H B X   W A V - 0 1 1 0   O u t d o o r   W i r e l e s s   S e n s o r

V e r s i o n   1 . 0

Page 6

WIRING AND INSTALLATION
Setting the Dipswitches

The Dipswitches enable you to configure the Wireless Outdoor Sensor to work with different thermistor curves. See FIG 1 to 

select the appropriate thermistor curve.

FIG 1

Mounting and Wiring the Base Unit 

•  Place a flat screwdriver into the top part of  the base unit. Pry the screwdriver up on the back of  the plastic and then pull off  

  the front cover.

•  Supply 24 VAC power to the terminals in the base unit. This connection provides power to the microprocessor.  

 

 

  (see FIG 2A/2B)

Make sure to wire the thermistor section to the control AFTER powering the WAV-0110.

•  Connect 18 AWG or similar wire to the THERM OUT terminals in the base and run the wire from here to the outdoor  

 

  sensor control terminal. See FIG 2A for regular setup, and FIG 2B for Vitodens 200 setup.

Dip 1 ON only: 500 Ohms 

Dip 2 ON only: 5k Ohms

Both ON: 20k Ohms

Both OFF : 10k Ohms*

*Default Setting

ON

ON

ON

ON

ON

ON

ON

ON

Dip 1 ON only: 500 Ohms 

Dip 2 ON only: 5k Ohms

Both ON: 20k Ohms

Both OFF : 10k Ohms*

*Default Setting

ON

ON

ON

ON

ON

ON

ON

ON

THERM OUT

    24 VAC    GND

C R

THERM OUT

    24 VAC    GND

C R

THERM OUT

    24 VAC      GND

Vitodens 200

THERM OUT

    24 VAC      GND

C   R

Outdoor

Sensor

Input

Regular Setup

Vitodens 200 Setup ONLY

FIG 2A

FIG 2B

Ensure GND is ON

C   R

THERM OUT

    24 VAC    GND

C R

THERM OUT

    24 VAC    GND

C R

THERM OUT

    24 VAC      GND

Vitodens 200

THERM OUT

    24 VAC      GND

C   R

Outdoor

Sensor

Input

Regular Setup

Vitodens 200 Setup ONLY

FIG 2A

FIG 2B

Ensure GND is ON

C   R

If  you are using an existing 

transformer to connect the Base 

Unit, make sure the “C” and “R” 

wires are connected  to the right 

terminal.
Use a seperate power supply for 

the Base Unit when connecting to 

a 24 VAC powered control.

Ensure Proper setup, or damage 

will occur to the board.

Try not to mount the Base Unit by 

high voltage wiring or equipment, 

especially contactors or high 

voltage switching devices.

Summary of Contents for WAV-0110

Page 1: ...Page 1 HBX Control Systems Inc WAV 0112 WAV 0111 WAV 0110 Installation Manual WAV 0110 WAV 0111 WAV 0112 Version 1 005...

Page 2: ...o Safety Symbols and Warnings 3 o Receiving Inspection and Storage 3 o Description 4 o Technical Data and Dimensions 5 Installation and Wiring 6 8 o Mounting and Wiring 6 o Setting the Dipswitches 6 o...

Page 3: ...rsonal injury or have adverse effects on the installation process if handled incorrectly Disconnect Power Source The presence of low voltage 24VAC or high voltage 120VAC could result in personal injur...

Page 4: ...0 are Temperature range 20 F to 225 F operating temperature range down to 40 F Proprietary pairing and communication protocol 500 5k 10k 20k Ohm thermistor options built in dipswitch selectable Provid...

Page 5: ...MB Contains FFC ID 0A3MRF24J40MB Dimensions OZ OZ THERM OUT 24 VAC GND Signal Power OZ OZ THERM OUT 24 VAC GND 116 mm 78 mm 114 mm 76 mm Front View Outdoor Sensor Inside View Indoor Sensor Inside View...

Page 6: ...r Vitodens 200 setup Dip 1 ON only 500 Ohms Dip 2 ON only 5k Ohms Both ON 20k Ohms Both OFF 10k Ohms Default Setting ON ON ON ON ON ON ON ON Dip 1 ON only 500 Ohms Dip 2 ON only 5k Ohms Both ON 20k Oh...

Page 7: ...ed on the outdoor sensor until the red LED light turns off approx 15 seconds then release the button The LED will switch back on after a few seconds as it is initiating the pairing process see FIG 6 O...

Page 8: ...also at least 1 foot away from any metal in all directions so there is not interference with the wireless sensor FIG 9 Do not mount the outdoor sensor with the conduit knockout facing upwards as rain...

Page 9: ...or sensor and press the button referred to on page 7 which will force the outdoor unit to send a temperature to the base unit If after trying this step the base unit is still in Loss of Communication...

Page 10: ...64129 5 41 53777 8 47 45249 9 49 42750 13 55 36111 16 61 30615 19 67 26037 23 73 22200 26 79 18994 29 85 16297 33 91 14016 Temp C Temp F Resistance Ohms Dip 1 ON only 500 Ohms Dip 2 ON only 5k Ohms B...

Page 11: ...d above the purchasers sole remedy shall be at HBX s option repair or replacement The foregoing warranties and remedies are exclusive and in lieu of all other warranties expressed or implied either in...

Page 12: ...Page 12 HBX Control Systems Inc 2015 Phone 1 403 720 0029 Fax 1 403 720 0054 Email info hbxcontrols com Web www hbxcontrols com HBX Control Systems Inc 4516 112th Avenue SE Calgary AB Canada T2C 2K2...

Reviews: