42
6. APPENDIX (continued)
Problem
Error
codes
Description
Solution
Flow sensor fault
E03
The sensor is open or has short-circuited.
Check the AIN2 connections on the card
or replace the sensor
Lack of water, check the filtration pump
operation
Check the stop valve opening
Check the by-pass adjustment
Water outlet temperature fault
E05
Applies only in Cold mode, Water outlet
temperature < 4°C
Stop the heat pump, serviceability limit
reached
Input/Output temperature difference
> 13°C
E06
Applicable in Cold mode only
Lack of water, check the filtration pump
operation
Check the stop valve opening
Check the by-pass adjustment
Antifreeze protection Cold mode
E07
Water output temperature < 4°C
Check the red AIN7 connector on
the board and measure the sensor's
resistance; if it is under 100 Ω or over
500 kΩ, replace it.
Stop the heat pump, drain the
condenser, high risk of it freezing.
Communication problem
E08
No communication between the printed
circuit board and the user interface
Check the connectors - see the wiring
diagram
Level 1 antifreeze protection
E19
2°< Water temperature < 4°
and Air temperature < 0°
Stop heat pump operation, empty the
condenser to avoid freezing, by default
the heat pump starts the filtration pump
to avoid icing over
Level 2 antifreeze protection
E29
Water temperature < 2°
and Air temperature < 0°
Stop heat pump operation, empty the
condenser to avoid freezing, by default
the heat pump starts the filtration pump
and the heat pump to avoid icing over.
DC1 fan motor fault
F031
Motor jammed or faulty connection
Check free rotation; check CN1
connectors; replace the motor
The heat pump does not start
F08
Possibly an inversion or lack of phase
Reverse two phases on the R-S-T
terminal block.
Check the connection and tightness of
the phases.
Exterior temperature too low
TP
Outdoor temperature too low,
< H34 (-15°C fault)
Check the AIN9 connector on the board
and measure the sensor's resistance;
if it is under 100 Ω or over 500 kΩ,
replace it.
Check the value of parameter H34
Pressure sensor fault
PP
The sensor is open or short-circuiting
Check the connections see electrical
diagram
Summary of Contents for SUMHEAT HP5171DT3
Page 2: ......
Page 35: ...31 Page laissée blanche intentionnellement ...
Page 81: ...31 Page left intentionally blank ...
Page 127: ...31 Página en blanco intencionalmente ...
Page 173: ...31 Página deixada em branco intencionalmente ...
Page 219: ...31 Seite bewusst leer gelassen ...
Page 265: ...31 Opzettelijk leeg gelaten pagina ...
Page 311: ...31 Pagina lasciata intenzionalmente bianca ...
Page 357: ...31 Denne siden er blank med hensikt ...
Page 403: ...31 Намеренно оставлено пустым ...
Page 417: ......