Assembly Instructions M8155-EN
M8155-EN 2018-03
3/5
The initialisation window (Fig. 2) is displayed at the individual
device or operation module as soon as a new DFM-53 was
detected.
Fig. 2: Assignment DFM-53
7.
Proceed as follows to set the affiliation of a flow rate meter
board DFM-53 to a device:
Assign flow rate meter board ID (left column) to a unit by
entering the device address (right column).
Acknowledge assignment with the
key.
Exit initialisation window using the
key.
NOTICE!
Failure to assign the DFM-53 will render the unit
unusable.
The affiliation can be subsequently set via
Service \
Configuration \ Assignment DFM-53
. The
Service \
Konfiguration
menu is accessed via the 1?2? code.
8.
Main switch off and switch on again after 30 s
9.
Switch the unit on with the
key.
Fig. 3: Calibrating the flow rate DFM-53
10.
Flow rate calibration
Operate unit in regular mode at 40 °C for at least 10 minutes.
Set
Pressure relief with unit OFF
parameter in
Setting \
Miscellaneous
to "OFF".
Switch off unit using
button and wait at least 10 seconds.
Set
Flow rate calibration DFM-53
parameter in
Service /
Calibrating / Flow rate
internally to "ON".
The flow rate is calibrated automatically.
Set
Pressure relief for unit OFF
parameter in
Setting \
Miscellaneous
to "ON".