background image

29

Heat & Glo  •  RED40-NNN,RED40-NM, RED40-LM, RED40-NNN, RED40ST-LM, RED40ST-NM Installation Manual  •  2155-975 Rev. E  •  12/14   

D.  Disassemble Vent Sections

•  Rotate either section (see Figure 7.9) so the seams on 

both pipe sections are aligned as shown in Figure 7.10

•  Pull carefully to separate the pieces of pipe.

Figure 7.10   Align and Disassemble Vent Sections

Figure 7.9 Rotate Seams for Disassembly

Summary of Contents for RED40-LM

Page 1: ...This appliance is only for use with the type s of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used DO NOT store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance What to do if you smell gas DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any...

Page 2: ...cation and Vent Information A Vent Termination Minimum Clearances 13 B Chimney Diagram 14 C Approved Pipe 15 D Use of Elbows 15 E Measuring Standards 15 F Vent Diagrams 15 5 Vent Clearances and Framing A Pipe Clearances to Combustibles 22 B Wall Penetration Framing Firestops 22 C Install the Ceiling Firestop 23 D Install Attic Insulation Shield 23 6 Appliance Preparation A Vent Collar Preparation ...

Page 3: ..._______________ Gas Section 9 Pg 40 42 Proper appliance for fuel type ___________________________ Was a conversion performed ___________________________ Leak check performed and inlet pressure veri ed ___________________________ Veri ed proper air shutter setting for installation type ___________________________ Finishing Section 10 Pg 43 48 Combustible materials not installed in non combustible a...

Page 4: ... tected with ground fault circuit interrupter protection in compliance with the applicable electrical codes when it is installed in locations such as in bathrooms or near sinks NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is tested and approved as either supplemen tal room heat or as a decorative appliance It should not be factored as primary heat in residential heating calculation...

Page 5: ... horizontally vented gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detector...

Page 6: ...and or refractory kits must be installed Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starting the instal lation Follow these instructions carefully during the installation to ensure maximum safety and benefit WARNING Risk of Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged in compl...

Page 7: ...nce only For framing dimensions and clearances refer to Section 5 Figure 3 1 Appliance Dimensions RED40 A B C D E F G H I J K O L P M N R Q S T Location Inches Millimeters K 46 3 4 1187 L 7 178 M 50 1 8 1273 N 25 1 16 637 O 18 5 8 473 P 9 1 16 230 Q 3 3 4 95 R 1 1 2 38 S 8 1 2 216 T 14 1 2 368 Location Inches Millimeters A 52 1321 B 13 3 16 335 C 10 3 4 273 D 42 3 4 1086 E 48 1 8 1222 F 21 533 G 4...

Page 8: ... 4 1187 L 7 178 M 50 1 8 1273 N 25 1 16 637 O 18 1 8 460 P 9 1 16 230 Q 3 3 4 95 R 1 1 2 38 S 8 1 2 216 T 14 1 2 368 Location Inches Millimeters A 52 1321 B 13 3 16 335 C 10 3 4 273 D 42 3 4 1086 E 48 1 8 1222 F 21 533 G 4 102 H 4 3 4 121 I 42 15 16 1090 J 17 1 8 435 C B A D E F G H I J K L O M N P T Q R S Figure 3 2 Appliance Dimensions RED40ST ...

Page 9: ...LM RED40ST NM Installation Manual 2155 975 Rev E 12 14 SRV2155 040 DECORATIVE FRONT Figure 3 3 Decorative Front Dimensions G A B C D E F Location Inches Millimeters A 41 3 8 1051 B 45 1 2 1156 C 8 3 4 221 D 12 1 8 307 E 16 1 8 409 F 19 3 4 502 G 20 11 16 525 ...

Page 10: ...grams are not drawn to scale Actual installation may vary due to individual design preference 1 IN 45 1 IN A E A B C TOP VENT ONE 90 ELBOW ALCOVE INSTALLATION B TOP VENT ONE 90 ELBOW B F D Figure 3 4 Appliance Locations RED40 A B C D E F Inches 60 3 8 50 85 3 8 See Section D Figure 5 6 5 7 24 1 8 18 3 4 Millimeters 1533 1270 2168 613 476 It is important to follow the framing and finishing instruc ...

Page 11: ...re stops should be caulked with caulk with a minimum of 300ºF continuous exposure rating to seal gaps Gas line holes and other openings should be caulked with caulk with a minimum of 300ºF continuous exposure rating or stuffed with unfaced insulation If the appliance is being installed on a cement surface a layer of plywood may be placed underneath to prevent conducting cold up into the room D Flo...

Page 12: ...iance Inches 10 46 3 4 17 1 4 50 1 4 31 0 0 1 36 Millimeters 254 1187 438 1276 787 0 0 25 914 F I G H E MEASURE FROM TOP OF FIREPLACE OPENING C A B D C B D A Figure 3 7 Clearances to Combustibles RED40 MINIMUM FRAMING DIMENSIONS A B C D E F G H I J Rough Opening Vent Pipe Rough Opening Height Rough Opening Depth Rough Opening Width Clearance to Ceiling Combustible Floor Combustible Flooring Behind...

Page 13: ...ING 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 4 4 Termination Location and Vent Information Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe could cause overheating and fire WARNING Figure 4 2 Staggered Termination Caps Gas...

Page 14: ...B A E V V V V V V M H or i V G X V H A V V H Electrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMAX 2 termination caps x QACT...

Page 15: ...l termination cap should have a 1 4 inch downward slant to allow any moisture in cap to be released F Vent Diagrams C Approved Pipe This appliance is approved for use with Hearth Home Technologies DVP venting systems Refer to Section 12 A for vent component information and dimensions DO NOT mix pipe fittings or joining methods from differ ent manufacturers The pipe is tested to be run inside an en...

Page 16: ... 63 ft 19 2 m Maximum Figure 4 5 Top Vent Horizontal Termination Venting with 1 elbow H1 V1 Fire Risk Explosion Risk Do NOT pack insulation or other combustibles between ceiling firestops ALWAYS maintain specified clearances around venting and firestop systems Install wall shield and ceiling firestops as specified Failure to keep insulation or other material away from vent pipe may cause fire WARN...

Page 17: ...829 mm 3 ft 914 mm 9 ft 2743 mm 4 ft 1219 mm 12 ft 3658 mm V1 H1 H2 63 ft 19 2 m Maximum H1 H2 23 ft 7 1 m Maximum INSTALLED HORIZONTALLY H1 H2 V1 Figure 4 6 1 Top Vent Horizontal Termination continued Top Vent Horizontal Termination Venting with 2 elbows Note Use DVP Series components only Note 12 inches minimum vertical is required prior to attaching any elbow to the appliance ...

Page 18: ...m 3 ft 914 mm 9 ft 2743 mm 4 ft 1219 mm 12 ft 3658 mm 5 ft 1524 mm 15 ft 4572 mm V1 V2 H1 H2 63 ft 19 2 m Maximum H1 H2 23 ft 7 1 m Maximum H2 H1 V2 V1 Top Vent Horizontal Termination Venting with 3 elbows Note Use DVP Series components only 1 Top Vent Horizontal Termination continued Figure 4 7 Note 12 inches minimum vertical is required prior to attaching any elbow to the appliance ...

Page 19: ...t restrictor may be needed The exhaust restrictor can be located in the appliance manual bag Figure 4 9 Exhaust Restrictor NOTICE Before painting contact your dealer for information on the appropriate high temperature paint 4 In some applications such as those where the fire place is elevated off the floor the vent restrictor may be painted but painting is not required 5 Recommended restrictor usa...

Page 20: ...m 2 ft 610 mm 4 ft 1219 mm 3 ft 914 mm 9 ft 2743 mm 4 ft 1219 mm 12 ft 3658 mm 5 ft 1524 mm 15 ft 4572 mm V1 H1 V2 63 ft 19 2 m Maximum H1 H2 23 ft 7 1 m Maximum H1 V1 V2 Figure 4 10 Top Vent Vertical Termination Venting with 2 elbows Note Use DVP Series components only Note 12 inches minimum vertical is required prior to attaching any elbow to the appliance ...

Page 21: ...N FT MAX VERT DROP FT 8 80 ft 12 ft Figure 4 11 INSTALLED HORIZONTALLY H1 H2 V1 V2 Top Vent Vertical Termination Venting with 3 elbows Note Use DVP Series components only Note 12 inches minimum vertical is required prior to attaching any elbow to the appliance NOTE Maximum total vent run Total vertical vent run Total horizontal vent run MAXIMUM VERTICAL DROP FROM APPLIANCE Note The RED40 has been ...

Page 22: ...ation for regarding the instal lation of a horizontal termination cap Non Combustible Wall Penetration If the hole being penetrated is surrounded by non com bustible materials such as concrete a hole with diameter one inch greater than the pipe is acceptable Whenever a non combustible wall is penetrated the wall shield firestop is only required on one side and no heat shield is necessary Figure 5 ...

Page 23: ...NING Risk of Fire DO NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating ATTIC ABOVE A PIPE DVP A 10 in 254 mm A INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRESTOP INSTALLED BELOW CEILING CEILING FIRESTOP INSTALLED ABOVE CEILING D Install Attic Insulation Shield WARNING Fire Risk DO NOT allow loose materi...

Page 24: ... 2 Place first twelve inch vent section on the starting collar WARNING Risk of Fire A MINIMUM of twelve inches vertical pipe is required prior to attaching any elbow to the appliance 3 Place fiberglass rope ring over initial twelve inch vent section and position tightly to top of appliance 4 Remove bottom metal panel by removing four screws Screw locations are shown in Figure 6 1 The two screws on...

Page 25: ...e Secure the appliance to the framing by using nails or screws through the nailing tabs Figure 6 2 shows the fireplace installed on the floor However this fireplace can be elevated off the floor provided that the fireplace is properly supported by framing materials and the ceiling clearances are maintained Figure 6 2 Proper Positioning Leveling And Securing Of An Appliance NAILING TABS BOTH SIDES ...

Page 26: ...acent interior wall NOTE The 6 in x 5 5 in intake vent cover provided with the appliance must be used The fireplace appliance has been provided with an active convection blower The blower is required to keep lower control chamber component temperatures at an ideal op erating temperature The blower also provides for more efficient use of appliance heat by assisting the convection air around the fir...

Page 27: ...rate inner pipe For 90º and 45º elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe Required Commercial Multi family Multi level exceeding two stories or High Rise Applica...

Page 28: ...d All unit collar pipe slip section elbow and cap outer flues shall be sealed Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and slip section with two screws no longer than 1 2 in 13 mm using the pilot holes in the slip section See Figure 7 6 120º Figure 7 7 Securing Vertical Pipe Sections 120º Figure 7 8 Securing Horizontal Pipe Sections C Secure T...

Page 29: ...l 2155 975 Rev E 12 14 D Disassemble Vent Sections Rotate either section see Figure 7 9 so the seams on both pipe sections are aligned as shown in Figure 7 10 Pull carefully to separate the pieces of pipe Figure 7 10 Align and Disassemble Vent Sections Figure 7 9 Rotate Seams for Disassembly ...

Page 30: ...NG 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING NOTICE Failure to properly caulk the roof flashing and pipe seams could permit entry of water Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing where it contacts the roof surface See Figure 7 12 Caulk the overlap seam of any exposed pipe sections that ...

Page 31: ...p and the horizontal termination cap shown in Figure 7 15 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 15 If the wall thickness does not allow the required 1 1 2 in 38 mm heat shield overlap when installed an extended heat shield m...

Page 32: ... cap base Flash and seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching the h...

Page 33: ...s can cause improper and dangerous operation Verify proper operation after servicing WARNING Risk of Shock Replace damaged wire with type 105º C rated wire Wire must have high temperature insulation Junction Box Installation WARNING Risk of Shock Label all wires prior to dis connection when servicing controls Wiring errors could cause improper and dangerous operation Verify proper operation after ...

Page 34: ...ion Diagram FAN ASSEMBLY FAN ASSEMBLY JUNCTION BOX JUNCTION BOX Optional Accessories Requirements This appliance ships standard with a wall switch and may use a remote control Wiring for optional Hearth Home Technologies approved accessories should be done now to avoid reconstruction Follow instructions that come with those accessories Optional Remote Control Receiver The junction box control modu...

Page 35: ...Ignition module valve pilot and wall switch operate on 3 volts 110 1 20 VAC is required at junction box INTERMITTENT PILOT IGNITOR IGNITION MODULE 3 VAC FAN PLUG IN 3V TRANSFORMER HIGH TEMP SWITCH LOW VOLTAGE SEE NOTE 1 IGNITION MODULE 3V FLAME SPARKER SENSOR LOW VOLTAGE SEE NOTE 1 VALVE GROUND REMOTE CONTROL NEUTRAL ORG WHITE GROUND TO FIREPLACE CHASSIS HIGH LIMIT SWITCH JUMPER JUMPER JUMPER BRN ...

Page 36: ...3 VAC I S PLUG IN PLUG IN PLUG IN BRN LIGHT CONTROL ORANGE YELLOW GREEN RED BRN BRN RED BRN BLK Figure 8 7 LED Wiring Diagram For models with LED lighting option only NOTE The chart below show the colors produced when light control is wired and orientated as shown in this wiring diagram SWITCH TRIPPED COLOR PRODUCED YELLOW GREEN ORANGE RED GREEN BLUE YEL ORG GRN WHITE CLEAR YEL ORG YELLOW ORG GRN ...

Page 37: ...screws from base pan and lift base pan up and out of appliance Set aside See Figure 8 9 and Figure 8 10 Figure 8 10 Lifting Base Pan Up and Out 4 Remove screws from each end of burner assembly Pull burner out of appliance Set aside Figure 8 11 Side Burner Screw SIDE BURNER SCREW 5 Remove left and right side glass pane frames from bottom of firebox Remove glass pane and gaskets Gaskets may have bec...

Page 38: ...ey are located on one side of the bracket Save the gasket for use with the new blower See Figure 8 18 and Figure 8 19 Figure 8 18 Removal of Mounting Bracket from Blower 7 Unplug blower power wires Pull blower mounting bracket toward you and remove hose clamp and air duct Remove blower and attached mounting bracket from the appliance See Figure 8 16 Figure 8 14 Component Tray Figure 8 15 Blower Mo...

Page 39: ...an so that the arrow on the side of the fan points toward the interior of the appliance Arrows are highlighted by white boxes in Figure 8 20 Figure 8 20 Arrow Indicates Direction of Air Flow Figure 8 21 Proper Blower Mounting 10 Attach new blower to mounting bracket by fastening the four screws in the appropriate locations See Figure 8 21 11 Connect electrical cord to the junction box ...

Page 40: ...n other household gas appliances are operating Install regulator upstream of valve if line pressure is greater than 1 2 psig Valve pressure taps are accessible by removing the outer panel tray and glass assembly Figure 9 1 Valve Pressure Taps Note This appliance does include a manual gas shutoff valve that is located in the valve compartment This manual gas shutoff valve is accessible for service ...

Page 41: ...pen flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory D High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or authorities having jurisdiction When installing above 2000 feet elevation I...

Page 42: ...tory for minimum vertical vent run Adjust air shutter for longer vertical runs See Figure 9 5 Loosen the 1 4 in screw Twist shutter to adjust Shutter may be open for longer horizontal vent runs Do not close the air shutter more than 1 16 in for NG or 1 4 in for propane Tighten the screw NOTICE If sooting occurs provide more air by opening the air shutter Air Shutter Settings RED40 RED40ST NG PROPA...

Page 43: ... Glass Damage and Cuts DO NOT drill or install any type of screw or fastener into the lower cover panel Sharp screw or fastener tips may penetrate and break the glass or cause cuts The RED40 comes standard with a mesh front The final fireplace installation can be accomplished by either the overlap or inside fit method This section discusses installation details associated with the Inside and Overl...

Page 44: ... install the hole for the fireplace opening in a single wallboard sheet if possible This will minimize the joints adjacent to the fireplace opening Tape wall board joints around the fireplace opening with fiberglass mesh tape It will provide a more crack resis tant joint than paper tape Fill smooth and finish wall joints with chemically setting type joint compound It will provide a more crack resi...

Page 45: ...OARD Figure 10 5 Non Combustible Finish Material Diagram for 0 1 Inch Thick Overlap Fit Method AIR SPACE NON COMBUSTIBLE BOARD ON FRONT FACE SIDE VIEW COMBUSTIBLE FRAMING 1 2 IN 1 IN 20 3 4 IN FACTORY SUPPLIED NON COMBUSTIBLE BOARD 2 1 2 IN THICK WALL SHEATHING 3 1 2 IN 11 1 4 IN 7 1 4 IN 3 1 2 IN WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all...

Page 46: ...ombustible board Figure 10 6 Inside Fit Method 1 2 IN THICK WALL SHEATHING 0 4 IN 17 1 4 IN 0 4 IN DRYWALL OR EQUIVALENT 1 2 IN 1 2 IN 13 1 8 IN 1 2 IN 16 1 4 IN 1 7 8 IN 1 7 8 IN 17 1 4 IN 1 1 2 IN 1 1 2 IN 46 1 4 IN FIREPLACE VIEWING AREA CLEARANCE FROM VIEWING AREA TO NON COMBUSTIBLE FINISHING MATERIAL INSIDE FIT METHOD 13 1 8 IN 42 3 4 IN Ensure that no non combustible finish materials are in ...

Page 47: ... both sides of opening Combustible Mantel Legs Or Wall Projections Extending Past The Face Of The Fireplace UNLIMITED 6 IN MIN 2 IN MIN FIREPLACE OPENING 4 IN MAX ACCEPTABLE NON COMBUSTIBLE MANTEL LEG ZONE MEASUREMENTS FROM TOP EDGE OF THE OPENING 7 8 9 10 11 12 13 31 TO CEILING 9 10 11 12 8 7 6 25 18 Note For non combustible fireplace finish material marble stone etc specifications refer to Secti...

Page 48: ...for a list of doors that may be used A mesh front is included with the RED40 and RED40ST To attach the mesh front to the appliance use the two mesh brackets These brackets are mounted to the un derside of the top of the appliance viewing area and are fastened to the appliance by two screws on each bracket See Figure 10 11 There are two hanging tabs on the back of the mesh front assembly that are b...

Page 49: ...forward Lift glass assembly up and out Replacing Fixed Glass Assembly 1 Locate glide tabs on lower left and right corners 2 Place glass bottom resting on right and left support Tilt top of glass assembly toward fireplace 3 Allow of the gasketing of the glass assembly to touch the face of the fireplace Lift the glass up and in to upper glass clip flanges 4 Hold bottom of the glass as you allow the ...

Page 50: ...n 25 mm 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45º Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 276 mm 13 mm Finished Height 19 3 4 in 502 mm UNIV AS2 Attic Insulation Shield Tab 1 in 25 4 mm 20 3 4 in 527 mm Pipe Effective Length...

Page 51: ...5 mm 8 in 203 mm Max Effective Length Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Le...

Page 52: ...1 2 in 699 mm RF6M Roof Flashing Multi pak 31 in 787 mm 24 5 8 in 625 mm 13 1 4 in 337 mm RF12M Roof Flashing Multi pak Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B...

Page 53: ... 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm DVP HRC SS NOT APPROVED FOR ALL UNITS 10 7 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm DVP HRC ZC SS NOT APPROVED FOR ALL UNITS PVK 80 For use with IPI and DSI appliances only 11 1 2 in 292 mm 12 1 2 in 318 mm 16 in 406 mm ...

Page 54: ... SLP Power Vent Inline SLP LPC SLP Low Profile Cap Note Wire harnesses required to power the PVI SLP connect to the appliance and are ordered separately from PVI SLP Contact your dealer to order 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN 318 mm 12 1 2 IN 318 mm 20 3 4 IN 527 mm 13 5 8 IN 346 mm Note Use only approved ...

Page 55: ... For safety Install a switch lock or a wall remote control with child protection lockout feature Keep remote controls out of reach of children See your dealer if you have questions Printed in U S A Copyright 2014 Heat Glo a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www heatnglo com Please contact your Heat Glo dealer with any questions or concerns For the location...

Reviews: