Assembly Instructions M8095-EN
M8095-EN 2020-09
12/13
Fig. 19: Configuration
10.
Configure unit
(to Software Version SW51-2 1431)
Service \ Configuration
menu using the “Support” user profile.
NOTICE!
When configuring note the following:
- Select product group according to table below
- Check data on the nameplate
- Read appendix of Operating Manual
(for special versions)
Product group Product type
TG
Thermo-5 temperature control unit
TR
Treat-5 water treatment unit
CL
Clean-5 cleaning unit
Fig. 20: Input window configuration
(from Software Version SW51-2 1449)
NOTICE!
As of software SW51-2 1449, the configuration is
requested after power ON automatically via the
input window
(
11.
Calibrate the pressure sensor
Fig. 21: Calibrate the pressure sensor 2
Read off the current
Main line pressure
under
Display \
Actual value
Set the parameter
Pressure sensor 2 offset
under
Service \
Calibrating \ Pressure
according to the following calculation:
Pressure Sensor 2 offset
new =
Pressure Sensor 2 offset
current
–
Main line pressure
current