Wall Pass-Through
Design your installation so that your connector does not
pass through a combustible wall. If you must pass
through, check with a local building inspector before you
begin. Use only pass through thimbles that have been
tested and listed for connection to solid fuel room heater
appliances.
Masonry Chimney
A masonry chimney should be inspected before
installation by local building inspector to assess the
suitability of venting a wood burning appliance. In Canada,
a masonry chimney must have or use a ULC S635 listed
Class III liner in chimney systems that are not ULC S629
listed. Similarly in the USA a UL1777 listed refractory or
metallic liner must be used. Follow installation
requirement outlines in CSA B365 for Canada and
NFPA211 for the U.S..
Factory Built Chimney
Chimneys manufactured in a factory must be tested and
listed to ULC S629 (Can.) or Type HT chimneys in the
Standard for Chimneys, Factory-Built Residential Type
and Building Heating Appliance UL 103 HT (USA).
Follow installation requirements outlined in CSA B365 for
Canada and NFPA 211 for the U.S.