Heat & Glo • PIER/ST/L&RCOR-HVB-CE • 2068-900 Rev. K • 6/09
34
102 mm
127 mm
153 mm
178 mm
204 mm
229 mm
254 mm
280 mm
305 mm
51 mm
77 mm
127 mm
153 mm
178 mm
204 mm
228 mm
254 mm
280 mm
305 mm
25.4 mm
HOOD
331 mm
356 mm
381 mm
407 mm
MANTEL
Step 9. Finishing
Figure 30 shows the minimum vertical and corresponding maximum
horizontal dimensions of fi replace mantels or other combustible
projections above the top front edge of the fi replace. See Figures 4
and 5 for other fi replace clearances.
Only non-combustible materials
may be used to cover the black fi replace front.
WARNING: WHEN FINISHING THE FIREPLACE, NEVER
OBSTRUCT OR MODIFY THE AIR INLET/OUTLET
GRILLES IN ANY MANNER.
Figure 30. Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles above Fireplace
CAUTION: IF JOINTS BETWEEN THE FIN-
ISHED WALLS AND THE FIREPLACE SUR-
ROUND (TOP AND SIDES) ARE SEALED,
A 150º C. MINIMUM SEALANT MATERIAL
MUST BE USED. THESE JOINTS ARE NOT
REQUIRED TO BE SEALED. ONLY NON-
COMBUSTIBLE MATERIAL (USING 150° C.
MINIMUM ADHESIVE, IF NEEDED) CAN BE
APPLIED AS FACING TO THE FIREPLACE
SURROUND (SEE FIGURE 31).
NOTE:
Sheetrock or other combustible
material such as wood can be placed on
the top edge and sides of the fi replace.
Figure 31. Sealant Material
ST-HVB-CE
PIER-HVB-CE and L/RCOR-HVB-CE
TOP
EDGE
0 mm GAG
0 mm GAG
SIDE
EDGE
TOP
EDGE
SIDE
EDGE
NOTE:
305 mm (12 in.) mantel at
407 mm (16 in.) above hood.
CAUTION: LABEL ALL WIRES PRIOR TO
DISCONNECTION WHEN SERVICING CON-
TROLS. WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERA-
TION. VERIFY PROPER OPERATION AFTER
SERVICING.
Step 8. Wiring the Fireplace
NOTE: Electrical wiring must be installed by a licensed electrician.
For Standing Pilot Ignition Wiring
Appliance Requirements
Optional Accessories
Optional remote control kits require that 230 VAC be wired to the factory
installed junction box before the fi replace is permanently installed.
Wall Switch
Position the wall switch in the desired position on a wall. Run a
maximum of 780cm or less length of 0.102 cm diameter minimum wire
and connect it to the fi replace ON/OFF switch pigtails.
WARNING: DO NOT CONNECT
230 VAC TO THE GAS CONTROL
VALVE OR THE APPLIANCE WILL
MALFUNCTION AND THE VALVE
WILL BE DESTROYED
.
!
!