Heat & Glo SL-550METRO Owner'S Manual Download Page 72

Heat & Glo  •  SL-550METRO, SL-550METRO-LP  •  2185-900 Rev. D  •  8/09

72

B.  Vent Components Diagrams (continued)

Figure 16.9  SLP Series Vent Components      

SLK-SNKD

Snorkel

Termination Cap

SLP-TVHW

Vertical

Termination Cap

SLP-FLEX-TRAP

Horizontal

Termination Kit

SLP-CCS-BK

Cathedral Ceiling 

Support Box-Black

SLP-DCF-BK

Ceiling Firestop 

Black

SLP-WT-BK

Wall Thimble-Black

SL-2DVP

Adapter

PVK-80

(For use with IPI and DSI appliances only.)

SLP-TRAP

Horizontal Termination Cap

15-1/8 in.

(384 mm)

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be 
used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) 
the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a 
DVP-HSM-B will be required.

Heat

Shield

Term Cap

Minimum

Effective Length

Maximum

Effective Length

Trap1

3-1/8 in. 

4-3/4 in. 

79 mm

121 mm

Trap2

5-1/4 in. 

9-1/4  in.

133 mm

235 mm

8 in.

(203 mm)

12 in.

(305 mm)

Max

Effective

Length

Summary of Contents for SL-550METRO

Page 1: ...gas indicated on the rating plate Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or technicians supervised by an NFI certified professional Leave this manual with party responsible for use and operation DO NOT DISCARD WARNING Important operating and maintenance instructions inclu...

Page 2: ... ANSI Z223 1 Z223 1 in in the the USA USA or or CAN CGA CAN CGA B149 B149 installation installation codes codes Installer Installer l appareil l appareil selon selon les les codes codes ou ou reglements reglements locaux locaux ou ou en en l absence l absence de de tels tels reglements reglements selon selon les les codes codes d installation d installation CAN CGA B149 CAN CGA B149 Type Type of o...

Page 3: ...ations 17 C Tools and Supplies Needed 17 D Inspect Appliance and Components 17 5 Framing and Clearances A Selecting Appliance Location 18 B Constructing the Appliance Chase 19 C Clearances 19 D Mantel and Wall Projections 20 6 Termination Locations A Vent Termination Minimum Clearances 21 7 Vent Information and Diagrams A Approved Pipe 23 B Vent Table Key 23 C Use of Elbows 23 D Measuring Standard...

Page 4: ...ce Setup A Remove Fixed Glass Assembly 61 B Remove the Shipping Materials 61 C Clean the Appliance 61 D Accessories 61 E Glass Rock Media Kit 61 F Fixed Glass Assembly 62 G Install Trim and or Surround 62 H Air Shutter Setting 62 15 Troubleshooting A IntelliFire Ignition System 63 16 Reference Materials A Appliance Dimension Diagram 65 B Vent Components Diagrams 66 C Service Parts 74 D Contact Inf...

Page 5: ...5 Heat Glo SL 550METRO SL 550METRO LP 2185 900 Rev D 8 09 B Limited Lifetime Warranty ...

Page 6: ...Heat Glo SL 550METRO SL 550METRO LP 2185 900 Rev D 8 09 6 B Limited Lifetime Warranty continued ...

Page 7: ...SL 550METRO LP LABORATORY Underwriters Laboratories Inc UL TYPE Direct Vent Gas Appliance Heater STANDARD ANSI Z21 88b 2008 CSA 2 33a 2008 C BTU Specifications Models U S 0 2000 ft or Canada 2000 4500 ft Maximum Input BTU h Minimum Input BTU h Orifice Size DMS SL 550METRO NG U S 21 000 N A 44 Canada 18 900 N A 45 SL 550METRO LP LP U S 19 000 N A 55 Canada 18 540 N A 56 D High Altitude Installation...

Page 8: ... eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage installed in ...

Page 9: ...es are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other flammable materials Keep clothing furniture draperies and other flammable mate...

Page 10: ...install one For more information refer to the instructions supplied with your decorative door or front F Remote Controls Wall Controls and Wall Switches Follow the instructions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protection lockout feature Keep remote controls out of reach of children See your dealer if ...

Page 11: ...e gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT 110 VAC TO THE CONTROL VALVE Improper installation adjustment al teration service or maintenance can cause injury or property damage Re fer to the owner s information manual provided with this appl...

Page 12: ... al lowed to burn for 20 to 40 minutes Odor from appliance When first operated this appliance may release an odor for the first several hours This is caused by the curing of the paint and the burning off of any oils remaining from manufacturing Odor may also be released from finishing materials and adhesives used around the appliance Film on the glass This is a normal result of the curing process ...

Page 13: ...be required due to lint from carpeting or other factors Control compartment burner and circulating air passageway of the fireplace must be kept clean CAUTION Risk of Burns The fireplace should be turned off and cooled before servicing When properly maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surroun...

Page 14: ...uency Annually By Qualified Service Technician Tools needed Protective gloves vacuum cleaner dust cloths Vacuum and wipe out dust cobwebs debris or pet hair Use caution when cleaning these areas Screw tips that have penetrated the sheet metal are sharp and should be avoided Remove all foreign objects Verify unobstructed air circulation Burner Ignition and Operation Frequency Annually By Qualified ...

Page 15: ...15 Heat Glo SL 550METRO SL 550METRO LP 2185 900 Rev D 8 09 Either cobrahead or SIT PRODUCT SPECIFIC Figure 3 1 IPI Pilot Flame Patterns ...

Page 16: ...ITHOUT AFFECTING ROOF RAFTERS SECTION 8 C FRAMING HEADED OFF IN CEILING JOISTS SECTION 8 C GAS LINE SECTION 11 MANTEL AND MANTEL LEG SECTION 5 D SURROUND HEARTH EXTENSION VENT PIPE SECTIONS 7 and 9 OPTIONAL WALL SWITCH STORM COLLAR SECTION 10 H NON COMBUSTIBLE ROOF FLASHING MAINTAINS MINIMUM CLEARANCE AROUND PIPE SECTION 10 G FRAMING HEADER SECTION 5 B ATTIC INSULATION SHIELD NOT SHOWN MUST BE USE...

Page 17: ...enefit WARNING Risk of Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry C Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers High temperature caulking material Hammer Phillips screwdriver Gloves ...

Page 18: ...liance should be locat ed out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 5 1 Appliance Locations K C A L F I B G E D J J G A F C A H M N Models A B C D E Min F Min G H I J K L M N SL 550METRO ...

Page 19: ...ng vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to appliance and vent pipe Insulation and other materials must be secured to prevent accidental contact The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney Failure to maintain airspace may ...

Page 20: ... 8 9 10 3 4 5 12 11 10 9 8 7 6 TOP OF HOOD OR FIREPLACE OPENING 4 12 13 11 32 CEILING Note Clearance from opening to perpendicular wall All measurements are in inches 5 3 8 IN MINIMUM 3 IN MINIMUM UNLIMITED Figure 5 6 Wall Projection Acceptable on one side of opening 11 1 2 IN 1 2 IN NON COMBUSTIBLE ZONE FRAMING HEADER 1 2 IN THICK WALL SHEATHING Figure 5 4 Non Combustible Zone Note Clearance from...

Page 21: ...2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 6 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire WARNING Figure 6 2 Staggered Termination Caps Gas Wood or Fuel Oil Terminat...

Page 22: ...h the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap 3 All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap See Note 1 See Note 2 Note 3 Local codes ...

Page 23: ...pipe is allowed between two 45º elbows see Figure 7 1 Figure 7 1 7 7 Vent Information and Diagrams B Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams D Measuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards Pipe measurements are shown using the effective length of pipe see Figure 7 2 H...

Page 24: ...t with no more than 1 2 inch sag between supports A support is required at each change in venting direction and in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Fig ure 7 3 requires only enough support to maintain the necessary clearance to combustibles However the vent at tachment point and the firestop loca tion are consid...

Page 25: ... 2 ft 457 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 14 ft 4 3 m H MAX 14 ft 4 3 m V H MAX 40 ft 12 2 m Note Use SLP Series components only Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 7 3 Fire Risk A one foot minimum vertical vent section is required before installing first...

Page 26: ... 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H H1 MAX 14 ft 4 3 m V H H1 MAX 40 ft 12 2 m Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 7 3 Note Use SLP Series components only Fire Risk Aone foot minimum vertical vent section is required before install...

Page 27: ...installation see Figure 7 3 Note Use SLP Series components only Fire Risk A one foot minimum vertical vent section is required before installing first elbow WARNING V1 Minimum H1 H2 Maximum SL 550METRO V2 V1 V2 Min 1 ft 305 mm 6 ft 1 8 m 1 1 2 ft 457 mm 10 ft 3 0 m 2 1 2 ft 762 mm 12 ft 3 7 m 3 1 2 ft 1 1 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 6 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on ...

Page 28: ...ictor installation Exhaust restrictor Instructions 1 Install the exhaust restrictor over the center of the ex haust outlet in the firebox see Figure 7 8 2 Center the exhaust restrictor in the open end of the exhaust outlet and secure through the slots on the ex haust restrictor with the 2 1 4 in self tapping screws provided in the appliance manual bag Exhaust restrictor Exhaust restrictor Exhaust ...

Page 29: ...see Figure 7 3 Note Use SLP Series components only V1 Minimum H Maximum SL 550METRO V2 V1 V2 Min 1 ft 305 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 15 ft 4 6 m H MAX 15 ft 4 6 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H cannot exceed 40 ft 12 2 m Fire Risk A one foot minimum vertical vent ...

Page 30: ...installation see Figure 7 3 Note Use SLP Series components only V1 Minimum H Maximum SL 550METRO V2 V1 V2 Min 1 ft 305 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 6 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H cannot exceed 40 ft 12 2 m Fire Risk A one foot minim...

Page 31: ...here MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 7 3 V1 Min H1 Max V2 Min H2 Max V3 Min 1 1 2 ft 457 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 0 m V1 V2 V3 H1 H2 Maximum 40 ft 12 2 m Figure 7 11 V1 H1 V2 V3 H2 Note Use SLP Series components only ...

Page 32: ...ation No Elbows H1 9 in 229 mm Maximum Rear Vent Horizontal Termination One 45º Elbow Note Use DVP Series components only Note Use DVP Series components only H1 MAX SL 550METRO 24 in 610 mm NOTICE For optimum flame perfor mance on LP models adjust shutter setting to 5 16 in when venting from rear with no elbows ...

Page 33: ... 14 ft 4 3 m V1 H1 H2 MAX 40 ft 12 2 m Figure 7 14 Rear Vent Horizontal Termination Venting with three 90º elbows H1 MAX V1 MIN H2 H3 MAX H1 H2 H3 MAX 1 1 2 ft 457 mm Back to back elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 1 2 ft 1 1 m 1 ft 305 mm 2 ft 610 mm 5 1 2 ft 1 7 m 5 1 2 ft 1 7 m 2 ft 610 mm 4 ft 1 2 m 9 1 2ft 2 9 m 7 1 2 ft 2 3 m 3 ft 914 mm 6 ft 1 8 m 13 1 2 ft 4 1 m H1 MAX 7 1 2 ft 2 3 m H1 ...

Page 34: ...ft 1 1 m 2 ft 610 mm 5 1 2 ft 1 7 m 3 ft 914 mm 7 1 2 ft 2 3 m H MAX 7 1 2 ft 2 3 m V1 H1 MAX 40 ft 12 2 m Rear Vent Vertical Termination Venting with two 90º elbows H1 H2 MAX V1 MIN 1 2 ft 152 mm Back to back elbows 2 1 2 ft 762 mm 1 ft 305 mm 4 1 2 ft 1 4 m 2 ft 610 mm 6 1 2 ft 2 0 m 3 ft 914 mm H MAX 6 1 2 ft 2 m V H H1 MAX 40 ft 12 2 m Note Use DVP Series components only Note Use DVP Series co...

Page 35: ...ft 305 mm 3 1 2 ft 1 1 m 3 ft 914 mm 6 1 2 ft 2 0 m 2 ft 610 mm 5 1 2 ft 1 7 m 5 ft 1 5 m 10 1 2 ft 3 2 m 3 ft 914 mm 7 1 2 ft 2 3 m 7 ft 2 1 m 14 1 2 ft 4 4 m H1 MAX 7 1 2 ft 2 3 m H1 H2 MAX 14 1 2 ft 4 4 m V1 V2 H1 H2 MAX 40 ft 12 2 m H1 V1 H2 V2 Figure 7 18 Rear Vent Vertical Termination Venting with three 90º elbows Note Use DVP Series components only ...

Page 36: ... Hearth Home Technologies recommends that NFI or CSIA certified professionals or technicians under the direction of certi fied professionals conduct a minimum of a NFPA 211 Level 2 inspection of the chimney Replace component parts of the chimney and fireplace as specified by the professionals Ensure all joints are properly engaged and the chimney is properly secured EXHAUST VENT PIPE INLET AIR VEN...

Page 37: ... See Figure 7 21 Rear Vent Remove the rear seal cap and insulation if equipped Connect the DVP 2SL adapter to the vertically positioned elbow Follow installation instructions included with DVP 2SLkit Secure DV 46DVA GCLadapter to DVP 2SLwith 3 1 2 in self tapping screws See Figure 7 21 Connecting the LINK DV30B to the DV 46DVA GCL adapter Insert the two sections of flexible vent pipe down the exis...

Page 38: ... in 25 mm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance around vertical sections B Wall Penetration Framing Combustible Wall Penetration Whenever a combustible wall is penetrated you must frame a hole for the wall shield firestop s The wall shield firestop maintains minimum clearances and prevents cold air infiltration The op...

Page 39: ...g firestop may be installed above or below the ceiling joists when installed with a attic insulation shield It must be under joists between floors that are not insulated Refer to Figure 8 4 Secure with three fasteners on each side WARNING Risk of Fire DO NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating Figure 8 3 Installing Ceiling Firestop Fig...

Page 40: ...must be used to prevent blown insulation from getting between the shield and vent pipe and to maintain air space clearance Figure 8 5 Attic Insulation Shield Vaulted Ceiling Installation Remove one shield from box NOTICE Cut previously installed batt insulation to make room for the attic insulation shield Cut the attic insulation shield if application is for vaulted ceiling to fit your ceiling pit...

Page 41: ...the fireplace shown in this section Figure 9 4 Rotate the top heat shield to the vertical position as shown above The heat shield must remain in the vertical position Figure 9 3 For top vent remove the two screws holding the top heat shield in place For rear vent see Section 9 B 2 SCREWS 2 SCREWS Figure 9 5 Replace the two screws as shown WARNING Risk of Fire Do not remove heat shield El evated he...

Page 42: ...ent pipe make sure to use the fiberglass gasket to seal between the first vent component and the outer fireplace wrap Use 2 self tapping screws to secure the gasket to the outer wrap Note Once the vent cap has been removed it cannot be reattached 2 SCREWS Figure 9 7 Remove the insulation basket and white insula tion from the center vent pipe Figure 9 8 Remove the insulation from the outer vent pip...

Page 43: ...s Block openings into the chase to prevent entry of blown in insulation Make sure insulation and other materials are secured DO NOT notch the framing around the appliance standoffs Failure to maintain air space clearance may cause overheating and fire The diagram shows how to properly position and secure the appliance see Figure 9 17 Nailing tabs are provided to secure the appliance to the framing...

Page 44: ...If predrilling holes DO NOT penetrate inner pipe For 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe Commercial Multi family Multi level exceeding two sto ri...

Page 45: ...p outer flues shall be sealed in this manner unless otherwise stated Figure 10 5 Adding Venting Components WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when remov ing termination cap from slip pipe If slip section seals are broken during removal of the termination cap vent may leak Note Align seams to engage pipe then rotate counterclockwise to lock C Ass...

Page 46: ...SLP pipe must be supported every 8 ft 2 44 m Horizontal sections must be supported every 5 feet 1 52 m Vent supports or plumbers strap spaced 120º apart may be used to support vent sections See Figures 10 8 and 10 9 Wall shield firestops may be used to provide horizontal support vent sections SLP ceiling firestops have tabs that may be used to provide vertical support WARNING Risk of Fire Explosio...

Page 47: ...port box on the outside roof Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box Cut the hole 1 8 in 3 mm larger than the support box outline Lower the support box through the hole in the roof until its bottom is at least 2 in 51 mm below the ceiling Figure 10 12 Level the support box both vertically and horizontally and temporarily tack it in place ...

Page 48: ...ailure to properly caulk the roof flashing could cause water entry Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing where it contacts the roof surface See Figure 10 15 H Assemble and Install Storm Collar CAUTION Risk of Cuts Abrasions or Flying Debris Wear protective gloves and safety glasses during instal lation Sheet metal edges are...

Page 49: ...NING Risk of Fire To prevent overheating and fire heat shields must extend through the entire wall thick ness DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 10 20 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other sec...

Page 50: ...ding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For certain exposures which requ...

Page 51: ...use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure may cause explosion Verify inlet pressures Verify minimum pressures when other household gas appliances are operating Install regulator ups...

Page 52: ...box to a switched circuit Incorrect wiring will override IPI safety lockout Refer to Figures 12 1 and 12 2 IntelliFire Pilot Ignition IPI Wiring Diagram This appliance is equipped with an IntelliFire control valve which operates on a 3 volt system Plug the 3 volt AC transformer into the appliance junction box to supply power to the unit OR install two D cell batteries not included into the battery...

Page 53: ...TE 1 Ignition module valve pilot and wall switch operate on 3 volts 120 VAC is required at junction box unless equipped with battery back up TRANSFORMER 3 VAC PLUG IN PLUG IN BLACK RED BATTERY PACK REMOTE WIRES TO BROWN ORANGE GREEN VALVE GROUND TO FIREPLACE CHASSIS HOT NEUTRAL WHITE ORANGE IGNITION MODULE 3 VAC INTERMITTENT PILOT IGNITOR I S Figure 12 2 Intellifire Ignition Wiring Diagram with Re...

Page 54: ...n If the box is being wired from the INSIDE of the appli ance Remove the screw attaching the junction box receptacle to the outer shell rotate the junction box inward to dis engage it from the outer shell see Figure 12 4 Pull the electrical wires from outside the appliance through the opening into the valve compartment and secure wires with a Romex connector See Figure 12 4 Make all necessary wire...

Page 55: ... Step 2 Crease flap on top side of splatter guard using the scored line as the guide See Figure 13 2 Figure 13 2 Step 3 Crease flaps on left and right sides of splatter guard using the scored line as the guide See Figure 13 3 Step 4 Center the splatter guard in front of the unit as shown in Figure 13 4 Place the splatter guard in the unit by guiding the top flap into proper position and then con t...

Page 56: ...s on the front of the splatter guard See Figure 13 7 Pull out and fold up the panel as shown in Figure 13 8 Disengage the tabs on left and right bottom of splatter guard and fit them into the square holes The tabs are now inside the front of the splatter guard carefully bend them down See Figure 13 9 Figure 13 9 Figure 13 8 To Close the Lower Access Panel Carefully disengage the tabs from the squa...

Page 57: ... 9 10 3 4 5 12 11 10 9 8 7 6 TOP OF HOOD OR FIREPLACE OPENING 4 12 13 11 32 CEILING Note Clearance from opening to perpendicular wall All measurements are in inches 5 3 8 IN MINIMUM 3 IN MINIMUM UNLIMITED Figure 13 15 Wall Projection Acceptable on one side of opening 11 1 2 IN 1 2 IN FRAMING HEADER 1 2 IN THICK WALL SHEATHING Figure 13 13 Non Combustible Zone Note Clearance from opening to perpend...

Page 58: ...ying combustible materials Seal joints between the finished wall and appliance top and sides using a 300 F minimum sealant Refer to Figure 13 17 WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all minimum clearances to combustibles as specified in this manual Overlapping materials could ignite and will interfere with proper operation of doors and l...

Page 59: ...ombustible sheathing See Figure 13 18 and 13 19 It is necessary to follow all of the requirements in Section 13 C when overlapping materials onto the face of the appliance Figure 13 18 Modern Door Clean Finishing Inside Fit Finishing materials 1 inch maximum thick Stop finishing material flush around the opening COMBUSTIBLE MATERIAL NON COMBUSTIBLE MATERIAL 34 IN 36 IN DOOR FIT FINISH MATERIAL MAX...

Page 60: ...shing material flush around the opening 34 in 36 in WITHOUT FRONT SHOWN WITH FRONT SHOWN Overlap Fit NON COMBUSTIBLE ZONE 32 5 8 IN Includes 1 8 in opening each side of door 30 5 8 IN Figure 13 20 Inside Fit Door Finishing material between 1 and 4 inches thick Finishing template METRO TEMPLATE may be used FINISHING MATERIAL 4 IN MAXIMUM THICKNESS DOOR FINISHING MATERIAL 4 IN MAXIMUM THICKNESS Insi...

Page 61: ... for a list of ap proved accessories WARNING Risk of Fire and Electric Shock Use ONLY Hearth Home Technologies approved optional acces sories with this appliance Using non listed accessories could result in a safety hazard and will void the warranty E Glass Rock Media Kit A glass rock media kit is available for use with the SL 550METRO Install glass rock media according to in structions included w...

Page 62: ...ut and latch the four glass assembly latches into the groove on the glass frame G Install Trim and or Surround Install optional trim kits and or surrounds using the instructions included with the accessory Use non combustible materials to cover the gap between the sheet rock and the appliance when applicable to the model GLASS ASSEMBLY LATCHES BOTH BOTTOM AND TOP Shutter Settings Models NG LP SL 5...

Page 63: ...r shorted sparker wire or cracked insulator around electrode Replace pilot if necessary 2 Pilot won t light there is no noise or spark A No power or transformer installed incorrectly Verify that transformer is installed and plugged into module Check voltage of transformer under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good transformer are betwee...

Page 64: ...r rect pilot orifice is installed and gas inlet is set to pressure specifications Clean flame sensing rod with emery cloth to remove any contaminants that may have accumulated on flame sensing rod C Module is not grounded Verify module is securely grounded to metal chassis of ap pliance Verify that wire harness is firmly connected to the module D Damaged pilot assembly or contami nated flame sensi...

Page 65: ...igure 16 1 Appliance Dimensions A B T E S V C D U R Ø L M N O P Q GAS LINE ACCESS H J I K Ø ELECTRICAL ACCESS G F W Location Inches Millimeters Location Inches Millimeters A 36 913 L 8 13 16 223 B 31 1 8 791 M 16 5 16 415 C 27 3 16 691 N 1 2 13 D 18 1 16 459 O 25 3 4 653 E 31 1 8 790 P 12 7 8 326 F 3 9 16 90 Q 15 7 8 403 G 6 7 8 174 R 6 5 8 168 H 23 3 8 594 S 2 3 16 55 I 42 5 8 1083 T 6 152 J 49 1...

Page 66: ...3 to 24 76 to 610 10 1 2 in 267 mm 10 7 8 in 276 mm 45 7 3 8 in 187 mm 11 3 8 in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP 10 in 254 mm 24 in 610 mm DVP HVS Vent Support DVP AS Attic Shield DVP WS Wall Shi...

Page 67: ...ive Length Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Leng...

Page 68: ... 5 8 in 625 mm 13 1 4 in 367 mm RF12M Roof Flashing Multi pak BEK Trap Cap Brick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADD Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing DVP HS...

Page 69: ...98 mm DVP TV VerticalTermination Cap 7 1 4 in 12 in 305 mm 184 mm 5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind PVK 80 For use with IPI and DSI appliances only 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10...

Page 70: ... 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm 10 7 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm DVP HRC SS DVP HRC ZC SS HORIZONTAL TERMINATION CAP SLP HRC SS SLP HRC ZC SS HORIZONTAL TERMINATION CAP DVP TB1 HORIZONTAL...

Page 71: ...tal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop EFFECTIVE HEIGHT LENGTH Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 6 51 152 SLP12A 2 12 51 305 SLP FLEX 2 24 610 SLP FLEX 3 36 914 SLP FLEX 5 60 1524 SLP FLEX 10 120 3048 6 in 152 mm 6 1 2 in 165 mm 6 5 8 in 168 mm 9 7 8 in 6 1 2 in 165 mm 9 1 4 in 235...

Page 72: ...PI and DSI appliances only SLP TRAP Horizontal Termination Cap 15 1 8 in 384 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required...

Page 73: ...73 Heat Glo SL 550METRO SL 550METRO LP 2185 900 Rev D 8 09 SLP90 SL 2DVP DVP FBHT DVP FBHT LINK DV30B Flex Liner Kit DV 46DVA GCL Coaxial Colinear Appliance Connector DVP 2SL Adapter ...

Page 74: ...50METRO SL 550METRO LP 2185 900 Rev D 8 09 74 C Service Parts Service Parts Diagram Beginning Manufacturing Date May 2009 Ending Manufacturing Date ______ SL 550METRO Part number list on following page 1 2 3 4 5 6 7 ...

Page 75: ...ss Assembly GLA 550TR Y 6 Thermostat Wire Assembly 2118 170 7 Junction Box 4021 013 Y Exhaust Restrictor 530 299 Gasket Assembly 2115 080 Contains Burner neck shutter bracket vent seal cap valve plate and air passage gaskets Glass Latch Assembly Qty 4 req 386 122A Y Heat Shield Battery Pack 2185 114 Heat Shield Junction Box 2185 117 Non combustible Board 2185 110 Pilot Tube SRV485 301 Y Touch Up P...

Page 76: ... may be ordered from an authorized dealer Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER 1 Pilot Bracket 2185 112 2 Pilot Assembly NG 2090 012 Y Pilot Assembly LP 2090 013 Y 3 Flex Ball Valve Assembly 302 320A Y 4 Valve Bracket 2118 104 5 Valve NG 593 500 Y Valve LP 593 501 Y 6 Battery Pack 593 594A Y 7 Thermostat Wire Assembly 2118 170 Y 8 Module 593 592 Y 9 Module Wire Assembly 593 590A ...

Page 77: ..._________________________________________________________ ________________________________________________________________________________ This product may be covered by one or more of the following patents United States 4593510 4686807 4766876 4793322 4811534 5000162 5016609 5076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452708 5542407 5601073 5613487 5647340 5688568 576...

Reviews: