background image

5

       WARNING:   

Rework  worksheet, add-

ing    the    space    of    the    adjoining
unconfined  space. The  combined  spaces
must  have  enough  fresh air to supply  all
appliances  in  both  spaces.

VENTILATION  AIR

Ventilation  Air  From  Inside Building
This  fresh  air  would  come  from  an  adjoining
unconfined  space.  When  ventilating   to  an
adjoining    unconfined  space,  you    must
provide  two permanent openings: one  within
12

"

  of  the  ceiling and  one  within  12

"

  of   the

floor  on  the wall  connecting  the  two  spaces
(see options 1 and 2,  Figure  2). You  can  also
remove  door  into  adjoining  room (see option
3, Figure 2). 

Follow  the  National Fuel  Gas

Code  NFPA 54/ANS Z223.1. Section  5.3,  Air
for  Combustion  and Ventilation  for  required
size of  ventilation grills or ducts

If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

 Example:
 Gas  water  heater          40,000        Btu/Hr
 Vent  free  heater    +      18,000        Btu/Hr
 Total                         =     58,000        Btu/Hr

3. Add the Btu/Hr of all fuel burning appliances in the space.
     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                         Btu/Hr
      Gas furnace                                                                  Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas Fireplace logs

                                        Btu/Hr

     Other gas appliances*    +                                          Btu/Hr
    Total                                =                                        Btu/Hr
    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.

4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.

Btu/Hr (maximum the space can support)

Btu/Hr (actual amount of Btu/Hr used)

Example :  51,200 Btu/Hr(maximum the space can support)

                           58,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. See

  Ventilation  Air  From

inside  Building, page 5.
B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  From  Outdoors, page 6 .

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

Summary of Contents for HR15ML-1

Page 1: ...e must be performed by a qualified installer service agency or gas supplier HR15TL 1 HR25TL 1 HR15ML 1 HR25ML 1 Table of Contents ImportantSafetyInformation 2 Product Features 3 ProperVentilation Fres...

Page 2: ...hot when running heater Keep children and adults away from hot surface to avoid burns or clothing ignition Heater will remain hot for a time after shut down Allow surface to cool before touching Caref...

Page 3: ...urce Heater Cabinet Control Knob Grill Burners Ignitor Button Lower Front Panel LOCAL CODES Install and use heater with care Follow all local codes In the absence of local codes use the latest edition...

Page 4: ...lation air by one of the methods described in the National Fuel Gas Code ANS Z223 1 Section 5 3 or applicable local codes Unusually Tight Construction The air that leaks around doors and windows may p...

Page 5: ...l burning appliances in the space Vent free heater Btu Hr Gas water heater Btu Hr Gas furnace Btu Hr Vented gas heater Btu Hr Gas Fireplace logs Btu Hr Other gas appliances Btu Hr Total Btu Hr Do not...

Page 6: ...joint pipe wrench A CSA AGA design certified equip ment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the CSA AGA design certified equip ment shutoff va...

Page 7: ...mounting screws through mounting bracket and into wall studs Attaching to Wall Anchor This method allows you to attach mounting bracket to hollow walls wall areas between studs or to solid walls concr...

Page 8: ...nting bracket onto wall Line up last hole on each end of bracket with wall anchors 6 Insert mounting screws through bracket and into wall anchors 7 Tighten screws until mounting bracket is firmly fast...

Page 9: ...e regulator with wrench when connecting it to gas piping and or fittings CAUTION Use pipe joint sealant that is resistant to liquid petroleum LP gas Figure 14 Gas Connection The installer must supply...

Page 10: ...e to control valve see Figure 16 Apply mixture of liquid soap and water to gas joints Bubbles forming show a leak 5 Correct all leaks at once 6 Light heater see Operating Heater pages 10 and 11 for no...

Page 11: ...unterclockwise Release the downward pressure on the knob while continuing to turn until the knob locks at the desired setting position Do not operate between locked positions Shutting Off Heater 1 Tur...

Page 12: ...ep 5 Turn control knob counterclock wise to the PILOT position Press in control knob for five 5 seconds see Figure 20 Note You may be running this heater for the first time after hooking up to gas sup...

Page 13: ...o remove dust MANUAL LIGHTING PROCEDURE 1 Remove lower front panel see Figure 7 page 7 2 Follow steps 1 through 5 under Lighting Instructions on page 12 3 With control knob pressed in strike match Hol...

Page 14: ...trol knob is not pressed in long enough 3 Equipment shutoff valve is not fully open 4 Thermocouple connection is loose at control valve 5 Pilot flame is not touching thermocouple This allows thermocou...

Page 15: ...o low 1 Residues from manufacturing processes 1 Metal expanding while heating or contracting while cooling 1 When heated vapors from furniture polish wax carpet cleaners etc turn into white powder res...

Page 16: ...ne LP gas company 3 Clean ODS pilot see Cleaning Page 13 1 Locate and correct all leaks see Checking Gas Connections Page 10 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2...

Page 17: ...nal fan kit part HAB01 fits all models noted in this manual The fan has 3 settings ON OFF Auto The thermostatically controlled HAB01improves heater efficiency and includes installation and operating i...

Page 18: ...18 ILLUSTRATED PARTS BREAKDOWN HR15ML Burner Assembly ODS Pilot Assembly...

Page 19: ...04E ML071 02 ML072 01 PART AVAILABLE NOT SHOWN DESCRIPTION Cabinet Assembly Lower Front Panel Assembly Deflector Unit Burner Assembly ODS Pilot Assembly Thermocouple lgnitor Electrode ODS Mounting Br...

Page 20: ...20 ILLUSTRATED PARTS BREAKDOWN HR25ML Burner Assembly ODS Pilot Assembly...

Page 21: ...NOT SHOWN DESCRIPTION Cabinet Assembly Lower Front Panel Assembly Reflector Unit Burner Assembly ODS Pilot Assembly Thermocouple lgnitor Electrode ODS Mounting Bracket Self Tapping Screws Control Val...

Page 22: ...22 ILLUSTRATED PARTS BREAKDOWN HR15TL ODS Pilot Assembly Burner Assembly...

Page 23: ...ML065 01 PARTS AVAILABLE NOT SHOWN DESCRIPTION Cabinet Assembly Lower Front Panel Assembly Reflector Unit Burner Assembly Thermostat Valve Assembly Thermostat Valve Base Self Tapping Screw Mounting Br...

Page 24: ...24 ILLUSTRATED PARTS BREAKDOWN HR25TL ODS Pilot Assembly Burner Assembly...

Page 25: ...SCRIPTION Cabinet Assembly Lower Front Panel Assembly Reflector Unit Burner Assembly Thermostat Valve Assembly Thermostat Valve Base Self Tapping Screw Mounting Bracket Thermostat Outlet Tube Assembly...

Page 26: ...26...

Page 27: ......

Page 28: ......

Reviews: