 5 seconds later when ready See Figure 12 11 Using a small item such as a paper clip press and release the LEARN button located near the ON OFF REMOTE switch See Figure 12 11 Control module will beep once and LED will blink green for 10 seconds While the LED is blinking press the POWER button on the remote control A double beep will come out of the control module ...

Page 59: ...e if no but tons are pressed within 5 seconds Press any button to resume full functionality In idle mode only active func tions will show on the screen Standby mode The remote control will go into a standby mode if no but tons are pressed within 5 minutes Press the POWER button to reactivate the remote control to ON mode Ac tive functions will be displayed Menu Select V V Menu Select V V Menu Sele...

Page 60: ...em will remember the previous FLAME HEIGHT setting and will automatically adjust after 10 seconds Adjusting Fan Speed Press the MENU button to activate the menu Using the UP and DOWN arrows highlight the FAN icon and press SELECT Use the UP and DOWN arrows to adjust the FAN SPEED then press SELECT The FAN SPEED can be adjusted to 3 different settings HIGH MEDIUM LOW Notice The fan has a timer buil...

Page 61: ...tivated A double beep will come from the control module indicating CONSTANT PILOT has been deactivated Setting the Child Lock Press and hold the MENU and UP arrow buttons simul taneously for 4 seconds to enable or disable the child lock feature Notice No functions will be usable until child lock feature is disabled Power Outage If fireplace battery backup system IS installed at time of power outag...

Page 62: ... on when power button is pressed verify that the control module is plugged in the fire place junction box located in the controls area Also verify that the batteries are installed in the battery pack Fan does not turn on when fireplace is started Built in time delay The fireplace must run for three minutes in order for the fan to engage Fan does not turn off when fireplace turned off Built in time...

Page 63: ...vice Facing and or finishing materials must never overhang into the glass opening Observe all clearances when applying combustible materials Seal joints between the finished wall and appliance top and sides using a 300 ºF 149 ºC minimum sealant WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all minimum clearances to combustibles as specified in th...

Page 64: ...ccumulated inside the firebox or underneath in the control cavity D Accessories Install approved accessories per instructions included with accessories Contact your dealer for a list of ap proved accessories WARNING Risk of Fire and Electric Shock Use ONLY Hearth Home Technologies approved optional acces sories with this appliance Using non listed accessories could result in a safety hazard and wi...

Page 65: ...re fragile Log 1 srv327 701 Place log 1 at the rear of the unit with the left edge behind the tab on the pilot bracket The right side sits behind the tab on the support bracket Log 2 srv2033 701 Locate the bottom groove of log 2 over the left most grate tine and align over the burner by placing the log slot over the burner tab as shown 1 2 2 SUPPORT BRACKET BURNER TABS PILOT BRACKET TAB 1 ...

Page 66: ...nt grate corner and place its slot over the right burner tab Log 4 srv530 716 Place the left end of log 4 in the groove on log 2 and the right end on log 1 as shown Log 5 srv438 724 Locate the top of log 5 onto log 1 and log 3 and place the bottom on the right side of the fourth grate tine 3 4 3 4 5 5 1 1 2 2 1 1 ...

Page 67: ...SI N CE SL350TRSI PB CE 2033 980 Rev J 3 13 Log 6 srv540 704 Place log 6 against the second and third grate tines If sooting occurs the logs might need to be repositioned slightly to avoid excessive flame impingement 6 6 ...

Page 68: ...pilot assembly for shorted sparker wire or cracked insulator around electrode Replace pilot if necessary 2 Pilot won t light there is no noise or spark a No power or transformer installed incorrectly Verify that transformer is installed and plugged into module Check voltage of transformer under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good trans...

Page 69: ... rect pilot orifice is installed and gas inlet is set to pressure specifications Polish flame sensing rod with fine steel wool to remove any contaminants that may have accumulated on flame sensing rod c Module is not grounded Verify module is securely grounded to metal chassis of ap pliance Verify that wire harness is firmly connected to the module d Damaged pilot assembly or contami nated flame s...

Page 70: ...ence only For framing dimensions and clearances refer to Section 5 Figure 16 1 Appliance Dimensions Location Centimeters L 22 3 M 41 4 N 1 3 O 57 8 P 28 9 Q 40 3 R 16 8 S 5 5 T 15 3 U 2 5 V 71 2 Location Centimeters A 83 8 B 71 4 C 61 3 D 38 4 E 74 1 F 9 0 G 17 5 H 54 1 I 82 7 J 98 4 K 20 3 A B T E ELECTRICAL ACCESS S V C D U G F H J I K Ø R Ø L M N O P Q GAS LINE ACCESS ...

Page 71: ...irebox 1 Inspect for paint condition warpage corrosion or perforation Sand and repaint as necessary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for plugged ports corrosion or deterioration Replace burner if necessary 3 Replace ember materials with new dime size ...

Page 72: ... 7 8 in 27 6 cm 45º 7 3 8 in 18 7 cm 11 3 8 in 28 9 cm 1 1 4 in 3 2 cm 9 1 4 in 23 5 cm 13 1 4 in 33 7 cm 1 2 in TYP DVP90ST 90 Elbow 10 in 25 4 cm 10 in 25 4 cm 1 in 2 5 cm 12 in 30 5 cm 14 in 35 6 cm 1 in 2 5 cm 8 in 20 3 cm 6 in 15 2 cm 10 in 25 4 cm 1 1 2 in 3 8 cm 5 in 12 7 cm 12 in 30 5 cm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45º Elbow DVP Pipe se...

Page 73: ...heat shield is designed to be used on a wall 4 in to 7 1 4 in 10 2 cm to 18 4 cm thick If wall thickness is less than 4 in 10 2 cm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 18 4 cm a DVP HSM B will be required Heat Shield 1 in 2 5 cm 14 in 35 6 cm 3 8 in 1 0 cm 1 in 2 5 cm 7 1 4 in 18 4 cm 7 3 4 in to 10 3 8 in 19 7 cm to 26 4 cm DVP FBHT FireBrickT...

Page 74: ...in 33 0 cm 15 in 38 1 cm 8 1 8 in 20 6 cm 10 7 8 in 27 6 cm 10 1 2 in 26 7 cm 3 87 Effective Length 5 3 4 in to 8 3 8 in 14 6 cm to 21 3 cm 5 1 2 in 14 0 cm 8 3 8 in 21 3 cm 31 in 78 7 cm 24 5 8 in 62 5 cm 13 1 4 in 36 7 cm RF12M Roof Flashing Multi pak 7 1 4 in 18 4 cm 12 in 30 5 cm 5 1 4 in 13 3 cm 12 1 2 in 31 8 cm DVP TVHW VerticalTermination Cap Highwind DRC RADIUS Cap Shield 13 7 8 in 35 2 c...

Page 75: ... 45 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop Effective Height Length Pipe inches cm SLP4 4 10 2 SLP6 6 15 2 SLP12 12 30 5 SLP24 24 61 0 SLP36 36 91 4 SLP48 48 121 9 SLP6A 2 6 51 15 2 SLP12A 2 12 51 30 5 6 in 15 2 cm 6 1 2 in 16 5 cm 6 5 8 in 16 8 cm 9 7 8 in 25 1 cm 6 1 2 in 16 5 cm 9 1 4 in 23 5 cm SLP90 90 Elbow ...

Page 76: ...ned to be used on a wall 4 in to 7 1 4 in 10 2 cm to 18 4 cm thick If wall thickness is less than 4 in 10 2 cm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 18 4 cm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap2 5 1 4 in 9 1 4 in 13 3 cm 23 5 cm 8 in 20 3 cm 12 in 30 5 cm Max Effective Length B ...

Page 77: ...thorized dealer ITEM DESCRIPTION COMMENTS PART NUMBER Log Set Assembly LOGS 350CE D 1 Log 1 SRV327 701 2 Log 2 SRV2033 701 3 Log 3 SRV705 703 4 Log 4 SRV530 716 5 Log 5 SRV438 724 6 Log 6 SRV540 704 7 Grate Assembly 2033 013 8 Base Pan 2033 105 9 Burner Assembly N 2089 010 Burner Assembly P 2089 012 10 Glass Assembly GLA 3504TRS 11 Hood SRV540 174 12 Dress Guard 2033 020 13 Lower Door Assembly 203...

Page 78: ... Post 0022995989 2090 012 Pilot Assembly P Pre 0022995989 2198 015 Post 0022995989 2090 013 17 2 Pilot Bracket 2089 104 17 3 3 Hole Grommet 2118 420 17 4 Orifice N 44C 582 844 Orifice P 55C 582 855 OrifIce B 56C 582 856 17 5 12 in Flex Tube Assembly 383 302A 17 6 18 in Flex Tube Assembly 2098 320A 17 7 Valve Bracket 2118 104 17 8 Valve N 2166 302 Valve P 2166 303 17 9 Male Connector Pkg of 5 303 3...

Page 79: ...BER Exhaust Restrictor 530 299 Gasket Assembly 2113 080 Includes Burner Neck Shutter Bracket Vent Seal Cap Valve Plate and Air Passage Gaskets Glass Latch Support Assembly Pkg of 2 33858 2 Heat Shield Control Module 2078 121 Heat Shield Header 2118 120 Jumper Wire Wall Switch 2179 300 Mineral Wool 050 721 Non Comb Board 539 401 Rocker Switch 2206 299 Top Heat Shield Interior 2089 109 RC300CE Remot...

Page 80: ...___________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ Printed in U S A Copyright 2013 DO NOT DISCARD THIS MANUAL NOTICE Leave this manual with party responsible for use and operation Important operat...

Reviews: