HB Products HBIB Installation And Calibration Manual Download Page 1

 

 

 WWW.HBPRODUCTS.DK 

1 / 6

 

 

 

Installation and calibration manual 

 

HBIB Ice Bank Sensor 

 

 

 
 
 
 

 

 

 

 

 
 
 
 

Introduction 

The HBIB sensor measures the ice thickness between two steel insulated wires. The output is an analog 
signal 4-20 mA which falls linear to the ice thickness up to 30 mm and then in a nonlinear curve to appx. 100 
mm which is the limit.  
 
 
The sensor has a standard M12 interface like other HB-product sensors and is configured by the HB tool. 
The product consists of a box and two steel wires which can be adjusted in length by cutting.  
 
The sensor is based on the capacitive measurement principle and reacts on ice and water between the wires   
 
The sensor is based on the existing defrost sensor where the wire is mounted between the fins in an 
evaporator. The HB tool is not adjusted to Ice Bank application yet, so there are parameters which are 
irrelevant and can be ignored. Feedback and ideas are welcome 
 
 
 

 

 

Summary of Contents for HBIB

Page 1: ...andard M12 interface like other HB product sensors and is configured by the HB tool The product consists of a box and two steel wires which can be adjusted in length by cutting The sensor is based on the capacitive measurement principle and reacts on ice and water between the wires The sensor is based on the existing defrost sensor where the wire is mounted between the fins in an evaporator The HB...

Page 2: ...ymbol below is used to point out important safety instructions for the user It will always be found in places in the chapters where the information is relevant The safety instructions and the warnings in particular must always be read and adhered to CAUTION Refers to a possible limitation of functionality or risk in usage NOTE Contains important additional information about the product and provide...

Page 3: ...cable ties or similar all the way from the box to the end of the wire Loose wires will impact stability 3 The free end of the wires must be placed above water level to avoid short circuiting by the water Likewise it is important that the insulation is unbroken on the wires in the water 4 The connection between the box and a PLC can normally be installed with a standard unshielded cable If the EMC ...

Page 4: ...ensor configuration All HB product sensors can be configured using a laptop and a M12 USB cable The software can be downloaded freely on the HB products web page The configuration data can be stored in the sensor and will be there until erased even without power connection just like you store data on a memory stick When you change a value setting there will be put a check mark next to it and that ...

Page 5: ...7 Calculate 0 4 actual measurement and type that in the box called Zero calibration in pF 8 Calculate 0 6 actual measurement and type that in the box called SPAN calibration in pF 9 Click on the box called Send Zero Span values Now the sensor will send you a signal from 4 to 20 mA linear to the measurement from Zero to Zero SPAN in the case shown from 185 to 463 The ice thickness will now be linea...

Page 6: ...tions IEC 68 2 6 4g Certifications EMC Emission EN61000 3 2 EMC Immunity EN61000 4 2 Mechanical specifications Materials mechanical parts AISI304 wire Materials electronic parts Nylon insulation Cable entry PG9 M12 Sensor Repair Complaints are processed by HB Products dealers distributors Please consider their complaint procedures before returning the sensor Note All terminals are protected agains...