H B X W A V - 0 1 1 0 O u t d o o r W i r e l e s s S e n s o r
V e r s i o n 1 . 0
Page 6
WIRING AND INSTALLATION
Setting the Dipswitches
The Dipswitches enable you to configure the Wireless Outdoor Sensor to work with different thermistor curves. See FIG 1 to
select the appropriate thermistor curve.
FIG 1
Mounting and Wiring the Base Unit
• Place a flat screwdriver into the top part of the base unit. Pry the screwdriver up on the back of the plastic and then pull off
the front cover.
• Supply 24 VAC power to the terminals in the base unit. This connection provides power to the microprocessor.
(see FIG 2A/2B)
Make sure to wire the thermistor section to the control AFTER powering the WAV-0110.
• Connect 18 AWG or similar wire to the THERM OUT terminals in the base and run the wire from here to the outdoor
sensor control terminal. See FIG 2A for regular setup, and FIG 2B for Vitodens 200 setup.
Dip 1 ON only: 500 Ohms
Dip 2 ON only: 5k Ohms
Both ON: 20k Ohms
Both OFF : 10k Ohms*
*Default Setting
ON
ON
ON
ON
ON
ON
ON
ON
Dip 1 ON only: 500 Ohms
Dip 2 ON only: 5k Ohms
Both ON: 20k Ohms
Both OFF : 10k Ohms*
*Default Setting
ON
ON
ON
ON
ON
ON
ON
ON
THERM OUT
24 VAC GND
C R
THERM OUT
24 VAC GND
C R
THERM OUT
24 VAC GND
Vitodens 200
THERM OUT
24 VAC GND
C R
Outdoor
Sensor
Input
Regular Setup
Vitodens 200 Setup ONLY
FIG 2A
FIG 2B
Ensure GND is ON
C R
THERM OUT
24 VAC GND
C R
THERM OUT
24 VAC GND
C R
THERM OUT
24 VAC GND
Vitodens 200
THERM OUT
24 VAC GND
C R
Outdoor
Sensor
Input
Regular Setup
Vitodens 200 Setup ONLY
FIG 2A
FIG 2B
Ensure GND is ON
C R
If you are using an existing
transformer to connect the Base
Unit, make sure the “C” and “R”
wires are connected to the right
terminal.
Use a seperate power supply for
the Base Unit when connecting to
a 24 VAC powered control.
Ensure Proper setup, or damage
will occur to the board.
Try not to mount the Base Unit by
high voltage wiring or equipment,
especially contactors or high
voltage switching devices.