4 Planning and installation – Structural requirements
25
R
EQUIRED
ROOM
SIZES
AND
MINIMUM
CLEARANCES
*does not apply in connection with HDG automatic ignition system
Danger!
When installing the pipes for the heating system, observe the
dimensions of the boiler and ensure the minimum clearances.
Figure 4/2 - Required room sizes and minimum clearances
F
D
E
C
B
A
G
HDG Euro 30/40/45/50
A
at least 750 mm
B
at least 200 (or 800) mm
C
at least 800 (or 200*) mm
D
1610 mm
E
at least 2600 mm
F
at least 1800 mm
G
at least 800 mm
Minimum ceiling height
2000 mm
Recommended room height
2300 mm
Installation dimensions
1380 x 800 x 1610 mm
Table 4/2 - Room sizes and minimum clearances