20
Table 4. Error Codes
Error Code Failure Mode
Action
Reset
E1
Internal Humidity
or Temperature
Sensor Open or
Shorted
1. Cycle power to clear error code.
2. If error code reoccurs replace User Interface, Catalog No. Y6459.
Cycle Power
E2
High Refrigeration
Pressure
1. Verify that the fan works, the backflow damper swings freely and there is no blocked or
restricted duct.
2. If the fault persists, call Technical Support.
Cycle Power
E3
Y6456
Remote Control
Communication
Loss
1. Check connections between Y6456 and dehumidifier control board. Terminals should be
fully inserted and secured in the control board and Y6456 control terminals.
2. If connections are correct and secure, turn off the dehumidifier and remove the Y6456.
Use a short section of 4-wire cable to reconnect the Y6456 to the control board. Turn
the dehumidifier back on and increase the dryness level setting on the Y6456. If the
dehumidifier turns on, the problem is with the wiring between the dehumidifier and
control.
3. If the dehumidifier does not turn on, call Technical Support at 1-800-453-6669.
Self-Correcting
E4
Insufficient
Capacity
1. Check the frost sensor connection at the power board. Terminal should be fully seated on
the power board pins.
2. Remove the side access panel and verify that the sensor is secured to the suction line.
3. If the sensor is connected and secured to the refrigeration line proceed to the next step.
4. Reset the fault by cycling power to the dehumidifier.
5. Turn the humidity setting down (below room/home humidity level) to make a
dehumidification call.
6. Allow the fan and compressor to run for approximately 10-15 minutes and then enter
diagnostic test mode by simultaneously pressing the UP ARROW and MODE buttons
for 3 seconds. The LCD will display the temperature measured by the internal sensor
while also displaying AIR SAMPLING and ON, the humidity measured by the internal
sensor while also displaying %RH and ON, and the frost sensor temperature while also
displaying ON. Scroll through these values and by using the UP/DOWN arrow buttons.
7. Record values and call Technical Support.
Cycle Power
E5
High Temperature
Thermistor Failure
1. Check the high temperature sensor connection at the power board. Terminal should be
fully seated on the power board pins.
2. Remove the side access panel and verify the sensor is not damaged and connected to
the refrigeration line coming from the compressor.
3. If the sensor is connected and secured to the refrigeration line, contact Technical Support.
Cycle Power
E6
Low Temperature
Thermistor Failure
1. Check the low temperature sensor connection at the power board.
2. Remove the side access panel and verify the sensor is not damaged and connected to
the suction line.
3. If the sensor is connected and secured to the refrigeration line, contact Technical Support.
Cycle Power
E7
Float Switch Open
1. Empty the condensate pan.
2. Check the float switch connection at the control board.
3. If not using a float switch, verify jumper is between float switch terminals on dehumidifier
control board.
4. If the problem persists, replace the float switch.
Self-Correcting
E8
Inlet Air
Temperature Out
of 50°F – 104°F or
dew point below
40°F
1. Verify all duct is properly sealed.
2. If no signs of leak points, contact Technical Support.
Self-Correcting
E9
Outdoor
Temperature
Sensor Open or
Shorted
1. Check the sensor connection at the power board.
2. Remove the wires from the terminals and
measure the resistance. An short circuit will have
a resistance very close to 0 Ohms and an open
circuit will have a very very high resistance. The
table at right can be used to approximate the
resistance based on outdoor temperature.
3. If the sensor is not reading correctly, replace the
sensor, Catalog No. 58N66.
Outdoor
Temperature
Resistance
0°F
84,500 Ohms
20°F
46,000 Ohms
40°F
26,000 Ohms
60°F
15,500 Ohms
80°F
9,500 Ohms
100°F
6,000 Ohms
Self-Correcting