6
Heat & Glo • Rutherford 42-B Installation Manual • 4059-712 • Rev O • 09/28/15
Figure 2.2 Fireplace Locations
NOTICE:
• Illustrations and photos reflect typical installations and
are
FOR DESIGN PURPOSES ONLY
.
• Illustrations/diagrams are not drawn to scale.
• Actual installation/appearance may vary due to individual
design preference.
• Hearth & Home Technologies reserves the right to alter
its products.
NOTICE:
In addition to these framing dimensions, also
reference the following section:
•
Clearances (Section 3).
NOTICE:
A minimum 1-1/2 in. air clearance at the back and
a minimum 1-1/2 in. air clearance to the sides of
the fireplace assembly must be maintained.
Chimney sections at any level require a 2 in. mini-
mum air space clearance between the framing
and chimney sections.
B. Design and Installation Considerations
NOTICE: Check building codes prior to installation.
• Installation MUST comply with local, regional, state and
national codes and regulations.
• Consult insurance carrier, local building inspector, fire
officials or authorities having jurisdiction over restrictions,
installation inspection and permits.
•
Before installing
, determine the following:
- Where the fireplace is to be installed.
- The vent system configuration to be used.
- Gas supply piping.
- Electrical wiring.
- Framing and finishing details.
- Whether optional accessories - devices such as a
fan, wall switch or remote control - are desired.
1. Selecting Fireplace Locations
This fireplace may be used as a room divider, installed
along a wall, across a corner or used in an exterior chase.
See Figure 2.2.
Locating the fireplace in a basement, near frequently
opened doors, central heat outlets or returns, or other
locations of considerable air movement can affect the
performance.
Consideration should be given to these factors before
deciding on a location.
A*
F
D
B
C
1/2 in. (13 mm) all
configurations
1-1/2 in. min. air space
from fireplace to
combustible materials.
1/2 in. min. air space at
nailing flanges.
Note:
In an exterior chase
or projecting into a
garage
Across a
corner
As a
room
divider
Along a wall
84 in.
(2134 mm)
G
B
E
48 in.
(1219 mm)
MINIMUM
24 in. (610 mm)
from fireplace opening to
any perpendicular wall
A
B
G
G
B
)))))))
)))
))
)))
))))
)))
))
)))))
))))
)))
))))
)))
)))
)))))
))))
))))
)))
)))
)))
)))))
))))
))
)))
)))
))
))
)
))))
))))
))))
))))
))))
Model #
A
B
C
D
E
F
G
in.
77 7/8
53 7/8
95 1/4
47 5/8
22 1/2
67 3/8
28 1/2
mm
1978
1368
2419
1210
572
1711
724
RUTHERFORD-42
* 12 in. (305 mm) extra space
included for each outside air
connection. If outside air
duct has no bends, this
diameter may be reduced as
long as minimum clearances
are met.