background image

Heat & Glo •  BE-41C / LP,   BE-41IPIC / LP  •  2105-900  Rev. P  •  6/09

45

SCREWS

CAULK

STORM 
COLLAR

(1 of 3)

Figure 10.18   

Figure 10.18   

TERMINATION CAP

I.  Install Vertical Termination Cap

•  Attach the vertical termination cap by sliding the inner 

collar of the cap into the inner 

fl

 ue of the pipe section  

while placing the outer collar of the cap over the outer 

fl

 ue of the pipe section.

•  Secure the cap by driving three self-tapping screws 

(supplied) through the pilot holes in the outer collar of the 
cap into the outer 

fl

 ue of the pipe (see Figure 10.18).

J.  Install Decorative Wall Components (SLP 

only)

A decorative wall thimble can be installed on wall through 
which the vent passes. The decorative wall thimble is used 
to cover the wall shield 

fi

 restop. 

•  Slide the decorative wall thimble over the last section of 

horizontal pipe before connecting the termination cap to 
the pipe. 

• 

Once the pipe section and the termination cap have been 
connected, slide the wall thimble up to the interior wall 
surface and attach with screws provided. See Figure 
10.19.

Important Notice:

  Heat shields may not be 

fi

 eld constructed.

K.  Heat Shield Requirements for  Horizontal 

Termination

WARNING! Risk of Fire! To prevent overheating and fi re, 
heat shields must extend through the entire wall thick-
ness.

•  DO NOT remove the heat shields attached to the 

wall shield fi restop and the horizontal termination cap 
(shown in Figure 10.20).

• Heat shields must overlap 1-1/2 in. (38 mm) mini-

mum.

There are two sections of the heat shield. One section 
is factory-attached to the wall shield 

fi

 restop.  The  other 

section is factory-attached to the cap. See Figure 10.20.
If the wall thickness does not allow the required 1-1/2 in. 
(38 mm) heat shield overlap when installed, an extended 
heat shield must be used.
•  If the wall thickness is less than 4 in./102 mm (DVP) 

or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap 
and wall shield 

fi

 restop must be trimmed. A minimum 

1-1/2 in. (38 mm) overlap MUST be maintained.

•  Use an extended heat shield if the 

fi

 nished wall thickness 

is greater than 7-1/4 in. (184 mm).

•  The extended heat shield may need to be cut to length 

maintaining suf

fi

 cient length for a 1-1/2 in. (38 mm) 

overlap between heat shields.

•  Attach the extended heat shield to either of the existing 

heat shields using the screws supplied with the extended 
heat shield.  Refer to vent components diagrams in the 
back of this manual.

•  Rest the small leg on the extended heat shield on top 

of the pipe section to properly space it from the pipe 
section.

Figure 10.19  Wall Thimble

Summary of Contents for BE-41C

Page 1: ...rformed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or technicians supervised by an NFI certified professional Leave this manual with party responsible for use and operation DO NOT DISCARD WARNING Important operating and maintenance instructions included Read understand and follow these instructions for safe installation and operation In ...

Page 2: ...NSI Z223 1 Z223 1 in in the the USA USA or or CAN CGA CAN CGA B149 B149 installation installation codes codes Installer Installer l appareil l appareil selon selon les les codes codes ou ou reglements reglements locaux locaux ou ou en en l absence l absence de de tels tels reglements reglements selon selon les les codes codes d installation d installation CAN CGA B149 CAN CGA B149 Type Type of of ...

Page 3: ...pplies Needed 18 D Inspect Appliance and Components 18 5 Framing and Clearances A Selecting Appliance Location 19 B Constructing the Appliance Chase 20 C Clearances 20 D Mantel and Wall Projections 21 6 Termination Locations A Vent Termination Minimum Clearances 22 7 Vent Information and Diagrams A Approved Pipe 24 B Vent Table Key 24 C Use of Elbows 24 D Measuring Standards 24 E Vent Diagrams 25 ...

Page 4: ... the Shipping Materials 53 C Clean the Appliance 53 D Accessories 53 E Ember Placement 53 F Install the Log Assembly 54 G Fixed Glass Assembly 56 H Install Trim and or Surround 56 I Air Shutter Setting 56 15 Troubleshooting A Standing Pilot Ignition System 57 B IntelliFire Ignition System 59 16 Reference Materials A Appliance Dimension Diagram 61 B Vent Components Diagrams 62 C Service Parts 69 D ...

Page 5: ...Heat Glo BE 41C LP BE 41IPIC LP 2105 900 Rev P 6 09 5 B Limited Lifetime Warranty Î ...

Page 6: ...Heat Glo BE 41C LP BE 41IPIC LP 2105 900 Rev P 6 09 6 B Limited Lifetime Warranty continued Î ...

Page 7: ...d pa per plant fibers plastics or other material that can ignite and burn whether flame proofed or not or plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric C...

Page 8: ...led heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage installed in ac...

Page 9: ...r surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other flammable materials Keep clothing furniture draperies and other flamma...

Page 10: ...all Controls and Wall Switches Follow the instructions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protection lockout feature Keep remote controls out of reach of children See your dealer if you have questions CLEAR SPACE 3 FT IN FRONT OF FIREPLACE H Before Lighting Fireplace Before operating this fireplace for ...

Page 11: ...gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT 110 VAC TO THE CONTROL VALVE Improper installation adjustment al teration service or maintenance can cause injury or property damage Re fer to the owner s information manual provided with this applia...

Page 12: ...e please refer to www fireplaces com A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these in structions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any ele...

Page 13: ... is al lowed to burn for 20 to 40 minutes Odor from appliance When first operated this appliance may release an odor for the first several hours This is caused by the curing of the paint and the burning off of any oils remaining from manufacturing Odor may also be released from finishing materials and adhesives used around the appliance Film on the glass This is a normal result of the curing proce...

Page 14: ... required due to lint from carpeting or other factors Control compartment burner and circulating air passageway of the fireplace must be kept clean CAUTION Risk of Burns The fireplace should be turned off and cooled before servicing When properly maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surrounds...

Page 15: ...rebox Top Frequency Annually By Qualified Service Technician Tools needed Protective gloves vacuum cleaner dust cloths Vacuum and wipe out dust cobwebs debris or pet hair Use caution when cleaning these areas Screw tips that have penetrated the sheet metal are sharp and should be avoided Remove all foreign objects Verify unobstructed air circulation Burner Ignition and Operation Frequency Annually...

Page 16: ...Heat Glo BE 41C LP BE 41IPIC LP 2105 900 Rev P 6 09 16 Either cobrahead or SIT Figure 3 1 IPI Pilot Flame Patterns Figure 3 2 Standing Pilot Flame Patterns ...

Page 17: ... RAFTERS SECTION 8 C FRAMING HEADED OFF IN CEILING JOISTS SECTION 8 C GAS LINE SECTION 11 MANTEL AND MANTEL LEG SECTION 5 D SURROUND HEARTH EXTENSION VENT PIPE SECTIONS 7 and 8 OPTIONAL WALL SWITCH STORM COLLAR SECTION 10 H NON COMBUSTIBLE ROOF FLASHING MAINTAINS MINIMUM CLEARANCE AROUND PIPE SECTION 10 G FRAMING HEADER SECTION 5 B ATTIC INSULATION SHIELD NOT SHOWN MUST BE USED HERE TO KEEP INSULA...

Page 18: ...Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry C Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers High temperature caulking material Hammer Phillips screwdriver Gloves Framing square Voltmete...

Page 19: ... locat ed out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 5 1 Appliance Locations 1 2 IN REAR VENT HORIZONTAL TERMINATION TWO ELBOWS REAR VENT NO ELBOWS REAR VENT ONE ELBOW ALCOVE INSTALLATION ...

Page 20: ...or wood surfaces extending full width and depth DO NOT install directly on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to appliance and vent pipe Insulation and other materials must be secured to prevent accidental contact The chase must be properly blocked to prevent blown insulation or other combustibles from enter...

Page 21: ... 5 10 11 12 2 1 2 13 14 15 16 17 18 19 32 TO CEILING 9 10 11 12 8 7 6 5 4 3 25 18 A B INTERIOR WALL TOP VIEW MANTEL LEG OR WALL PROJECTIONS FIREPLACE OPENING Note All measurements in inches If A minimum is ____ then B maximum is_____ A Inches 2 7 16 3 7 16 4 7 16 5 7 16 6 7 16 7 7 16 Millimeters 62 87 113 138 164 189 B Inches 1 2 3 4 5 Millimeters 25 51 76 102 127 Note Measurement is taken from to...

Page 22: ...FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 6 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire WARNING Gas Wood or Fuel Oil Termination Cap B Gas Termination Cap A If using...

Page 23: ...the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap 3 All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap See Note 1 See Note 2 Note 3 Local codes or...

Page 24: ...e is allowed between two 45º elbows see Figure 7 1 Figure 7 1 7 7 Vent Information and Diagrams B Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams D Measuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards Pipe measurements are shown using the effective length of pipe see Figure 7 2 Hori...

Page 25: ...lation or other material away from vent pipe may cause fire Note The 6000 series fireplaces can adapt to SLP series vent pipe if desired When venting off the top of the unit use a DVP 2SL adapter and a minimum 48 inch vertical section of SLP series vent pipe A DVP SLP24 adapter may also be used with a 24 inch vertical section of SLP series vent pipe After the 48 inch vertical section the venting t...

Page 26: ... V2 V1 V1 Min H1 Max V2 Min H2 Max Elbow only 2 ft 610 mm 0 in 0 mm 1 ft 305 mm 6 in 152 mm 3 ft 914 mm 6 in 152 mm 2 ft 610 mm 1 ft 305 mm 6 ft 1 8 m 1 ft 305 mm 6 ft 1 8 m 2 ft 610 mm 11 ft 3 4 m 2 ft 610 mm 10 ft 3 1 m 3 ft 914 mm 16 ft 4 9 m 3 ft 914 mm 14 ft 4 3 m H1 H2 20 ft 6 1 m Maximum V1 V2 H1 H2 40 ft 12 2 m Maximum ...

Page 27: ...e ap pliance the flue restrictor should be used V1 V1 40 ft Max 12 4 m V1 3 ft Min 914 mm Flue Restrictor Instructions 1 Remove exhaust shield using a 1 4 inch nut driver by removing the four screws securing it in place see Figure 7 7 Figure 7 8 Flue Restrictor 2 Break the flue restrictor into two pieces Do this by bending the part back and forth until it breaks see Figure 7 8 Figure 7 7 BREAK HER...

Page 28: ... NG LP NG LP 4 ft 1 1 No Restrictor No Restrictor No Restrictor 8 ft 2 2 1 2 1 1 No Restrictor 15 ft 3 3 3 2 2 2 1 2 20 ft 3 4 3 3 3 3 2 3 25 ft 3 4 3 3 3 3 2 3 30 ft 4 4 3 4 3 4 3 3 35 ft 4 4 3 4 3 4 3 3 40 ft 5 4 4 4 4 4 3 4 Note If the DVP 2SL or DVP SLP24 adapter is used with SLP pipe you MUST subtract one number from the table above Example Top vent 40 ft vertical with DVP pipe 5 4 Top vent 4...

Page 29: ...ORIZONTALLY H1 H2 V1 V2 V1 H1 H2 V2 V1 V2 Minimum H1 H2 Maximum Elbow only 1 ft 305 mm 1 ft 305 mm 6 in 152 mm 2 ft 610 mm 2 ft 610 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 4 ft 1 2 m 3 ft 914 mm 9 ft 2 7 m 9 ft 2 7 m 4 ft 1 2 m 18 ft 5 5 m 18 ft 5 5 m H1 H2 20 ft 6 1 m Maximum V1 V2 H1 H2 40 ft 12 2 m Maximum ...

Page 30: ... BE 41IPIC LP 2105 900 Rev P 6 09 30 Rear Vent Horizontal Termination Figure 7 13 Figure 7 14 No Elbow One 45º Elbow H1 H1 H1 16 in 406 mm Maximum Do not use a 45º elbow in corner installations Use two 90º elbows instead ...

Page 31: ...1 2 m 7 ft 2 1 m 3 ft 914 mm 3 ft 914 mm 9 ft 2 7 m 12 ft 3 7 m 3 ft 914 mm 4 ft 1 2 m 18 ft 5 5 m 20 ft 6 1 m V1 H1 H2 40 ft 12 2 m Maximum H1 3 ft 914 mm Maximum H1 H2 20 ft 6 1 m Maximum H1 Maximum V1 Minimum H2 H3 H1 H2 H3 Max 1 ft 305 mm Back to Back 90º Elbows 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 6 in 152 mm 1 5 ft 457 mm 3 5 ft 1 1 m 3 ft 914 mm 1 ft 305 mm 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm...

Page 32: ... 6 in 152 mm 2 ft 610 mm 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm 7 ft 2 1 m 4 ft 1 2 m 8 ft 2 4 m 5 ft 1 5 m 8 ft 2 4 m V1 H1 40 ft 12 2 m Maximum H1 8 ft 2 4 m Maximum H1 H2 Maximum V1 Minimum Back to Back 90º Elbows 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 4 ft 1 2 m 9 ft 2 7 m 6 ft 1 8 m 12 ft 3 7 m 8 ft 2 4 m 15 ft 4 6 m V1 H1 40 ft 12 2 m Maximum H1 H2 8 ft 2 4 m Maximum ...

Page 33: ...1 m 8 ft 2 4 m V1 H1 H2 H3 40 ft 12 2 m Maximum No specific restrictions on this value EXCEPT V1 H1 H2 H3 cannot exceed 40 ft 12 2 m Maximum H1 H2 H3 8 ft 2 4 m Maximum H1 Maximum V1 Minimum H2 H1 H2 Maximum 2 ft 610 mm 6 in 152 mm 2 ft 610 mm 4 ft 1 2 m 3 ft 914 mm 1 ft 305 mm 4 ft 1 2 m 7 ft 2 1 m 5 ft 1 5 m 2 ft 610 mm 6 ft 1 8 m 11 ft 3 4 m 7 ft 2 1 m 3 ft 914 mm 8 ft 2 4 m 15 ft 4 6 m 8 ft 2 ...

Page 34: ...76 mm top clearance 1 in 25 mm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance bottom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance around vertical sections A B C D Inches 42 3 4 27 7 8 41 3 4 26 7 8 B Wall Penetration Framing Combustible Wall Penetration Whenever a combus...

Page 35: ...firestop may be installed above or below the ceiling joists when installed with a attic insulation shield It must be under joists between floors that are not insulated Refer to Figure 8 4 Secure with three fasteners on each side WARNING Risk of Fire DO NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating Figure 8 3 Installing Ceiling Firestop Figur...

Page 36: ...ust be used to prevent blown insulation from getting between the shield and vent pipe and to maintain air space clearance Figure 8 5 Attic Insulation Shield Vaulted Ceiling Installation Remove one shield from box NOTICE Cut previously installed batt insulation to make room for the attic insulation shield Cut the attic insulation shield if application is for vaulted ceiling to fit your ceiling pitc...

Page 37: ...ime A Top Vent 9 9 Appliance Preparation Figure 9 1 Cut the seal cap strap across the rectangles next to the disk Figure 9 2 Remove the white gasket material covering the seal cap Figure 9 3 Remove the seal cap Figure 9 4 Remove the insulation basket and white insula tion from the center vent pipe Figure 9 5 Remove the insulation from the outer vent pipe For rear venting there is no insulation in ...

Page 38: ...he gasket to the outer wrap Secure the first section of venting to the fireplace by screw ing through the two straps left over from cutting the seal cap strap in step 2 Figure 9 7 Fold the tabs toward the center of the seal cap 90º and remove the insulation gasket Figure 9 8 Cut the metal retaining band and fold the sides out Figure 9 9 Fold the center parts of the retaining band out and use to re...

Page 39: ... the framing around the appliance standoffs Failure to maintain air space clearance may cause overheating and fire The diagram shows how to properly position and secure the appliance see Figure 9 13 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing Level the applianc...

Page 40: ...predrilling holes DO NOT penetrate inner pipe For 90º and 45º elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe Commercial Multi family Multi level exceeding two sto rie...

Page 41: ...ollar pipe slip section elbow and cap outer flues shall be sealed in this manner unless otherwise stated Figure 10 5 Adding Venting Components WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when remov ing termination cap from slip pipe If slip section seals are broken during removal of the termination cap vent may leak Note Align seams to engage pipe then r...

Page 42: ...P pipe must be supported every 8 ft 2 44 m Horizontal sections must be supported every 5 feet 1 52 m Vent supports or plumbers strap spaced 120º apart may be used to support vent sections See Figures 10 8 and 10 9 Wall shield firestops may be used to provide horizontal support vent sections SLP ceiling firestops have tabs that may be used to provide vertical support WARNING Risk of Fire Explosion ...

Page 43: ...rt box on the outside roof Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box Cut the hole 1 8 in 3 mm larger than the support box outline Lower the support box through the hole in the roof until its bottom is at least 2 in 51 mm below the ceiling Figure 10 12 Level the support box both vertically and horizontally and temporarily tack it in place th...

Page 44: ...lure to properly caulk the roof flashing could cause water entry Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing where it contacts the roof surface See Figure 10 15 H Assemble and Install Storm Collar CAUTION Risk of Cuts Abrasions or Flying Debris Wear protective gloves and safety glasses during instal lation Sheet metal edges are s...

Page 45: ...NG Risk of Fire To prevent overheating and fire heat shields must extend through the entire wall thick ness DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 10 20 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other secti...

Page 46: ... of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For certain exposures which require superior resistance to win...

Page 47: ...e open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure may cause explosion Verify inlet pressures Verify minimum pressures when other household gas appliances are operating Install regulator upstr...

Page 48: ...110 VAC voltage cannot be shared within the same wall box WARNING Risk of Shock or Explosion DO NOT wire 110V to the valve or to the appliance wall switch Incorrect wiring will damage controls Determine if the appliance uses an IntelliFire ignition sys tem or standing pilot ignition system Open the control access panel or remove the decorative front A red or black ignitor button as shown in Figure...

Page 49: ...ated wire Wire must have high temperature insulation THERMOSTAT WIRE ASSEMBLY ON OFF PIGGYBACK WIRE BRN VALVE WHT RED RED STANDING PILOT PLUG IN 3V TRANSFORMER ON OFF WALL SWITCH IGNITION MODULE 3V VALVE NEUTRAL GROUND LOW VOLTAGE SEE NOTE 1 REMOTE CONTROL HOT PLUG IN REMOTE JUMPER WIRE ORG GRN BRN BRN RED BLK INTERMITTENT PILOT IGNITOR ORG WHT IGNITION MODULE 3 VAC TRANSFORMER VALVE 3 VAC THERMOS...

Page 50: ...own W H T W HT B L K BLK GRN wire inside box Copper ground attached to GRN screw with GRN wire 14 2WG Cover Plate outside firebox Romex Connector Figure 12 4 Junction Box Detail NOTICE DO NOT wire 110 VAC to wall switch Red Switch Switch Box Red Black Black Green Green White Power Supply Wires White Red Black Green White Minimum 14 3 AWG with Ground Junction Box Knockout Figure 12 5 Junction Box W...

Page 51: ...7 16 4 7 16 5 7 16 6 7 16 7 7 16 Millimeters 62 87 113 138 164 189 B Inches 1 2 3 4 5 Millimeters 25 51 76 102 127 Note Measurement is taken from top of the opening NOT the top of the fireplace B Facing Material Metal front faces may be covered with non combustible materials only Facing and or finishing materials must not interfere with air flow through louvers operation of louvers or doors or acc...

Page 52: ...Inside fit door Figure 13 7 Operable hinge door DOOR FINISHING MATERIAL FINISHING MATERIAL Outside door width Includes 1 8 in opening each side of door 37 in 37 1 4 in ELBOW HEAT SHIELD Finishing materials over 1 inch thick Finishing material between 1 and 3 inches thick 37 in 33 3 4 in 37 1 4 in 34 in Outside door width Includes 1 8 in opening each side of door Figure 13 5 Overlap Fit Door Figure...

Page 53: ...r Placement WARNING Risk of Explosion Follow ember placement instructions in manual DO NOT place embers directly over burner ports Replace ember material annually Improperly placed embers interfere with proper burner operation Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over ports Care should be taken not to cover the lighting trai...

Page 54: ...ny part of the tie in the fireplace See Figure 2 Figure 1 Figure 3 Figure 2 Log Placem ent Tabs 3 Grasp the log assembly by the ends Do NOT grasp the log assembly by the center Remove the log assembly from the fireplace and set aside 4 Remove the foam pad from the fire place and discard Make sure all pieces of the foam are removed With a screwdriver bend up the log place ment tabs See Figure 3 CAU...

Page 55: ...Figure 4 Log Placement Tabs 9 Carefully position the log set in the fireplace Pull the log set forward until the log set contacts the log placement tabs Center the log set in the firebox side to side as shown in Figure 5 Grate has been removed in Figure 5 photo only for purpose of illustration 8 Install embers See Ember Placement section of the Owner s Manual for details WARNING Risk of Explosion ...

Page 56: ... NG LP Burner 3 8 in Full Open H Install Trim and or Surround Install optional trim kits and or surrounds using the instructions included with the accessory Use non combustible materials to cover the gap between the sheet rock and the appliance when applicable to the model GLASS ASSEMBLY LATCHES BOTH BOTTOM AND TOP I Air Shutter Setting This appliance has an adjustable air shutter which controls t...

Page 57: ...le connection at the gas valve is fully in serted and tight hand tighten plus 1 4 turn Verify proper voltage output from the thermocouple to the valve Place one millivolt meter lead wire on the thermocouple copper lead Place the second lead wire on the solder button on the back of the valve blue wire Start the pilot and hold the valve knob in The mil livolt reading should read 8 16 millivolts If m...

Page 58: ...fuel tank B Improper gas inlet pressure Natural gas should be 5 14 in w c LP should be 10 14 in w c Verify pressure with manometer C Inner vent pipe leaking exhaust gases back into the system Check venting system for damage Replace repair im properly assembled pipe sections D Glass installed improperly Check to ensure glass is installed properly Replace fixed glass panel assembly E Thermopile or t...

Page 59: ...nto module Check voltage of transformer under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good transformer are between 3 2 and 2 8 volts AC B A shorted or loose connection in wiring configuration or wiring har ness Remove and reinstall the wiring harness that plugs into module Verify there is a tight fit Verify pilot assembly wiring to module Re mo...

Page 60: ...rect pilot orifice is installed and gas inlet is set to pressure specifications Clean flame sensing rod with emery cloth to remove any contaminants that may have accumulated on flame sensing rod C Module is not grounded Verify module is securely grounded to metal chassis of ap pliance Verify that wire harness is firmly connected to the module D Damaged pilot assembly or contami nated flame sensing...

Page 61: ...o Section 5 Figure 16 1 Appliance Dimensions A D B C H ELECTRICAL ACCESS G F E GAS LINE ACCESS N O L M I J K TOP VIEW RIGHT SIDE LEFT SIDE FRONT VIEW Q R P Location Inches Millimeters J 11 5 8 295 K 28 1 2 724 L 14 1 4 362 M 8 dia 203 N 2 1 8 54 O 6 7 8 175 P 38 965 Q 1 25 R 39 3 8 1000 Location Inches Millimeters A 41 1041 B 36 1 8 918 C 33 1 2 851 D 34 5 8 879 E 2 3 8 60 F 5 127 G 26 7 8 683 H 6...

Page 62: ...n 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP 10 in 254 mm 24 in 610 mm DVP HVS Vent Support DVP AS Attic Shield DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45º Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 276 mm 13 mm Pipe Effective Length Inches Millimeters DVP4 4 102 DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 91...

Page 63: ...m The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield B Vent Components Diagrams continued Figure 16 3 DVP vent components Term Cap Minimum Effective Length Maximum Effective Length...

Page 64: ...ick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADD Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield B Vent Components Diagrams continued Fi...

Page 65: ...TVHW VerticalTermination Cap Highwind PVK 80 For use with IPI and DSI appliances only 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap B Vent Components Diagrams continued Figure 16 ...

Page 66: ...5 in 381 mm 8 1 8 in 206 mm 10 7 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm Figure 16 6 DVP vent components Fire Risk When using DVP HRC SS and DVP HRC ZC SS termination caps on top vented fireplaces a 6 inch minimum vertical vent section is required before installing first elbow WARNING ...

Page 67: ...LP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 6 51 152 SLP12A 2 12 51 305 8 3 4 in 222 mm 6 1 2 in 165 mm 6 5 8 in 168 mm 6 in 152 mm 6 1 2 in 165 mm 6 5 8 in 168 mm 9 7 8 in 251 mm 6 1 2 in 165 mm 9 1 4 in 235 mm SLP45 45 Elbow SLP 90ST 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter ...

Page 68: ...nation Cap 15 1 8 in 384 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maxim...

Page 69: ..._______________________________________________________ ________________________________________________________________________________ This product may be covered by one or more of the following patents United States 4593510 4686807 4766876 4793322 4811534 5000162 5016609 5076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452708 5542407 5601073 5613487 5647340 5688568 57620...

Reviews: