28
ROOM ABOVE (non-insulated ceiling)
ATTIC ABOVE (insulated ceiling)
B
A
Ceilng firestop from
bottom
Ceiling firestop from
top
Note:
Use same dimensional lumber for framing
ceiling firestop and joists.
Figure 8.5 Installing the Ceiling Firestop
• Install a ceiling firestop whenever chimney penetrates
ceiling/floor.
• Mark and cut an opening in ceiling as shown in
Figure 8.5.
• Frame the opening with the same size lumber used in the
ceiling joists.
• Nail the ceiling firestop to the bottom of the ceiling joists
when there is a room above/
• Use an attic insulation shield if the ceiling is insulated. The
ceiling firestop may then be attached above or below the
joists. Refer to Figure 8.6 and 8.7.
D. Install Ceiling Firestops
CAUTION! Risk of Fire! Ceiling firestops must be used
whenever the chimney penetrates a ceiling/floor.
• Chase construction requires ceiling firestops at each floor
or every 10 ft (3.05 m) of clear space.
• The ceiling firestop slows spread of fire and reduces cold
air infiltration.
WARNING! Risk of Fire! DO NOT seal area between
firestop opening and chimney pipe except where they enter
the attic or leave the warm-air envelope of the home (use
600° F sealant).
Heat & Glo • RUTHERFORD-42 • 4059-309 Rev L • 5/11
Catalog #
A
B
in.
mm
in.
mm
FS538
17
432
17
432
FS540
17
432
26
660