Getting Started

Introducing the Heat-N-Glo Gas Appliances

Heat-N-Glo direct vent gas appliances are designed to
operate with all combustion air siphoned from outside of
the building and all exhaust gases expelled to the outside.

The information contained in this 

Installers Guide

, unless

noted otherwise, applies to all models and gas control
systems. Gas appliance diagrams, including the dimensions,
are shown in this section.

Pre-install Preparation

This gas insert fireplace and its components are tested
and safe when installed in accordance with this 

Installers

Guide

. Report to your dealer any parts damaged in shipment,

particularly the condition of the glass. 

Do not install any

unit with damaged, incomplete, or substitute parts.

The vent system components and trim surrounds are shipped
in separate packages. The gas logs are packaged
separately and must be field installed.

Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the
installation to ensure maximum safety and benefit.
Failure to follow these instructions will void the own-
er’s warranty and may present a fire hazard.

The Heat-N-Glo Warranty will be voided by, and Heat-N-Glo
disclaims any responsibility for, the following actions:
• Installation of damaged fireplace or vent system component.
• Modification of the fireplace or direct vent system.
• Installation other than as instructed by Heat-N-Glo.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not manu-

factured and approved by Heat-N-Glo, not withstanding
any independent testing laboratory or other party approval
of such component part or accessory.

ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE
HAZARD.

VENTING AND INSTALLATION

1. Heat-N-Glo gas inserts are designed for recessed instal-

lations into solid fuel masonry or factory built non-com-
bustible fireplaces that have been installed in accordance
with the National, Provincial, State and local building codes.

2. Minimum fireplace opening requirements are shown in

Figures 1 and 2 of this installation manual. The firebrick
(refractory) can be removed from a factory built fireplace
in order to gain minimum gas insert opening requirements.

WARNING:  Under no circumstances is cutting
of sheet metal surfaces allowed for installation.

If the factory built fireplace has no gas ac-
cess holes provided, an access hole of 1” di-

ameter (25mm) or less may be drilled through the
lower sides or bottom of the combustion chamber
in a proper workmanship like manner.

3. To assure top performance, safety and efficiency, inserts

must be installed with an approved flue liner as per CAN/
CGA B-149 or National Fuel Code ANSI Z223 and these
instructions.

WARNING: A HEARTH OR HEARTH EXTEN-
SION (IF PRESENT) MUST COMPLY WITH EI-

THER OF THE FOLLOWING: 1) THE SOLID-FUEL
BURNING FIREPLACE MANUFACTURER’S SPECI-
FICATION, OR 2) LOCAL BUILDING CODES RE-
QUIRED BY AUTHORITY HAVING JURISDICTION.

WARNING: THE SOLID FUEL FIREPLACE HAS
BEEN CONVERTED FOR USE WITH GAS
ONLY AND CANNOT BE USED FOR BURNING

WOOD OR SOLID FUELS UNLESS ALL ORIGINAL
PARTS HAVE BEEN REPLACED AND THE FIRE-
PLACE HAS BEEN REAPPROVED BY THE AUTHOR-
ITY HAVING JURISDICTION.

4. The solid fuel fireplace’s flue damper must be fully locked

in the open position or removed for installation.

5. The chimney must be cleaned and in good working order

and constructed of noncombustible materials.

6. Make sure that all chimney cleanouts fit properly so air

cannot leak into the chimney.

7. Install the insert without the trim surround and make all

gas, venting, and electrical connections.

WARNING: Modification of any sheetmetal or
fiber surfaces is strictly PROHIBITED in the
installation of this appliance.

Only trim kit(s) supplied by the manufacturer shall
be used in the installation of this appliance.

8. Install decorative trim surround. The surround is tested

AND approved with this gas insert AND may cover exist-
ing air circulation vents or grills on the solid fuel fireplace
into which it is installed. Should the surround not cover
all ventilation grill surfaces, the grill should be left open.

NOTE: DECORATIVE TRIM SURROUND HAS BEEN
TESTED AND APPROVED TO COVER EXISTING AIR
CIRCULATION VENTS OR GRILLS.

WARNING: Only the surround, as supplied,
may be used to cover integral grills on the

solid fuel burning fireplace. No other components
such as  shrouds, sheet metal plates, etc. may be
used to seal off vents. Remote grills or openings
outside of the surround MUST NOT be covered or
sealed.

Summary of Contents for CFX-Grand-B

Page 1: ...se contact your Heat N Glo dealer with any questions or concerns For the number of your nearest Heat N Glo dealer please call 1 888 427 3973 Printed in U S A Copyright 2002 Heat N Glo a division of He...

Page 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Page 3: ...1 Installing the Vent System 14 Step 2 Positioning Leveling and Securing the Insert 18 Step 3 The Gas Control Systems 18 Step 4 The Gas Supply Line 18 Step 5 Gas Pressure Requirements 19 Step 6 Wiring...

Page 4: ...t on following page La liste des num ros de pi ce se trouve la page suivante 9 10 11 12 4 Log Set Assembly 5 6 7 8 13 19 20 17 16 21 22 18 15 u 14 NG LP Exploded Parts Diagram GN PL Vue clat e des pi...

Page 5: ...sembly NG Module de veilleuse GN 485 510A 18 Pilot Assembly LP Module de veilleuse PL 485 511A 19 Glass Tab Right tiquette de Verre Droit 783 133 20 Glass Tab Left tiquette de Verre Gauche 783 134 21...

Page 6: ...ir l Assembl e de Soupape de Balle 302 302A 17 Valve NG Valve GN 060 522 17 Valve LP Valve PL 060 523 18 Pilot Assembly NG Module de veilleuse GN 485 510A 18 Pilot Assembly LP Module de veilleuse PL 4...

Page 7: ...uve la page suivante 4 Log Set Assembly 2 1 3 5 6 7 8 9 10 11 12 FB IN SHOWN 20 19 21 22 16 17 18 14 15 NG LP Exploded Parts Diagram GN PL Vue clat e des pi ces Service Parts FB IN CFX IN B u CFX IN B...

Page 8: ...lve PL 060 523 18 Pilot Assembly NG Module de veilleuse GN 485 510A 18 Pilot Assembly LP Module de veilleuse PL 485 511A 19 Glass Tab Right tiquette de Verre Droit 783 133 20 Glass Tab Left tiquette d...

Page 9: ...Fl chir l Assembl e de Soupape de Balle 302 320A 17 Valve NG Valve GN 060 522 17 Valve LP Valve PL 060 523 18 Pilot Assembly NG Module de veilleuse GN 485 510A 18 Pilot Assembly LP Module de veilleuse...

Page 10: ...es or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1 Canadian Electric Code in Canada These models may be installed in a bedroom...

Page 11: ...built fireplace in order to gain minimum gas insert opening requirements WARNING Under no circumstances is cutting of sheet metal surfaces allowed for installation If the factory built fireplace has...

Page 12: ...Height 25 3 4 654 22 1 2 571 5 NOTE If exhaust collar on insert and fireplace damper do not line up add 4 inches 102mm to minimum fireplace height for bends in vent pipe Figure 1 Diagram of insert GA...

Page 13: ...1 D 30 9 16 776 26 1 16 661 E 23 7 8 606 20 5 8 524 F 18 7 16 468 15 3 16 385 G 25 3 8 644 22 1 8 562 H 24 1 2 622 21 1 4 540 Dimensions in brackets are millimeters Figure 2 Diagram and dimension of a...

Page 14: ...ars of the unit to the end Vent System Approvals of the last section of vent pipe See dimension V in Figure 4 A vertical vent termination system installed on this model will include one 1 length of 3...

Page 15: ...CODES SPECIFY MINIMUM CHIMNEY AND OR VENT HEIGHT ABOVE THE ROOF TOP THESE MINIMUM HEIGHTS ARE NECESSARY IN THE INTEREST OF SAFETY SEE THE FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMINATION...

Page 16: ...LLAR ON COLLAR SLIDE PLATE THE INLET AIR PIPE MUST ONLY BE CONNECTED TO THE INLET AIR COLLAR OF THE UNIT AND EITHER ATTACHED TO THE INLETAIRCOLLAROFTHETERMINATIONCAP OR TERMINATED IN THE CHIMNEY TERMI...

Page 17: ...gasket to insure positive exhaust seal TERMINATION CAP ADAPTOR STAINLESS STEEL ADAPTER FOR EXHAUST MUST BE INSTALLED EXHAUST VENT PIPE SUPPLIED WITH TERMINATION KIT INLET AIR VENT COLLAR LINK DV30 SH...

Page 18: ...pped air NOTE Consult local building codes to properly size the gas supply line leading to the 1 2 inch 13 mm hook up at the unit This gas fireplace is designed to accept a 1 2 inch 13 mm gas supply l...

Page 19: ...led by a li censed electrician CAUTION DISCONNECT REMOTE CONTROLS IF AB SENT FOR EXTENDED TIME PERIODS THIS WILL PRE VENT ACCIDENTAL APPLIANCE OPERATION For Standing Pilot Ignition Wiring Appliance Re...

Page 20: ...Detach flexible liner from back of unit Remove the four screws on the coverplate see Figure 11 Bend up the tabs on the base pan see Figure 10 Place the blower in between the bend up tabs Install and...

Page 21: ...terials for use during fire place servicing The embers provided are sufficient for 2 to 4 applications Place MYSTIC EMBERS over burner surface and around base of the burner do not cover any burner por...

Page 22: ...and let it cool completely Remove and clean the glass Replace the glass and run the fireplace for an additional 8 hours This will help to cure the chemicals used in the paint and logs Step 10 Lighting...

Page 23: ...ompartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your...

Reviews: