background image

Heat & Glo  •  Cyclone-BN, Cyclone-BC  •  2073-900 Rev. N  •  10/08

5

H.  Requirements for the Commonwealth of 

Massachusetts

For all side wall horizontally vented gas fueled equipment 
installed in every dwelling, building or structure used in 
whole or in part for residential purposes, including those 
owned or operated by the Commonwealth and where the 
side wall exhaust vent termination is less than seven (7) 
feet above fi nished grade in the area of the venting, in-
cluding but not limited to decks and porches, the following 
requirements shall be satisfi ed:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 
gas fueled equipment, the installing plumber or gas fi tter 
shall observe that a hard wired carbon monoxide detector 
with an alarm and battery back-up is installed on the fl oor 
level where the gas equipment is to be installed. In addi-
tion, the installing plumber or gas fi tter shall observe that 
a battery operated or hard wired carbon monoxide detec-
tor with an alarm is installed on each additional level of 
the dwelling, building or structure served by the side wall 
horizontal vented gas fueled equipment. It shall be the 
responsibility of the property owner to secure the services 
of qualifi ed licensed professionals for the installation of 
hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu-
eled equipment is installed in a crawl space or an attic, 
the hard wired carbon monoxide detector with alarm and 
battery back-up may be installed on the next adjacent 
fl oor level.
In the event that the requirements of this subdivision can 
not be met at the time of completion of installation, the 
owner shall have a period of thirty (30) days to comply 
with the above requirements; provided, however, that dur-
ing said thirty (30) day period, a battery operated carbon 
monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accor-
dance with the above provisions shall comply with NFPA 
720 and be ANSI/UL 2034 listed and IAS certifi ed. 

Signage

A metal or plastic identifi cation plate shall be permanent-
ly mounted to the exterior of the building at a minimum 
height of eight (8) feet above grade directly in line with the 
exhaust vent terminal for the horizontally vented gas fu-
eled heating appliance or equipment. The sign shall read, 
in print size no less than one-half (1/2) inch in size, 

“GAS 

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-
STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon-
tally vented gas fueled equipment shall not approve the 
installation unless, upon inspection, the inspector ob-
serves carbon monoxide detectors and signage installed 
in accordance with the provisions of 248 CMR 5.08(2)(a)1 
through 4. 

Exemptions

The following equipment is exempt from 248 CMR 
5.08(2)(a)1 through 4: 

•  The equipment listed in Chapter 10 entitled “Equip-

ment Not Required To Be Vented” in the most current 
edition of NFPA 54 as adopted by the Board; and 

•  Product Approved side wall horizontally vented gas fu-

eled equipment installed in a room or structure sep-
arate from the dwelling, building or structure used in 
whole or in part for residential purposes. 

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall 
horizontally vented gas equipment provides a venting 
system design or venting system components with the 
equipment, the instructions provided by the manufacturer 
for installation of the equipment and the venting system 
shall include:

•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system. 

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 
horizontally vented gas fueled equipment does not pro-
vide the parts for venting the fl ue gases, but identifi es 
“special venting systems”, the following requirements 
shall be satisfi ed by the manufacturer:

•  The referenced “special venting system” instructions 

shall be included with the appliance or equipment in-
stallation instructions; and 

•  The “special venting systems” shall be Product Ap-

proved by the Board, and the instructions for that sys-
tem shall include a parts list and detailed installation 
instructions. 

A copy of all installation instructions for all Product Ap-
proved side wall horizontally vented gas fueled equip-
ment, all venting instructions, all parts lists for venting 
instructions, and/or all venting design instructions shall 
remain with the appliance or equipment at the completion 
of the installation. 

See Gas Connection section for additional Common-
wealth of Massachusetts requirements.

Note: 

The following requirements reference various 

Massachusetts and national codes not contained in this 
document.

Summary of Contents for Cyclone-BC

Page 1: ...ted on the rating plate Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or techni...

Page 2: ...appliance can be found on the rating plate usually located in the control area of the appliance Homeowner Reference Information Heat Glo a of Hearth Home Technologies Inc 20802 Kensington Boulevard L...

Page 3: ...ons 21 B Assemble Slip Sections 22 C Secure the Vent Sections 22 D Disassemble Vent Sections 23 E Install Decorative Ceiling Components 23 F Install Metal Roof Flashing 24 G Assemble and Install Storm...

Page 4: ...crete slate glass or plasters or any combination thereof Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C shall be c...

Page 5: ...heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspe...

Page 6: ...ove the appliance and components from the packaging The vent system components and trim doors are shipped in separate packages Report to your dealer any parts damaged in shipment particularly the cond...

Page 7: ...pliance away from traffic areas A Selecting Appliance Location When selecting a location for your appliance it is important to consider the required clearances to walls see figure 3 1 Figure 3 1 Appli...

Page 8: ...chase as per regional codes for the rest of the home Additionally in regions where cold air infiltration may be an issue the inside surfaces may be sheetrocked and taped for maximum air tightness To...

Page 9: ...e BC 2073 900 Rev N 10 08 9 D Mantel Projections Figure 3 3 Clearances to mantels or other combustibles above appliance 12 IN MIN TO CEILING AND OR MANTEL TOP OF UNIT Clearances to Mantels or other Co...

Page 10: ...4 2 Minimum height from roof to lowest discharge opening 4 4 Termination Locations Measure horizontal clearances from this surface Measure vertical clearances from this surface Figure 4 3 Multiple Ver...

Page 11: ...d with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10...

Page 12: ...al run A length of straight pipe is allowed between two 45 elbows see Figure 5 1 Figure 5 1 5 5 Vent Information and Diagrams A Vent Table Key The abbreviations listed in this vent table key are used...

Page 13: ...ure to keep insulation or other material away from vent pipe may cause fire WARNING VT Min HT Max 1 5 ft 2 ft 2 5 ft 5 ft 3 5 ft 8 ft 4 5 ft 11 ft VT HT 40 ft Max H1 H2 VT Min HT Max 1 5 ft 2 ft 2 5 f...

Page 14: ...bows H2 V1 V2 H1 V1 H1 V2 H2 VT Min HT Max 1 5 ft 2 ft 2 5 ft 5 ft 3 5 ft 8 ft 4 5 ft 11 ft VT HT 40 ft Max No specific restrictions on this value EXCEPT VT HT cannot exceed 40 ft Max NOTE There MUST...

Page 15: ...rted with the spacing between support intervals not exceeding 4 feet with no more than inch sag between supports A support is required at each change in venting direction and in any location where it...

Page 16: ...T cannot exceed 40 ft Max Two Elbows HT V1 V2 NOTE There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 5 7 NOTE There MUST be a...

Page 17: ...s 1 in 25 mm clearance bottom and sides Heat Shields Wall Shield Firestop WALL 3 in 76 mm top clearance 1 in 25 mm clearance around vertical sections Figure 6 1 Horizontal venting clearances to combus...

Page 18: ...s used in ceiling floor joist The ceiling firestop may be installed above or below the ceiling joists when installed with a attic insulation shield It must be under joists between floors that are not...

Page 19: ...and to maintain air space clearance Figure 6 5 Attic Insulation Shield Vaulted Ceiling Installation The attic insulation shield has been laser etched with cut lines and ceiling pitches to make field...

Page 20: ...are square with the back prior to nailing the appliance completely into place Bend up nailing tabs on top and bottom Keep nailing tabs flush with the framing Secure the appliance to the framing by usi...

Page 21: ...omponent Commercial Multi family Multi level exceeding two sto ries or High Rise Applications For Installation into a commercial multi family multi level exceeding two stories or high rise application...

Page 22: ...sealed sealing the inner flue is not required All unit collar pipe slip section elbow and cap outer flues shall be sealed Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe sectio...

Page 23: ...rews A decorative cathedral ceiling support box can be installed on a cathedral ceiling through which the vent passes Use a plumb bob to mark the center line of the venting system on the ceiling and d...

Page 24: ...PENING CAULK NOTICE Failure to properly caulk the roof flashing could cause water entry Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing...

Page 25: ...e pipe or flue with water and slide the flashing down It may be necessary to trim the top shingles around the base of the rubber boot to ensure a good fit Draw around flashing remove Apply silicone se...

Page 26: ...ARNING Risk of Fire To prevent overheating and fire heat shields must extend through the entire wall thick ness DO NOT remove the heat shields attached to the wall shield firestop and the horizontal t...

Page 27: ...of the cap base Flash and seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI...

Page 28: ...gas appliances are operating Install regulator upstream of valve if line pressure is greater than 1 2 psig 9 9 Gas Information Note Gas line may be run from either side of the appliance provided the h...

Page 29: ...k with local authorities Ensure that gas line does not come in contact with outer wrap of appliance Follow local codes Incoming gas line should be piped into the valve compartment and connected to the...

Page 30: ...ector 1 are designed for use with 10 12 AWG wire If another gauge wire is being used these connectors should be replaced with the appropriate gauge insulated connectors to ensure a proper connection S...

Page 31: ...s can cause improper and dangerous operation Verify proper operation after servicing Shock hazard Replace damaged wire with type 105 C rated wire Wire must have high temperature insulation WARNING Fig...

Page 32: ...d wall and appliance top and sides using only a 300 F minimum sealant Figure 11 1 Clearances to mantels or other combustibles above appliance Fire Risk Do NOT obstruct air inlet or outlet grilles Do N...

Page 33: ...in a safety hazard Only Hearth Home Technologies approved accessories may be used safely WARNING E Glass Assembly Installation D Marbles and Polished Rock Placement Placing the Marbles or Rock With th...

Page 34: ...le raising the platform as shown Figure 12 6 Continue until all four screws have been bottomed out and the glass cylinder is in place Reverse these steps to remove the assembly CYLINDER STOP Figure 12...

Page 35: ...ided with this appliance For assistance or additional information consult a qualified installer service agency or the gas supplier Do NOT use this appliance if any part has been under water Immediatel...

Page 36: ...as is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT...

Page 37: ...ctors Smoke and odors may be irritating to sensitive individuals CAUTION Prevent accidental appliance operation when not attended Unplug or remove batteries from remote control if absent or if applian...

Page 38: ...may cause a permanent white film on glass CAUTION When cleaning glass assembly Avoid striking scratching or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white...

Page 39: ...gure 14 3 Lift the platform The HSI Hot Surface Ignitor and the sensor wire can be unplugged Set platform aside Figure 14 6 When screwing the panel in place start with the center screw and with your f...

Page 40: ...hould be avoided 2 Remove any foreign objects 3 Verify unobstructed air circulation Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burn...

Page 41: ...appliance dimensions Use for reference only For framing dimensions and clearances refer to Section 3 Figure 15 1 Appliance Dimensions Location Inches Millimeter Location Inches Millimeter Location In...

Page 42: ...Effective Height Length Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 6 51 152 SLP12A 2 12 51 305 SLP FLEX 2 24 610 SLP FLEX...

Page 43: ...CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLP WT BK Wall Thimble Black B Vent Components Diagrams continued Figure 15 3 SLP Series Vent Components SLP TRAP2 Horizon...

Page 44: ...e ordered from an authorized dealer Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER 1 Cover Reflector 2073 146 2 Plate Reflector 2073 112 3 Tube Assembly 2061 015 4 Ignitor Pre Aug 2007 SRV2061...

Page 45: ...rdered from an authorized dealer Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER 1 Burner Tube 2073 025 Y 2 Transformer 060 599 Y 3 Control Module Pre Feb 2005 2061 138 Y Post Feb 2005 SRV2061...

Page 46: ...able under this warranty is limited to the purchase price of the product In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product Adjustments regula...

Page 47: ...zed and approved by HHT in writing This warranty does not apply to non HHT venting components hearth components or other accessories used in conjunction with the installation of this product This warr...

Page 48: ..._______________________________________________________ ________________________________________________________________________________ Printed in U S A Copyright 2008 This product may be covered by...

Reviews: