background image

Heat & Glo  •  ST-36TRB-IPI, PIER-36TRB-IPI, LCOR-36TRB-IPI, RCOR-36TRB-IPI  •  2128-900 Rev. i  •  3/13

38

D.  Vertical Penetration Framing

Figure 8.6

Figure 8.7  Installing the Attic Shield

3 FASTENERS

PER SIDE

INSTALL ATTIC INSULATION SHIELDS

BEFORE OR AFTER INSTALLATION OF VENT SYSTEM

CEILING FIRESTOP

INSTALLED BELOW CEILING

CEILING FIRESTOP

INSTALLED ABOVE CEILING

ATTIC ABOVE

A

PIPE

DVP

SLP

A

10 in. (254 mm)

9 in. (229 mm)

A

A ceiling fi restop 

MUST

 be used between 

fl oors and attics.

• 

DVP pipe only

 - Frame an opening 10 in. 

by 10 in. (254 mm by 254 mm) whenever 
the vent penetrates a ceiling/fl oor  (see 
Figure 8.6).

• 

SLP pipe only

 - Frame opening 9 in. x 9 

in. (229 mm x 229 mm) whenever the vent 
penetrates a ceiling/fl oor (see Figure 8.6).

•  Frame the area with the same sized lumber 

as used in ceiling/fl oor joist.

• The ceiling fi restop may be installed above or 

below the ceiling joists when installed with a 
attic insulation shield. It must be under joists 
between fl oors that are not insulated.  Refer 
to Figure 8.7.

•  Secure with three fasteners on each side.

WARNING! Risk of Fire! DO NOT pack insu-
lation around the vent. Insulation must be kept 
back from the pipe to prevent overheating.

Summary of Contents for LCOR-36TRB-IPI

Page 1: ...lified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or technicians supervised by an NFI certified professional Leave this manual with party responsible for use and operation DO NOT DISCARD WARNING Important operating and maintenance instructions included Read understand and follow these instructions for safe installation and operation In the Commonweal...

Page 2: ...tion Serial Number Type of Gas Model Number Not Not for for use use with with solid solid fuel fuel Ne Ne doit doit pas pas entre entre utilise utilise avec avec un un combustible combustible solide solide This This appliance appliance must must be be installed installed in in accordance accordance with with local local codes codes if if any any if if not not follow follow ANSI ANSI Z223 1 Z223 1 ...

Page 3: ...tions 17 C Tools and Supplies Needed 17 D Inspect Appliance and Components 17 5 Framing and Clearances A Selecting Appliance Location 18 B Constructing the Appliance Chase 19 C Clearances 19 D Mantel and Wall Projections 21 6 Termination Locations A Vent Termination Minimum Clearances 23 7 Vent Information and Diagrams A Approved Pipe 25 B Vent Table Key 25 C Use of Elbows 25 D Measuring Standards...

Page 4: ... 59 14 Appliance Setup A Remove Fixed Glass Assembly 60 B Remove the Shipping Materials 60 C Clean the Appliance 60 D Accessories 60 E Lava Rock and Glowing Ember Placement 60 F Install the Log Assembly 61 G Fixed Glass Assembly 63 H Install Trim Kits and Surrounds 63 I Air Shutter Setting 63 15 Troubleshooting A Intellifire Ignition System 64 16 Reference Materials A Appliance Dimension Diagram 6...

Page 5: ...e date of original purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier The warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupanc...

Page 6: ...PRESSED WARRANTY SPECIFIED ABOVE WARRANTY EXCLUSIONS This warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enameled surfaces caused by fingerprints accidents misuse scratches melt...

Page 7: ...s made of or surfaced with wood compressed pa per plant fibers plastics or other material that can ignite and burn whether flame proofed or not or plastered or unplastered shall be considered combustible materials NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is tested and approved as either supplemen tal room heat or as a decorative appliance It should not be factored as primary he...

Page 8: ...y vented gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and sign...

Page 9: ...all one HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other flammable materials Keep clothing f...

Page 10: ...child protection lockout feature Keep remote controls out of reach of children See your dealer if you have questions CLEAR SPACE 3 FT IN FRONT OF FIREPLACE H Before Lighting Fireplace Before operating this fireplace for the first time have a qualified service technician Verify all shipping materials have been removed from inside and or underneath the firebox Review proper placement of logs ember m...

Page 11: ... smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT LINE VOLT AGE 110 120 VAC OR 220 240 VAC TO THE CONTROL VALVE Improper installation adjustment al teration service or maintenance can cause injury or property da...

Page 12: ...arms this condensation will disappear Blue flames This is a result of normal operation and the flames will begin to yellow as the fireplace is al lowed to burn for 20 to 40 minutes Odor from fireplace When first operated this fireplace may release an odor for the first several hours This is caused by the curing of materials from manufacturing Odor may also be released from finish ing materials and...

Page 13: ...t cleaning may be required due to lint from carpeting or other factors Control compartment burner and circulating air passageway of the fireplace must be kept clean CAUTION Risk of Burns The fireplace should be turned off and cooled before servicing When properly maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technicia...

Page 14: ...sed to heat Confirm there is no damage to glass or glass frame Replace as necessary Verify that fixed glass assembly is properly retained and attachment components are intact and not damaged Replace as necessary Logs Frequency Annually By Qualified Service Technician Tools needed Protective gloves Inspectfordamagedormissinglogs Replaceasnecessary Refer to Section 14 for log placement instructions ...

Page 15: ...o prevent premature battery failure or leaking Check for smooth lighting and ignition carryover to all ports Verify that there is no ignition delay Inspect for lifting or other flame problems Verify air shutter setting is correct See Section 14 for required air shutter setting Verify air shutter is clear of dust and debris Inspect orifice for soot dirt and corrosion Verify orifice size is correct ...

Page 16: ... CEILING FIRESTOP ON FLOOR OF ATTIC SECTION 8 C VERTICAL TERMINATION CAP SECTION 10 E VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS SECTION 8 D FRAMING HEADED OFF IN CEILING JOISTS SECTION 8 C GAS LINE SECTION 11 C MANTEL AND MANTEL LEG SECTION 5 D SURROUND HEARTH EXTENSION VENT PIPE SECTION 9 and 10 OPTIONAL WALL SWITCH STORM COLLAR SECTION 10 H NON COMBUSTIBLE ROOF FLASHING...

Page 17: ...sk of Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry C Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Non corrosive leak check solution Hammer Phillips screwdriver Gloves Framing square Vol...

Page 18: ... Due to high temperatures the appliance should be locat ed out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 5 1 Appliance Locations PIER ST RCOR LCOR 36 in 914 mm 36 in 914 mm 36 in 914 mm 36 in...

Page 19: ...ith caulk with a minimum of Figure 5 2 Clearances to Combustibles ST 36TRB IPI C Clearances NOTICE Install appliance on hard metal or wood surfaces extending full width and depth DO NOT install directly on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to appliance and vent pipe Insulation and other materials must be se...

Page 20: ...pening Width Rough Opening Depth Inches 10 8 5 8 38 1 8 23 40 31 5 8 0 0 1 2 36 Millimeters 254 219 968 584 1016 803 0 0 13 914 C A B D Figure 5 4 Clearances to Combustibles LCOR 36TRB IPI and RCOR 36TRB IPI Adjust framing dimensions for interior sheathing such as sheetrock RCOR 36TRB IPI LCOR 36TRB IPI A B C D E F G H I DVP Pipe SLP Pipe Rough Opening Height DVP Pipe Rough Opening Width Clearance...

Page 21: ...nishing material closer than the minimums listed must be constructed entirely of noncom bustible materials i e steel studs concrete board etc Figure 5 5 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles Figure 5 6 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles MEASUREMENTS FROM TOP EDGE OF THE OPENING 10 11 12 18 9 8 7 6 1 2 3 4 5 6 12 32 MAX MIN TO CEILING MEA...

Page 22: ...nlimited 1 in Max FIREPLACE OPENING Note Clearance from opening to perpendicular wall Figure 5 10 Non Combustible Zone PIER and ST Figure 5 9 Combustible Mantel Leg or Wall Projections Acceptable on both sides of opening Figure 5 11 Non Combustible Zone LCOR and RCOR SHEETROCK AIR SPACE REQUIRED 3 5 in SHEETROCK AIR SPACE REQUIRED 3 5 in ...

Page 23: ...NG 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 6 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire WARNING Gas Wood or Fuel Oil Termination Cap B Gas Termination Cap A If ...

Page 24: ... V V M H or i V G X V H A V V H Electrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMAX 2 termination caps x QACTUAL Covered A...

Page 25: ...216 mm vertical run A length of straight pipe is allowed between two 45º elbows see Figure 7 1 Figure 7 1 7 7 Vent Information and Diagrams B Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams D Measuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards Pipe measurements are shown using the ...

Page 26: ...uns may be level E Vent Diagrams Top Vent Horizontal Termination Two 45 Elbows Installation requirements to replace the first 90 elbow with two 45 elbows 4 ft min 1 22 m 16 ft max 4 87 m Figure 7 3 Note TheMulti Sidedseriesfireplacescanadapt to SLP series vent pipe if desired Whenventingoffthetopoftheunit attachaDVP 2SLadapterto theappliancestartingcollar immediatelyfollowedbyaminimum 48 inch vert...

Page 27: ...mm 6 in 152 mm 2 1 2 ft 610 mm 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 3 ft 914 mm 9 ft 2 7 m 4 ft 1 2 m 12 ft 3 7 m 5 ft 1 5 m 15 ft 4 6 m 6 ft 1 8 m 18 ft 5 5 m V1 H1 50 ft 15 2 m Maximum H1 18 ft 5 5 m Maximum V1 Minimum H1 H2 Maximum Elbow only 6 in 152 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 3 ft 914 mm 9 ft 2 7 m 4 ft 1 2 m 12 ft 3 7 m 5 ft 1 5 m 15 ft 4 6 m 6 ft 1 8 m 18 ft...

Page 28: ...um H1 H2 Maximum Elbow only 1 ft 305 mm 6 in 152 mm 1 ft 305 mm 6 in 152 mm 1 ft 305 mm 6 in 152 mm 3 ft 914 mm 6 in 152 mm 2 ft 610 mm 1 ft 305 mm 3 ft 914 mm 1 ft 305 mm 6 ft 1 8 m 1 ft 305 mm 6 ft 1 8 m 2 ft 610 mm 12 ft 3 7 m 2 ft 610 mm 10 ft 3 m 2 ft 610 mm 10 ft 3 m 4 ft 1 2 m 18 ft 5 5 m 3 ft 914 mm 12 ft 3 7 m 3 ft 914 mm 12 ft 3 7 m 6 ft 1 8 m 18 ft 5 5 m H1 H2 18 ft 5 5 m Maximum V1 V2 ...

Page 29: ...al Termination No Elbow NOTE If installing a vertical vent termination off the top of the appli ance the optional vertical termina tion baffle should be used V1 Figure 7 7 Figure 7 8 Exhaust restrictors are recommended for these verti cally terminated products which have excessive draft Exhaust restrictors will compensate for high draft and restore visual flame height If the vent configuration has...

Page 30: ...10 1 2 3 4 5 SETTINGS 1 2 3 4 5 Vertical TOP VENT REAR VENT NG LP NG LP 4 ft 1 1 No Restrictor No Restrictor No Restrictor 8 ft 2 2 1 2 1 1 No Restrictor 15 ft 3 3 3 2 2 2 1 2 20 ft 3 4 3 3 3 3 2 3 25 ft 3 4 3 3 3 3 2 3 30 ft 4 4 3 4 3 4 3 3 35 ft 4 4 3 4 3 4 3 3 40 ft 5 4 4 4 4 4 3 4 45 ft 5 4 4 4 4 4 3 4 50 ft 5 5 5 4 5 4 4 4 55 ft 5 5 5 4 5 4 4 4 Note If the DVP 2SL adapter and SLP pipe is used...

Page 31: ... 1 8 m 18 ft 5 5 m V1 V2 H1 50 ft 15 2 m Maximum No specific restrictions on this value EXCEPT V1 V2 H1 cannot exceed 50 ft 15 2 m V1 H1 H2 V2 V1 V2 Minimum H1 H2 Maximum ELBOW ONLY 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 4 ft 1 2 m 3 ft 914 mm 9 ft 2 7 m 9 ft 2 7 m 4 ft 1 2 m 12 ft 3 7 m 12 ft 3 7 m 6 ft 1 8 m 18 ft 5 5 m 18 ft 5 5 m H1 H2 18 ft 5 5 m Ma...

Page 32: ... LCOR 36TRB IPI RCOR 36TRB IPI 2128 900 Rev i 3 13 32 3 Rear Vent Horizontal Termination Figure 7 13 Figure 7 14 No Elbow One 45 Elbow H1 16 in 406 mm Maximum H1 H1 DO NOT use a 45º elbow in corner installations Use two 90º elbow instead ...

Page 33: ...914 mm 3 ft 914 mm 7 ft 2 1 m 9 ft 2 7 m 3 ft 914 mm 4 ft 1 2 m 10 ft 3 m 12 ft 3 7 m 3 ft 914 mm 5 ft 1 5 m 12 ft 3 7 m 15 ft 4 6 m 3 ft 914 mm 6 ft 1 8 m 15 ft 4 6 m 18 ft 5 5 m V1 H1 H2 50 ft 15 2 m Maximum H1 3 ft 914 mm Maximum H1 H2 18 ft 5 5 m Maximum H1 Maximum V1 Minimum H2 H3 H1 H2 H3 Maximum 6 in 152 mm 6 in 152 mm 6 in 152 mm 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm 2 ft 610 mm 3 ft 914 mm ...

Page 34: ...RIZONTALLY H2 V2 H1 V1 Minimum H1 Maximum 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm 7 ft 2 1 m 4 ft 1 2 m 8 ft 2 4 m 5 ft 1 5 m 8 ft 2 4 m V1 H1 40 ft 12 2 m Maximum V1 Minimum H1 H2 Maximum Back to Back 90 Elbows 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 4 ft 1 2 m 9 ft 2 7 m 5 ft 1 5 m 10 ft 3 m 6 ft 1 8 m 12 ft 3 7 m V1 H1 H2 50 ft 15 2 m Maximum H1 H2 16 ft 4 9 m Maximum ...

Page 35: ... 1 m 6 ft 1 8 m No specific restrictions on this value EXCEPT V1 H1 H2 H3 cannot exceed 50 ft 15 2 m Maximum H1 H2 H3 6 ft 1 8 m Maximum H1 Maximum V1 Minimum H2 H1 H2 Maximum 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 3 ft 914 mm 5 ft 1 5 m 4 ft 1 2 m 3 ft 914 mm 4 ft 1 2 m 8 ft 4 6 m 5 ft 1 5 m 4 ft 1 2 m 6 ft 1 8 m 11 ft 3 4 m 6 ft 1 8 m 5 ft 1 5 m 8 ft 2 4 m 14 ft ...

Page 36: ... isting heat shields must be field trimmed f wall thickness is greater than 7 5 8 in a DVP HSM B will be required DVP SLP Pipe Shown 3 in 76 mm top clearance 1 in 25 mm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance aro...

Page 37: ...e side only on interior walls If your local inspector requires a wall shield firestop on both sides then both wall shield firestops must have a heat shield refer to Section 16 B attached to them See Section 10 M for information for regarding the in stallation of a horizontal termination cap Non Combustible Wall Penetration If the hole being penetrated is surrounded by noncom bustible materials suc...

Page 38: ...pe only Frame an opening 10 in by 10 in 254 mm by 254 mm whenever the vent penetrates a ceiling floor see Figure 8 6 SLP pipe only Frame opening 9 in x 9 in 229 mm x 229 mm whenever the vent penetrates a ceiling floor see Figure 8 6 Frame the area with the same sized lumber as used in ceiling floor joist The ceiling firestop may be installed above or below the ceiling joists when installed with a ...

Page 39: ...eld These tabs must be used to prevent blown insulation from getting between the shield and vent pipe and to maintain air space clearance Figure 8 8 Attic Insulation Shield Vaulted Ceiling Installation Remove one shield from box NOTICE Cut previously installed batt insulation to make room for the attic insulation shield Cut the attic insulation shield if application is for vaulted ceiling to fit y...

Page 40: ...donut insulation plug and the insulation basket Attach the first vent section it will snap into place Slide the vent gasket onto the vent section and then up against the ap pliance Secure the vent gasket to the appliance with two self tapping screws found in the manual bag Note The vent gasket can found in the manual bag Proceed to Section 9 C Figure 9 1 Remove the elbow heat shield by removing th...

Page 41: ...OT be reattached Figure 9 5 Cut the metal retaining band Figure 9 6 Remove the seal cap Figure 9 7 Discard the seal cap insulation plug and the insulation basket Figure 9 8 Attach the first vent section it will snap into place Slide the vent gasket onto the vent section and then up against the appliance Secure the vent gasket to the appliance with two self tapping screws found in the manual bag No...

Page 42: ...d on the side of the unit and reattach it to the front corner of the unit as shown in Figure 9 9 R COR Figure 9 11 Securing An Appliance NAILING TABS Note Once appliance is setup for top or rear venting it CANNOT be changed at a later time Figure 9 10 Proper Positioning and Leveling of an Appliance 90º SIDE TO SIDE FRONT TO BACK 3 Place the appliance into position making sure to maintain proper cl...

Page 43: ...ther If predrilling holes DO NOT penetrate inner pipe For 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe Commercial Multi family Multi level exceeding two s...

Page 44: ...need to be sealed All unit collar pipe slip section elbow and cap outer flues shall be sealed in this manner unless otherwise stated Figure 10 5 Adding Venting Components WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when remov ing termination cap from slip pipe If slip section seals are broken during removal of the termination cap vent may leak Note Align...

Page 45: ...st be supported every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal runs must be supported every 5 feet 1 52 m Vent supports or plumbers strap spaced 120º apart may be used to support vent sections See Figures 10 8 and 10 9 Wall shield firestops may be ...

Page 46: ...ine of the cathedral ceiling support box on the outside roof Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box Cut the hole 1 8 in 3 mm larger than the support box outline Lower the support box through the hole in the roof until its bottom is at least 2 in 51 mm below the ceiling Figure 10 12 Level the support box both vertically and horizontally a...

Page 47: ...Cuts Abrasions or Flying Debris Wear protective gloves and safety glasses during instal lation Sheet metal edges are sharp Connect both halves of the storm collar with two screws see Figure 10 16 Wrap the storm collar around the exposed pipe section closest to the roof and align brackets Insert a bolt provided through the brackets and tighten the nut to complete the storm collar assembly Make sure...

Page 48: ... Termination WARNING Risk of Fire To prevent overheating and fire heat shields must extend through the entire wall thick ness DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 10 20 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firest...

Page 49: ...T OUTER VENT EXTERIOR Note When using termination caps with factory supplied heat shield attached no additional wall shield firestop is required on the exterior side of a combustible wall L Install Horizontal Termination Cap DVP and SLP Pipe WARNING Risk of Fire The telescoping flue section of the termination cap MUST be used when connecting vent 1 1 2 38 mm minimum overlap of flue telescoping sec...

Page 50: ...ble leak check solution DO NOT use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire Explosion High pressure will damage valve Low pressure may cause explosion Verify inlet pressures Verify minimum pressures when other household gas appliances are ope...

Page 51: ...circuit Incorrect wiring will override IPI safety lockout Refer to Figures 12 1 and 12 2 Intellifire Pilot Ignition IPI Wiring Diagram This appliance is equipped with an Intellifire control valve which operates on a 3 volt system Plug the 3 volt AC transformer into the appliance junction box to supply power to the unit OR install two D cell batteries not included into the battery pack before use N...

Page 52: ...e on 3 volts 110 120 VAC is required at junction box unless equipped with battery back up TRANSFORMER 3 VAC PLUG IN BLACK RED BATTERY PACK WIRE ASSEMBLY WIRES TO BROWN ORANGE GREEN VALVE HOT NEUTRAL GROUND TO FIREPLACE CHASSIS WHITE ORANGE IGNITION MODULE 3 VAC INTERMITTENT PILOT IGNITOR I S TRANSFORMER 3 VAC PLUG IN PLUG IN BLACK RED BATTERY PACK REMOTE WIRES TO BROWN ORANGE GREEN VALVE GROUND TO...

Page 53: ...n Box Detail NOTICE DO NOT wire 110 120 VAC to wall switch RED SWITCH SWITCH BOX RED BLACK BLACK GREEN GREEN WHITE POWER SUPPLY WIRES WHITE RED BLACK GREEN WHITE MINIMUM 14 3 AWG WITH GROUND JUNCTION BOX KNOCKOUT Figure 12 4 Junction Box Wired to Wall Switch E Junction Box Installation The junction box must be wired from the INSIDE of the appliance Determine which side of the appliance the junctio...

Page 54: ...terial used to protect the appliance during the installation process before finishing work on the whole hearth is complete Splatter guards may be factory installed or accompany the door of the unit depending on the fire place model Splatter guards must be removed before appliance is fired WARNING Risk of Fire Close the ball valve before in stalling the splatter guard to prevent accidental lighting...

Page 55: ... the tabs on left and right bottom of splatter guard and fit them into the square holes The tabs are now inside the front of the splatter guard carefully bend them down See Figure 13 9 To Close the Lower Access Panel Carefully disengage the tabs from the square holes and bend the access panel to its original position Bend the center bottom flap and insert it into the bottom of the ap pliance To Re...

Page 56: ...the minimums list ed must be constructed entirely of noncombustible materi als i e steel studs concrete board etc Failure to comply could cause fire Figure 13 12 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles Figure 13 13 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles MEASUREMENTS FROM TOP EDGE OF THE OPENING 10 11 12 18 9 8 7 6 1 2 3 4 5 6 12 32 MAX MIN TO ...

Page 57: ...n Top and Side Seal Joint Figure 13 17 Noncombustible Facing Diagram Figure 13 19 Overlap Fit Door Figure 13 18 Folio Door and Aero DOOR FIT FINISH MATERIAL MAXIMUM THICKNESS SEE FIGURE Aero Inside Any 13 18 Folio Inside Any 13 18 Arcadia Overlap 1 inch 13 19 Inside Any 13 20 Halston Overlap 1 inch 13 19 Inside 1 inch 2 inch 13 21 Chateau Overlap 1 inch 13 19 Inside Any 13 20 Valencia Overlap 1 in...

Page 58: ...e of door 37 in 37 1 4 in Finishing materials over 1 inch thick Finishing material between 1 and 2 inches thick 37 in 33 3 4 in Inside door height 37 1 4 in 34 in Outside door width Includes 1 8 in opening each side of door FINISHING MATERIAL FINISHING MATERIAL IF FINISHING MATERIAL IS THICKER THAN 2 IN DOORS WILL ONLY OPEN AS FAR AS PICTURED DOORS 37 1 4 IN 33 3 4 IN 34 IN Figure 13 22 Pier Door ...

Page 59: ...CRIPTION PART ELEVATED APPLIANCE DIMENSION See Note 1 MARBLE LEG CUT LENGTH See Note 2 KENWOOD MANTEL AFKDMPB 0 See Note 3 27 3 8 in KENWOOD MANTEL W BASE AFKDMPB W HTKDMPB 9 1 4 in 29 3 8 in LAURENT SURROUND LAURENT 36 1 1 2 in N A CAMDEN SURROUND CAM36PG 0 N A CAMDEN SURROUND W HEARTH CAM36PGH 1 3 4 in N A CAMDEN SURROUND W MANTEL CAMM36PG 0 N A CAMDEN SURROUND W MANTEL HEARTH CAMM36PGH 1 3 4 in...

Page 60: ...ace ember material annually Improperly placed embers interfere with proper burner operation Placing the Ember Material Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over ports Care should be taken not to cover the lighting trail of ports from back to front When placing Glowing Embers onto the burner care should be taken so that the p...

Page 61: ...ve the logs and cardboard tray from the inside of the fireplace See Figure 1 Remove the microfoam and inspect the logs for damage Inspect the four factory installed logs for damage Locate the pilot in order to verify your position in relation to the appliance See Figure 2 STEP 2 Log 1 SRV2128 704 Mate the notch on the end of log 1 with the hump on top of log A Set the other end of Log 1 onto the s...

Page 62: ...contact with the second grate tine from the left Mate the bottom of log 2 with the notches on top of log B and the smooth area on top of the end of log C Figure 6 Placement of Log 2 Figure 6 Placement of Log 2 1 1 A A 2 2 B B D D C C GRATE TINES GRATE TINES STEP 4 Log 3 SRV2128 707 The bottom end of log 3 should come in contact with the far left grate tine Mate the bottom of log 3 with the indenta...

Page 63: ... 14 3 Fixed Glass Assembly G Fixed Glass Assembly WARNING Risk of Asphyxiation Handle fixed glass assembly with care Inspect the gasket to ensure it is undamaged and inspect the glass for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Air Shutter Settings H Install Trim Kits and Su...

Page 64: ...ilot assembly for shorted sparker wire or cracked insulator around electrode Replace pilot if necessary 2 Pilot won t light there is no noise or spark a No power or transformer installed incorrectly Verify that transformer is installed and plugged into module Check voltage of transformer under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good transf...

Page 65: ... Verify correct pilot orifice is installed and gas inlet is set to pressure specifications Polish flame sensing rod with fine steel wool to remove any contaminants that may have accumulated on flame sensing rod c Module is not grounded Verify module is securely grounded to metal chassis of appliance Verify that wire harness is firmly connected to the module d Damaged pilot assembly or contami nate...

Page 66: ...ng dimensions and clearances refer to Section 5 Figure 16 1 See Through Dimensions B C FRONT VIEW RIGHT VIEW ELECTRICAL ACCESS GAS LINE ACCESS LEFT VIEW A P J Ø K L Ø K D F G H M O i N E TOP VIEW Location Inches Millimeters I 1 1 2 38 J 27 686 K 8 203 L 12 305 M 9 1 2 241 N 38 965 O 34 5 8 880 P 24 610 Location Inches Millimeters A 36 914 B 42 1 2 1080 C 24 1 2 622 D 33 1 2 851 E 1 25 F 2 1 8 54 G...

Page 67: ...VIEW RIGHT VIEW LEFT VIEW A P L Ø K D M O N E ELECTRICAL ACCESS GAS LINE ACCESS J Ø K F G H i TOP VIEW Location Inches Millimeters I 1 1 2 38 J 27 686 K 8 203 L 12 305 M 9 1 2 241 N 38 965 O 34 5 8 880 P 24 610 Location Inches Millimeters A 36 914 B 40 1 2 1029 C 24 1 2 622 D 33 1 2 851 E 1 25 F 2 1 8 54 G 4 1 8 105 H 4 1 4 108 ...

Page 68: ... VIEW RIGHT VIEW ELECTRICAL ACCESS GAS LINE ACCESS LEFT VIEW A J Ø K L Ø K D F G H M P N i O E TOP VIEW Location Inches Millimeters I 1 1 2 38 J 27 686 K 8 203 L 12 305 M 9 1 2 241 N 24 1 2 622 O 38 965 P 34 5 8 880 Location Inches Millimeters A 36 914 B 40 1 2 1029 C 24 1 2 622 D 33 1 2 851 E 1 25 F 2 1 8 54 G 4 1 8 105 H 4 1 4 108 ...

Page 69: ...n 254 mm 1 in 25 mm 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 124 mm 13 mm Assembled Height 24 in 610 mm Diameter 10 in 254 mm DVP AS2 Pipe Effective Length Inches Millimeters DVP4 4 10...

Page 70: ...m of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield B Vent Components Diagrams continued Figure 16 5 DVP vent components Term Cap Minimum Effective Length Maximu...

Page 71: ...k BEK Trap Cap Brick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield B Vent Components Dia...

Page 72: ...DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap PVK 80 For use with IPI and DSI appliances only 11 1 2 in 292 mm 12 1 2 in 318 mm 16 in 406...

Page 73: ...ss PVI WH40 60 ft PV Wire Harness PVI WH60 80 ft PV Wire Harness PVI WH80 100 ft PV Wire Harness PVI WH100 PVI SLP Power Vent Inline SLP LPC SLP Low Profile Cap Note Wire harnesses required to power the PVI SLP connect to the appliance and are ordered separately from PVI SLP Contact your dealer to order 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 m...

Page 74: ...n 165 mm 6 5 8 in 168 mm 9 7 8 in 251 mm 6 1 2 in 165 mm 9 1 4 in 235 mm Effective Height Length Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 6 51 152 SLP12A 2 12 51 305 SLP FLEX 2 24 610 SLP FLEX 3 36 914 SLP FLEX 5 60 1524 SLP FLEX 10 120 3048 SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Fi...

Page 75: ...er 26 in 660 mm DVP HSM B Extended Heat Shield SLP TRAP Horizontal Termination Cap 15 1 8 in 384 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HS...

Page 76: ...Log B SRV2128 702 C Log C SRV2128 703 D Log D SRV2128 706 1 Log 1 SRV2128 704 2 Log 2 SRV2128 705 3 Log 3 SRV2128 707 4 Glass Door Assembly End GLA 2130 Y 5 Burner NG LP 2128 007 Y 6 Pilot Shield 2128 124 7 Base Pan Grate Assembly 2128 005 8 Glass Door Assembly Side GLA 750TR Y 9 Thermostat Wire 2118 170 Y 10 Junction Box 4021 013 Y 11 Junction Box Bracket 2128 128 12 Sheetrock Ledge Side 2130 118...

Page 77: ...B Log B SRV2128 702 C Log C SRV2128 703 D Log D SRV2128 706 1 Log 1 SRV2128 704 2 Log 2 SRV2128 705 3 Log 3 SRV2128 707 4 Sheetrock Ledge side 2130 118 5 Refractory Panel 2129 016 6 Burner NG LP 2128 007 Y 7 Pilot Shield 2128 124 8 Base Pan Grate Assembly 2128 005 9 Glass Door Assembly Side Qty 2 req GLA 750TR Y 10 Thermostat Wire 2118 170 Y 11 Junction Box 4021 013 Y 12 Junction Box bracket 2128 ...

Page 78: ... Log B SRV2128 702 C Log C SRV2128 703 D Log D SRV2128 706 1 Log 1 SRV2128 704 2 Log 2 SRV2128 705 3 Log 3 SRV2128 707 4 Sheetrock Ledge Side 2130 118 5 Refractory End 2129 016 6 Burner NG LP 2128 007 Y 7 Pilot Shield 2128 124 8 Base Pan Grate Assembly 2128 005 9 Glass Door Assembly Side GLA 750TR Y 10 Thermostat Wire 2118 170 Y 11 Junction Box 4021 013 Y 12 Junction Box bracket 2128 128 13 Glass ...

Page 79: ...2128 Y A Log A SRV2128 701 B Log B SRV2128 702 C Log C SRV2128 703 D Log D SRV2128 706 1 Log 1 SRV2128 704 2 Log 2 SRV2128 705 3 Log 3 SRV2128 707 4 Sheetrock Ledge 2128 118 5 Refractory Left 2129 017 Refractory Right 2129 016 6 Burner NG LP 2128 007 Y 7 Base Pan Grate Assembly 2128 005 8 Glass Door Assembly Qty 2 req GLA 750TR Y 9 Thermostat Wire 2118 170 Y 10 Pilot Shield 2128 124 11 Junction Bo...

Page 80: ...S PART NUMBER 15 1 Shutter Bracket Assembly 2118 121 Y 15 2 Pilot Assembly NG 2090 012 Y Pilot Assembly LP 2090 013 Y 15 3 Flexible Gas Connector 530 302A Y 15 4 Orifice NG 32C 582 832 Y Orifice LP 50C 582 850 Y 15 5 Valve NG 750 500 Y Valve LP 750 501 Y 15 6 Battery Pack 593 594A Y 15 7 Module 593 592 Y 15 8 Flex Ball Valve Assembly 302 320A Y 15 9 3 Volt Transformer 593 593A Y 15 10 Module Wire ...

Page 81: ...is manual may be ordered from an authorized dealer Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER Exhaust Baffle 385 105 Flue Restrictor 385 128 Gasket Assembly 2128 081 Contains Vent Seal Cap Burner Neck Shutter Bracket and Valve Plate Gaskets Glass Latch Assembly Pkg of 2 33858 2 Y Lava Rock 2005 790 Mineral Wool 050 721 Touch Up Paint TUP GBK 12 Conversion Kit NG NGK MS36 Y Conversion K...

Page 82: ...________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ Printed in U S A Copyright ...

Reviews: