29

Step 9.  Finishing

Figure 37 shows the minimum vertical and corresponding
maximum horizontal dimensions of fireplace mantels or other
combustible projections above the top front edge of the
fireplace. See Figures 2 and 3 for other fireplace clearances.

Only non-combustible materials may be used to cover the
black fireplace front.

WARNING: WHEN FINISHING THE FIREPLACE,
NEVER OBSTRUCT OR MODIFY THE AIR IN-
LET/OUTLET GRILLES IN ANY MANNER.

!

Figure 37.
Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles above Fireplace

CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS
AND THE FIREPLACE SURROUND (TOP AND SIDES)
ARE SEALED, A 300°

 

F. MINIMUM SEALANT MATE-

RIAL MUST BE USED.  THESE JOINTS ARE NOT RE-
QUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE
MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF
NEEDED) CAN BE APPLIED AS FACING TO THE FIRE-
PLACE SURROUND. SEE THE DIAGRAM BELOW.

Hearth Extensions

A hearth extension may be desirable for aesthetic reasons.
However, ANSI or CAN/CGA testing standards 

do not

 require

hearth extensions for gas fireplace appliances.

Figure 38.   Sealant Material

2”

4"

5”

6”

7”

8”

9”

2"

3"

4"

5"

12"

11"

10"

9"

8"

7"

6"

TOP FRONT EDGE

OF FIREPLACE

3”

11”

12”

10”

31”

CEILING

1”

1”

Installing the Trim

Combustible materials may be brought up to the specified
clearances on the side and top front edges of the fireplace,
but 

MUST NEVER

 overlap onto the front face. The joints

between the finished wall and the fireplace top and sides
can only be sealed with a 300° F. (149° C) minimum sealant.

WARNING: WHEN FINISHING THE FIREPLACE,
NEVER OBSTRUCT OR MODIFY THE AIR INLET/
OUTLET GRILLES IN ANY MANNER.

Install optional marble and brass trim surround kits as
desired. Marble, brass, brick, tile, or other non-combustible
materials can be used to cover up the gap between the
sheet rock and the fireplace.

Do not obstruct or modify the air inlet/outlet grilles. When
overlapping on both sides, leave enough space so that the
bottom grille can be lowered and the trim door removed.

!

Step 10.    Installing Trim, Logs,
                   and Ember Material

HIGH TEMPERATURE 

SIDE SEAL JOINT

(300F /149C MIN.)

TOP & 

00

0”

FINISH WALL MATERIAL MAY BE 

COMBUSTIBLE - TOP AND SIDES

0”

0”

NON-COMBUSTIBLE

BOARD

Summary of Contents for BE-41B

Page 1: ...REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use with the type of gas ind...

Page 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Page 3: ...3 Installing the Vent System 12 A Vent System Approvals 12 B Installing Vent Components 19 C Vent Termination 22 Step 4 Positioning Leveling and Securing the Fireplace 25 Step 5 The Gas Control System...

Page 4: ...e des num ros de pi ce se trouve la page suivante 2 3 1 8 9 10 5 7 6 Log Set Assembly 4 NG LP Exploded Parts Diagram GN PL Vue clat e des pi ces Service Parts BE 41B Beginning Manufacturing Date 5 02...

Page 5: ...0 523 Pilot Assembly NG Module de veilleuse GN 485 510A Pilot Assembly LP Module de veilleuse PL 485 511A Thermocouple Thermocouple 446 511 Thermopile Thermopile 060 512 Intermittent Pilot Ignition Pa...

Page 6: ...ce with local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1 Canadian Electric Code in Canada These models may be insta...

Page 7: ...to follow these instructions will void the owner s warranty and may present a fire hazard The Hearth Home Technologies Warranty will be voided by and Hearth Home Technologies disclaims any responsibil...

Page 8: ...LS RATING PLATE AND LABELS LOWER LOUVER HOOD TOP STANDOFFS TOP LOUVER 41 1043mm 38 965mm 36 1 8 916mm 25 642mm 34 5 8 879mm 8 5 8 219mm VENT COLLARS ELECTRICAL ACCESS 26 7 8 683mm 10 259mm 3 90mm GAS...

Page 9: ...THESE INSTRUCTIONS ARE NOT SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL BUILDING CODES THEREFORE YOUR LOCAL BUILD ING CODES MUST BE CHECKED TO DETERMINE THE REQUIREMENTS FOR THESE STEPS Factory built fir...

Page 10: ...ng material The dia gram below shows framing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING 1 2 CLEARANCE FROM BACK OF FI...

Page 11: ...36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 48D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220mm 35 3 4 908mm...

Page 12: ...dentifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in vent configura ti...

Page 13: ...want to install the vertical baffle 385 128 See flue restrictor installation in structions Figure 6 Flex Vent The flex vent must be supported with the spacing between support intervals not exceeding...

Page 14: ...tem with the chart to find the appropriate position to set the Flue Restrictor 1 2 3 4 5 SETTINGS 1 2 3 4 5 Figure 10 CHART Vertical Top Vent NG Top Vent LP Rear Vent NG Rear Vent LP 4 1 1 No Restrict...

Page 15: ...914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H 40 MAX 12 4MM H 20 MAX 6 2m Figure 13 Venting with One 90 Elbow NOTE If a 90o elbow is first attached to the unit the maximum horizontal run is 3 feet 91...

Page 16: ...Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOWS V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H H1 40 MAX 12 4m H H1 20 MAX 6...

Page 17: ...V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H 1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4 MAX 1 22m 10 MAX 3 1m 3 MIN 914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX...

Page 18: ...1 H H1 40 MAX 12 4m V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m H H1 20 MAX 6 2m NOTE V V1 H H1 40 MAX 12 4m Figure 17 Venting with th...

Page 19: ...erglass gasket supplied in the man ual bag seals between the first 8 5 8 inch 219mm vent component and the outer fireplace wrap Using 2 self tapping screws from the manual bag secure that gasket to th...

Page 20: ...l brackets to the vent pipe and secure the wall bracket to the framing members with nails or screws Figure 22 Installing Support Brackets 4 Install Firestops For Horizontal Runs Firestops are REQUIRED...

Page 21: ...ical runs that pass through ceilings Position a plumb bob directly over the center of the verti cal vent component Mark the ceiling to establish the centerpoint of the vent Drill a hole or drive a nai...

Page 22: ...E WALL VENTING TERMINALS SHALL NOT BE RE CESSED INTO AWALL OR SIDING SEE THE FOL LOWING DIAGRAM FOR VENT TERMINATION CLEARANCES TRAPEZOID CAP TERMINATION 7 1 4 184mm WARNING THETERMINATIONCAPMUSTBEPO...

Page 23: ...RONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT 30 minimum for vinyl clad soffits a vent shall not terminate directly above a sidewalk or paved driveway which is located between tw...

Page 24: ...FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICAL WALLAND 2 FEET BELOW AHORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems...

Page 25: ...Figure 32 Gas Controls Systems Step 5 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Two types of gas control systems are used with these models Standing Pilot Ignition and...

Page 26: ...h non combustible insulation to pre vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When attaching the pipe s...

Page 27: ...witch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING D...

Page 28: ...nstalled junction box before the fire place is permanently installed Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G mi...

Page 29: ...GAtesting standards donot require hearth extensions for gas fireplace appliances Figure 38 Sealant Material 2 4 5 6 7 8 9 2 3 4 5 12 11 10 9 8 7 6 TOP FRONT EDGE OF FIREPLACE 3 11 12 10 31 CEILING 1 1...

Page 30: ...of the tie in the fireplace see Figure 40 WARNING USE WIRE CUT TERS DO NOT ATTEMPT TO CUT THE TIE WITH A KNIFE 3 Grasp the log assembly by the ends Do NOT grasp the log as sembly by the center Remove...

Page 31: ...ut shrink wrap and remove from around the log assembly WARNING REMOVE ALL PACKAGING FROM LOGS 8 Install embers See ember placement instructions for details WARNING USE DIME SIZE PIECES ONLY DO NOT COV...

Page 32: ...er material is shipped with this gas fireplace To place the ember material Pull the four glass latches out of the groove on the glass frame Remove glass door from the unit see Figure 44 Place dime siz...

Page 33: ...e thermopile thermocouple tips should be covered with flame See Figure 32 Figure 46 Burner Flame Patterns MAKE SURE THE FLAMES ARE STEADY NOT LIFTING OR FLOATING Checking Vent System Frequency Before...

Reviews: