Heat & Glo • SL-550 / 750 / 950TR-E • 2118-900 Rev. AC • 3/15
26
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
Figure 7.5
Top Vent - Horizontal Termination
Venting with two 90º elbows
V Minimum
H
1
+ H
2
Maximum
SL-550TR-E
SL-750TR-E
SL-950TR-E
90 Elbow *
1/2 ft. 152 mm 1/2 ft. 152 mm
0 ft.
0 mm
1/2 ft.*
152 mm
1 ft.
305 mm
1 ft.
305 mm
1 ft.
305 mm
1-1/2 ft.*
457 mm
2 ft.
610 mm
2 ft.
610 mm
2 ft.
610 mm
2-1/2 ft.*
762 mm
4 ft.
1.2 m
4 ft.
1.2 m
4 ft.
1.2 m
3-1/2 ft.
1.1 m
6 ft.
1.8 m
6 ft.
1.8 m
6 ft.
1.8 m
4-1/2 ft.
1.4 m
14 ft.
4.3 m
14 ft.
4.3 m
14 ft.
4.3 m
H + H
1
MAX. =14 ft. (4.3 m)
V + H + H
1
MAX. = 40 ft. (12.2 m)
* See warning below
Note
: There MUST be a 25%
reduction in total H when using
fl
ex vent except when using the
simple up and out installation
(see Figure 7.3).
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps on top vented
fi
replaces, a one
foot minimum vertical vent section is required before
installing
fi
rst elbow.
WARNING *
• When using DVP-TB1 termination cap on top vented
fi
replaces,
a three foot minimum vertical vent section is required before
installing
fi
rst elbow.
Note
: Use SLP Series
components only.