background image

Heat & Glo  •  FB-IN-S, FB-GRAND-S  •  783-910  Rev. G  •  11/08

31

A.  Standing Pilot Ignition System

13 

13 

Troubleshooting  

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service.  If you do 
experience a problem, this troubleshooting guide will assist a qualifi ed service person in the diagnosis of a problem and the 
corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed service technician. 

Symptom

Possible Causes

Corrective Action

1.  After repeated triggering 
of the red or black piezo 
ignitor button, the spark 
ignitor will not light the pilot.

a. Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode 
wire is properly connected, replace the ignitor.

b. Defective pilot or misaligned 
electrode (spark at electrode).

Using match, light the pilot. If the pilot lights, turn off the pilot and 
trigger the red piezo ignitor button again. If the pilot lights, an im-
proper gas/air mixture caused the bad lighting and a longer purge 
period is recommended. If the pilot will not light, ensure the gap 
at the electrode and pilot is one-eighth (1/8) inch to have a strong 
spark. If the gap is OK, replace the pilot.

c. No gas or low gas pressure.

Check the remote shut-off valves from the fi replace. Usually, there 
is a valve near the gas main. There can be more than one (1) valve 
between the fi replace and the main.

d.  No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2.  The pilot will not stay lit 
after carefully following the 
lighting instructions.

a. Defective thermocouple.

Check that the pilot fl ame impinges on the thermocouple. Clean 
and/or adjust the pilot for maximum fl ame impingement.

Ensure that the thermocouple connection at the gas valve is fully 
inserted and tight (hand tighten plus 1/4 turn).

Disconnect the thermocouple from the valve, place one millivolt 
meter lead wire on the tip of the thermcouple and the other meter 
lead wire on the thermocouple copper lead. Start the pilot and hold 
the valve knob in. If the millivolt reading is less than 15mV, replace 
the thermocouple.

b.  Defective valve.

If the thermocouple is producing more than 15 millivolts, replace 
faulty valve.

3.  The pilot is burning, 
there is no burner fl ame, 
the valve knob is in the ON 
position, and the ON/OFF 
switch is in the ON position.

a. ON/OFF switch or wires 
defective.

Check the ON/OFF switch and wires for proper connections. Place 
the jumper wires across the terminals at the switch. If the burner 
comes on, replace the defective switch. If the switch is OK, place the 
jumper wires across the switch wires at the gas valve. If the burner 
comes on, the wires are faulty or connections are bad.

b. Thermopile may not be gener-
ating suffi cient millivoltage.

If the pilot fl ame is not close enough physically to the thermopile, 
adjust the pilot fl ame.

Be sure the wire connections from the thermopile at the gas valve 
terminals are tight and that the thermopile is fully inserted into the 
pilot bracket.

Check the thermopile with a millivolt meter. Take the reading at 
TH-TP&TP terminals of the gas valve. The meter should read 325 
millivolts minimum, while holding the valve knob depressed in the 
pilot position, with the pilot lit, and the ON/OFF switch in the OFF 
position. Replace the faulty thermopile if the reading is below the 
specifi ed minimum.

With the pilot in the ON position, disconnect the thermopile leads 
from the valve. Take a reading at the thermopile leads. The read-
ing should be 325 millivolts minimum. Replace the thermopile if the 
reading is below the minimum.

Summary of Contents for FB-GRAND-S

Page 1: ...dicated on the rating plate Leave this manual with party responsible for use and operation DO NOT DISCARD Important operating and maintenance instructions included Read understand and follow these ins...

Page 2: ...ppliance can be found on the rating plate usually located in the control area of the appliance Homeowner Reference Information Heat Glo a of Hearth Home Technologies Inc 20802 Kensington Boulevard Lak...

Page 3: ...Venting Components 12 B Connecting Vent Pipe 12 C Placing Securing and Leveling the Appliance 13 D Installing Adaptor and Termination Cap 14 8 Gas Information A Fuel Conversions 15 B Gas Pressures 15...

Page 4: ...ce Heaters and applicable sections of Gas Burn ing Heating Appliances for Manufactured Homes and Recreational Vehicles and Gas Fired Appliances for Use at High Altitudes Models U S 0 2000 ft or Canada...

Page 5: ...local regional state and national codes and regulations Consult insurance carrier local building fire officials or authorities having jurisdiction about restrictions installation inspection and permit...

Page 6: ...acture lines or spider webbing on the surface of the material Cracks that are less than 1 32 in wide and less than 3 in long If cosmetically unacceptable such cracks may be repaired with the SRV PACK...

Page 7: ...affic and away from furniture and draperies The firebrick refractory glass doors screen rails screen mesh and log grates can be removed from a factory built firebox in order to gain minimum gas insert...

Page 8: ...ce to combustible material under the insert is 1 4 inch 0 6 cm Use leveling legs to raise insert minimum 1 4 inch above combustible material or outer wrap of factory built firebox WARNING WARNING MEAS...

Page 9: ...12 to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 6 0 Over 16 12 to 18 12 7 0 Over 18 12 to 20 12...

Page 10: ...ances connected to the flue Vent this appliance directly outside Use separate vent system for this appliance B Horizontal Venting Horizontal venting is NOT allowed 5 5 Vent Information and Diagrams A...

Page 11: ...lid fuels unless all original parts have been replaced and the fireplace re approved by the authority having jurisdiction F Remote Control The receiver for the remotes must be installed BETWEEN the ba...

Page 12: ...ng the factory installed 3 inch collar in the stainless steel section of pipe see Figure 7 1 Use 3 screws to attach either a 4 foot or 30 foot section of inlet air vent to the inlet collar on the coll...

Page 13: ...ther to shorten Install fiberglass insulation pieces to back face of surround Attach surround Follow instructions accompanying surround Push insert so that surround becomes tight against face of firep...

Page 14: ...oof with self tapping screws included in kit Figure 7 4 To help eliminate cold air drafts it may be necessary to place non combustible insulation around the flues as they go though the damper Note The...

Page 15: ...2 psig Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1 2 psig Verify inlet pressures High pressure may cause overfire condition Low pressure m...

Page 16: ...e check with the local gas utility If installing this appliance at an elevation above 4500 feet in Canada check with local authorities CHECK FOR GAS LEAKS Explosion Risk Fire Risk Asphyxiation Risk Ch...

Page 17: ...control See Figure 9 2 for junction box wiring Prevent accidental appliance operation when not attended Unplug or remove batteries from remote control if absent or if appliance will not be used for an...

Page 18: ...s insert is required Detach flexible liner from back of unit if insert is installed Remove the four screws on the cover plate see Figure 9 3 Figure 9 3 FAN COVER PLATE POWER CORD GROUND WIRE Bend up t...

Page 19: ...E MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 1050 C RATED WIRE JUNCTION BOX VARIABLE SPEED CONTROL TEMPERATURE SENSOR SWITCH WHT GRN BLK BLK 110 120 VAC BLOWER BLOWER RECEPTACLE BLK BLK BLK BLK WH...

Page 20: ...ON OFF switch at tached to outer right side of the insert see Figure 10 2 2 Reconnect the low voltage wires to the ON OFF switch 3 Attach surround assembly by hooking the support bracket on the locati...

Page 21: ...d safely D Ember Placement Explosion Risk Follow ember placement instructions in manual Do NOT place embers directly over burner ports Replace ember material annually Improperly placed embers interfer...

Page 22: ...cate the logs with respect to the grate assembly Please refer to grate assembly LOG NUMBER 1 SRV768 701 Place log 1 onto the grate Push log back until it rests against locating tabs B and D E D B A C...

Page 23: ...ross both flat spots on log 1 and log 3 with the Y in log 4 placed on log 1 The back of log 4 should make contact with the back of the firebox LOG NUMBER 2 SRV768 704 Position log 2 onto grate such th...

Page 24: ...BLY This model uses locating tabs to positively locate the logs with respect to the grate assembly Please refer to grate assembly LOG 1 SRV773 701 Position log 1onto the grate such that grooves on bot...

Page 25: ...surface of log LOG 3 SRV768 704 Position log 3 onto grate such that the tab D fits into the slots on bottom surface of log and the right back side of log is flush against tab E LOG 4 SRV573 702 Place...

Page 26: ...s door on the appliance Fasten the latches on the glass frame FIREBOX SURROUND LOCATING TABS G Air Shutter Setting Optimal flame appearance is dependent on the air shutter setting Adjustments should b...

Page 27: ...ation manual provided with this appliance For assistance or additional information consult a qualified installer service agency or the gas supplier Do NOT use this appliance if any part has been under...

Page 28: ...stion and ventilation air If not installed operated and main tained in accordance with the man ufacturer s instructions this product could expose you to substances in fuel or fuel combustion which are...

Page 29: ...products used in the paint and logs During this break in period it is recommended that some windows in the house be opened for air circulation This will help avoid setting off smoke detectors and hel...

Page 30: ...ance Combustible materials may ignite ISSUE SOLUTIONS Condensation on the glass This is a result of gas combustion and temperature variations As the appliance warms this condensation will disappear Bl...

Page 31: ...ame impingement Ensure that the thermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt meter lea...

Page 32: ...tank Check the LP propane tank Refill the fuel tank b Inner vent pipe leaking exhaust gases back into the system Check venting system for damage Replace repair improperly assembled pipe sections c Gl...

Page 33: ...assembly with care NOTE Clean glass after initial 3 4 hours operation Longer operation without cleaning glass may cause a permanent white film on glass CAUTION When cleaning glass door Avoid striking...

Page 34: ...r for inspection 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect f...

Page 35: ...3 16 in 71 mm 9 9 16 in 142 mm REF 15 15 Reference Materials A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For framing dimensions and clearances refer...

Page 36: ...Flex Liner Kits Figure 15 3 Direct Vent Flex Liner Accessory Kits Direct Vent Flex Liner Accessory Kits see Figure 15 3 Flash Damp Zero clearance damper flashing kit for use with LINK DV 30B or LINK D...

Page 37: ...ND S 783 910 Rev G 11 08 37 C Service Parts Service Parts Diagram FB GRAND S Beginning Manufacturing Date Oct 2007 Ending Manufacturing Date ______ Part number list on following page Log Set Assembly...

Page 38: ...783 108A Slide Plate Handle 2019 201 6 Baffle Assembly 2020 046 7 Burner 768 188A Y 8 Control Panel Valve Cover Plate 783 125 9 Piezo Ignitor 291 513 Y 10 Log Grate 768 360A 11 Glass Door Assembly GLA...

Page 39: ...RAND S 783 910 Rev G 11 08 39 Service Parts Service Parts Diagram FB IN S Beginning Manufacturing Date Oct 2007 Ending Manufacturing Date ______ Part number list on following page Log Set Assembly 1 2...

Page 40: ...108A 6 Baffle Assembly 2020 046 Slide Plate Handle 2019 201 7 Burner 773 180A 8 Control Panel Valve Cover Plate 783 125 9 Piezo Ignitor 291 513 Y 10 Log Grate 773 360A 11 Glass Door Assembly Ceramic...

Page 41: ...03 011 Y 2 Pilot Gasket 768 432 3 Burner Orifice NG 125A FB GRAND S 768 801 Y BurnerOrifice NG 31A FB IN S 446 800 Y Burner Orifice LP 50A 446 801 Y 4 Bracket Orifice 778 169 5 Bracket Pilot 783 170 6...

Page 42: ...le under this warranty is limited to the purchase price of the product In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product Adjustments regular...

Page 43: ...d and approved by HHT in writing This warranty does not apply to non HHT venting components hearth components or other accessories used in conjunction with the installation of this product This warran...

Page 44: ..._______________________________________________ ________________________________________________________________________________ Printed in U S A Copyright 2008 This product may be covered by one or m...

Reviews: