Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. AN • 2/16
FLUE
RESTRICTOR
TOP
REFRACTORY
Top Vent - Vertical Termination
No Elbow
Figure 7.6
Note:
If installing a vertical vent/
termination off the top of the appli-
ance, the flue restrictor should be
used. See Figure 7.9.
V
1
V
1
= 40 ft. Max. (12.4 m)
V
1
= 3 ft. Min. (914 mm)
Figure 7.7
Flue Restrictor Instructions
1. Remove the top piece of refractory, if already installed.
See Figure 7.7.
2. Orientate and align the two pieces of the flue restrictor
as shown in Figure 7.9.
3. Match the amount of vertical you have in the system
with the chart to find the appropriate position to set the
flue restrictor. See Figure 7.8 and 7.9.
4. Center the two flue restrictor pieces on the vent at the
setting selected in step 3 and secure in place by using
two self-tapping screws. See Figure 7.7.
5. Reinstall the refractory.
Figure 7.8
Vertical
TOP VENT
REAR VENT
NG
LP
NG
LP
4 ft.
1-1
No
Restrictor
No
Restrictor
No
Restrictor
8 ft.
2-2
1-2
1-1
No
Restrictor
15 ft.
3-2
3-2
2-2
1-2
20 ft.
3-2
3-2
3-2
3-2
25 ft.
3-2
3-2
3-2
3-2
30 ft.
3-3
3-3
3-3
3-3
35 ft.
3-4
3-4
3-4
3-3
40 ft.
3-4
3-4
3-4
3-4