background image

Heat & Glo • EXCLAIM-36C Woodburning Fireplace • 4013-093 Rev G • 08/06

21

Slanted Roofs

Flat Roofs

Chimney must
extend 3 ft (.9 m)
above the roof

Chimney must extend 2 ft (.6 m)
above any portion of the roof
within 10 ft (3 m) of the chimney

Chimney must
extend 3 ft (.9 m)
above the roof

Chimney must extend 2 ft (.6 m)
above any portion of the roof
within 10 ft (3 m) of the chimney

Figure 6.1 

Termination Requirements

Figure 6.3 

Ceiling/Attic Construction

Fire Risk

• 

Must maintain 2 in. (51 mm) air clearance 
to insulation and other combustible 
materials.

WARNING

 Gas 

Termination 

    Wood & Fuel Oil Termination

 A 

6 in.  

(152 mm)

              20 in. 

(508 mm)

Gas, Wood or Fuel

Oil Termination

20 in.

(508 mm)

(minimum) to

Perpendicular

Wall

(gas only)

18 in.

(457 mm)

A

Gas

Termination

Figure 6.2 

Multiple Chimneys

Complete the Enclosure 

A. Chimney Termination

Chimney Termination Requirements (See Figures 6.1 and 6.2)

•  Must have a cap approved and listed for this 

¿

 replace system

•  Must not be located where it will become plugged by snow or other material
•  Must terminate at least 3 ft (914 mm) above the roof 

and

 at least 2 ft (610 mm) above any portion of the roof within 10 ft 

(3.05 m)

•  Must be located away from trees or other structures

Mark the Exit Point of the Roof

Locate the point where the chimney will exit the roof by plumbing down to the 
center of the chimney. Drive a nail up through the roof to mark the center. See 
Figure 6.3.

Cut Out the Hole in the Roof

Measure to either side of the nail and mark the 14-1/2 in. x 14-1/2 in. 
(368 mm x 368 mm) opening required. This is measured on the horizontal; 
actual length may be larger depending on the pitch of the roof. Cut out and 
frame the opening. See 

Chapter 25

 of the

 Uniform Building Code

 for roof 

framing details.

Assemble the Chimney Sections Through the Roof

Continue to add chimney sections through the roof opening, maintaining at 
least a 2 in. (51 mm) air space to combustible materials.

Install the Roof Flashing

 

If a roof 

À

 ashing is to be used, install the roof 

À

 ashing appropriate to the 

roof pitch and install a round termination cap and storm collar following the 
instructions shipped with the cap.

Summary of Contents for EXCLAIM-36H-C

Page 1: ...H SEVERE BURNS MAY RESULT CLOTHING IGNITION MAY RESULT WARNING Keep children away CAREFULLY SUPERVISE children in same room as replace Alert children and adults to hazards of high temperatures Keep cl...

Page 2: ...nformation Location The model information regarding your speci c replace can be found on the rating plate located on the smoke shield of the replace Congratulations FIREPLACE NO MODEL NO MODEL NO MFG...

Page 3: ...mney Assembly 20 G Secure the Chimney 20 6 Complete the Enclosure 21 A Chimney Termination 21 B Chase Top 22 C Install the Termination Cap 22 7 Accessories 24 A Gas Log Lighter Provisions 24 8 Finishi...

Page 4: ...pproved as a decorative re place It should not be factored as a primary heat source in residential heating calculations Improper installation adjustment alteration service or maintenance can cause inj...

Page 5: ...return vents are not located in the immediate vicinity of the replace Avoid installing the replace near doors walkways or small isolated spaces Recessed lighting should be a sealed can design attic ha...

Page 6: ...he re Penetrate the highest part of the roof This minimizes the effects of wind turbulence Be located away from trees adjacent structures uneven roof lines and other obstructions Offsets can restrict...

Page 7: ...and surround Decorative facing and trim Hearth extension Factory built fireplace Protective metal hearth strip s Outside combustion air Combustible framing header on top of V shaped standoffs spacers...

Page 8: ...cause odors CAUTION E Inspect Fireplace and Components Carefully remove the replace and components from the packaging The vent system components and doors are shipped in separate packages Report to yo...

Page 9: ...ntel Projections Section 8 C Fireplace Dimensions Section 12 A 48 in 1219 mm 12 in 305 mm Figure 3 1 Fireplace Locations Fire Risk Provide adequate clearances Around air openings To combustibles For s...

Page 10: ...ceiling 2 in min 51 mm 2 in min 51 mm 2 in min 51 mm 2 in min 51 mm 2 in min 51 mm 2 in min 51 mm Must have 2 in 51 mm minimum clearance to header Ceiling Firestop Offset Return with hanger straps St...

Page 11: ...ee Figure 3 2 Any framing across the top of the replace must be above the level of the top standoffs 23 3 4 in 603 mm 50 12 in 305 mm 36 in 914 mm opening 45 1 2 in 1156 mm framing 39 4 in 102 mm BRIC...

Page 12: ...irestop Tabs False Ceiling False Ceiling Insulation Insulation Figure 3 5 Chase Assembly F Chimney Requirements When planning your replace location the chimney con struction and necessary clearances m...

Page 13: ...y recommended to minimize the effects of negative pressure within the structure We recommend you utilize the shortest duct run to optimize the performance of the outside air kit Cold air ow can be min...

Page 14: ...ed crawl space YES NO NO NO NO Use only duct materials specified by manufacturer preferably with short run or mainly straight duct except small dip for cold air trap which will help prevent flow of co...

Page 15: ...he elevated platform must be protected with a protective metal hearth strip as shown in Figure 4 6 Raised Platform Floor 2 in 51 mm 1 in 25 mm min overlap 2 in 51 mm Top piece must overlap bottom piec...

Page 16: ...f Additional support for tall chimneys Install roof flashing according to minimum requirements Maintain minimum clearances to combustibles as specified Offsets returns may not exceed 30 from vertical...

Page 17: ...ght double offset return 90 ft 27 4 m max height 6 ft 1 8 m max unsupported chimney above roof 71 3 4 in 1822 mm Effective Height bottom of fireplace to top of starter collar Figure 5 2 Chimney Requir...

Page 18: ...restop must be installed The effective height of the replace assembly is measured from the base of the replace to the top of the starter collar See Dimensions in Section 12 Table 5 2 A B 1 1 4 in 32 m...

Page 19: ...ou must provide support for the pipe during con struction and check to be sure inadvertent loading has not dislodged the chimney section from the replace or at any chimney joint Note Inner ue and oute...

Page 20: ...nto position with the screws provided outer only using the predrilled holes To prevent gravity from pulling the chimney sections apart the returns and the chimney stabilizers have hanger straps for se...

Page 21: ...e it will become plugged by snow or other material Must terminate at least 3 ft 914 mm above the roof and at least 2 ft 610 mm above any portion of the roof within 10 ft 3 05 m Must be located away fr...

Page 22: ...rom cap Separation allows sparks heat and embers to escape WARNING C Install the Termination Cap For installations utilizing a TR442 Round Telescoping Termination Cap the uppermost chimney section mus...

Page 23: ...T475 Square Termination Cap For installations utilizing an ST475 Square Termination Cap the last chimney section must not be more than 4 1 2 in 114 mm below the chase top See Figure 6 7 For chase inst...

Page 24: ...38 mm air space Refractory Seal with fireplace mortar or cement 4 in 102 mm Outer Shell of Fireplace Figure 7 1 Gas Line Installation 7 7 Accessories Asphyxiation Risk Damper must be locked open when...

Page 25: ...of 1 16 To substitute materials for the factory available hearth ex tensions see Figure 8 3 and calculate insulation alterna tives as per Table 8 1 and the following formulas Thermal conductivity per...

Page 26: ...12 in 305 mm Min 20 in 508 mm Min Noncombustible Material Hearth Strip 20 in 508 mm Min Hearth Extension Micore Floor Note Maximum height from floor under fireplace to top of finished hearth extension...

Page 27: ...s Please refer to the manual packed with each set of doors for instal lation instructions 12 in 305 mm Min 12 in 305 mm Max Top of Fireplace Opening Mantel 1 1 2 in 38 mm max 6 in 152 mm Min Header St...

Page 28: ...improper installation and operation of the replace Make certain that installation and operation of the replace system is in accordance with these instructions It is extremely important that the re be...

Page 29: ...g homes tted with tightly sealed doors and windows are relatively air tight In this case an outside air source must be made available to feed combustion air from outside the home An outside air contro...

Page 30: ...n of water put it in the replace and try to burn it This sounds ridiculous but that is exactly what you are doing if you burn unseasoned wood Fire Risk Use only factory installed integral grate May ca...

Page 31: ...oils and binders to be burned from the replace and the refractory and paint to cure You may notice an industrial odor the rst few res This is consid ered normal Note When rst lighting your replace it...

Page 32: ...down drafts tight sealing construction of the structure or mechan ical exhausting devices which will create a negative air pres sure within the structure where the replace is located A Understanding V...

Page 33: ...bstruction in chimney Downdraft from chimney temperature or from negative house pressure Does the kindling wood not ignite Condition amount arrangement of kindling and fuel Use more drier well spaced...

Page 34: ...stion air Yes Fire too close to front Build re farther back Do not use exhaust fans during startup and or check for need for balanced air make up system Competition with exhaust devices Diagnostic Que...

Page 35: ...rmination Cap Remove screws and lift top cover Figure 11 1 Chimney Termination Cap Cleaning Fire Risk Disposal of ashes Ashes should be placed in metal container with tight tting lid Do not place meta...

Page 36: ...ll joints are properly engaged and the chimney is properly secured A chimney re can permanently damage your chimney sys tem Failure to replace damaged components and make proper repairs creates risk o...

Page 37: ...8 1 2 in 724 mm 43 1 8 in 1095 mm 59 1 4 in 1505 mm 7 5 8 in 194 mm 36 in 914 mm 71 3 4 in 1822 mm effective height Gas Knockout 8 5 8 in 219 mm 9 5 8 in 244 mm 9 1 2 in 241 mm 9 1 4 in 235 mm Outside...

Page 38: ...036 Glass doors Bi fold clear view black DM6036B Glass doors Bi fold clear view polished brass DM6036S Glass doors Bi fold clear view stainless steel DP6036 Perception Glass Doors Tinted black DP6036B...

Page 39: ...uct Outside Air UD4 Uninsulated Duct Outside Air SL406 Chimney Section 6 in long SL412 Chimney Section 12 in long SL418 Chimney Section 18 in long SL436 Chimney Section 36 in long SL448 Chimney Sectio...

Page 40: ...lation Shield 2 in 51 mm 13 in 330 mm JB577 Chimney Joint Band 13 in 330 mm CB576 Chimney Joint Band 15 1 4 in 387 mm 28 in 711 mm 39 7 8 in 1013 mm RF571 Roof Flashing 29 in 737 mm 15 1 4 in 387 mm 2...

Page 41: ...Square Termination Cap 72 in 1829 mm 36 in 914 mm 2 in 51 mm 13 3 8 in 340 mm CT56 Chase Top A B C D Decorative Shroud LDS33 LDS46 15 3 4 in 400 mm 32 3 8 in 822 mm 34 3 8 in 873 mm 14 3 4 in 375 mm 2...

Page 42: ...Heat Glo EXCLAIM 36C Woodburning Fireplace 4013 093 Rev G 08 06 42 This page intentionally left blank...

Page 43: ...sides Minimum Base Dimensions Inches N A 26 5 X 28 with Radiation Shield 28 X 30 34 X 34 with Radiation Shield 28 X 30 with Radiation Shield or 34 X 34 Minimum Height Inches N A 28 1 4 27 1 2 28 1 4...

Page 44: ...Heat Glo EXCLAIM 36C Woodburning Fireplace 4013 093 Rev G 08 06 46 This page intentionally left blank...

Page 45: ...at the current minimum wholesale price but HHT SHALL NOT BE RESPONSIBLE FOR ANY LABOR TRANSPORTATION OR OTHER INDIRECT DAMAGES 4 During the first six 6 months after installation HHT shall at its opti...

Page 46: ...ay be covered by one or more of the following patents United States 4593510 4686807 4766876 4793322 4811534 5000162 5016609 5076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452...

Reviews: