Torque (motor) Minimum

133”lb/15Nm

Torque (spring) Minimum

133”lb/15Nm

Minimum Required Torque

27”lb/3Nm

Supply Voltage/Frequency

24...230vac/dc, +15% / -20% AC:50/60Hz

Current Draw

4.7A @ 3 sec Mode MAX

Wiring Class

Class 1 (grounded)

Angle of Rotation

95 deg including 5 deg pre-load

Runtime (Power)

30 seconds @ 90 deg

Motor Type

Brushless DC

Runtime (Spring)

10 seconds @ 90 deg

Life Cycles at 10 sec Spring

Minimum 10,000 Cycles at 10 sec Spring

Response Time (Spring)

Up to 1 second after power failure

Control Mode

On/Off/Jog 

On/Off/Jog

4-20mA or 2-10vdc IN

Feedback

None

None

4-20mA or 2-10vdc OUT

Auxiliary Switch Rating 

(2) - fixed @ 5° and 85°

None

0.1A @ 250vac / 3A @ 24vac

None

Drive Configuration

12mm Double Square, 100% Overload-Proof

 

Self-Locking up to 133”lbs/15Nm

Electrical Connections

1m Cable, Exits through 1/2” EMT Connector

Environmental Rating

NEMA 4X / IP66

Manual Override

Supplied Hex Key (Opt Handwheel)

Integral Heater

Thermostatically controlled

Housing Material

Aluminum die casting

Physical Dimensions

8.3”L x 3.7”W x 3.2”D / 210mm x 95mm x 80mm

Weight

7.8 lbs / 3.5Kg (no options installed)

Ambient Operating Range

Storage Temp: -40F/+158F (-40C/+70C)

Working Temp: -40F/+122F (-40C/+50C)

Duty Cycle (>14 sec Mode)

50%

50%

50%

Maintenance

Maintenance Free

Default Mode:                     Power:

Spring:

133”lb/15Nm - 30 sec @ 90 deg

133”lb/15Nm - 10 sec @ 90 deg

Actuator Specifications

RSR3 Series

WARNING – 

the manual override allen key will NOT remain in position...  once you let go of the key, 

the spring WILL drive the actuator back to its unwound position.

1-888-HAY-INDL (1-888-429-4635)

RSR3IOM Rev B  ECR 043V

Page 4 of 9 

USE ONLY HAYWARD GENUINE REPLACEMENT PARTS

www.haywardflowcontrol.com

Hayward Flow Control

1-888-HAY-INDL (1-888-429-4635)

RSR3IOM Rev B  ECR 043V

Page 4 of 9 

USE ONLY HAYWARD GENUINE REPLACEMENT PARTS

www.haywardflowcontrol.com

Hayward Flow Control

The RSR has a manual override built into the geartrain. Inserting the supplied allen key into 

the port (black arrow above), you can manually turn the spring mechanism to WIND the spring 

system. However you CANNOT UNWIND the spring system if power is present. As shown 

above, the RSR has a spring CW and a spring CCW side, identified by the “L” and “R” on 

their respective sides of the actuator label. Notice that the override key rotates in OPPOSITE 

directions depending on which side of the actuator you are accessing. 

Note label identifier “R” (blue arrow). The 

manual override key winds the spring in a 

CCW direction, and the spring unloads in 

a CW direction (default for Hayward valve 

assemblies). 

Note label identifier “L” (blue arrow). The 

manual override key winds the spring in 

a  CW  direction,  and  the  spring  unloads 

in  a  CCW  direction.  (non-standard  for 

Hayward assemblies).

Summary of Contents for RSR3 Series

Page 1: ...i of i USE ONLY HAYWARD GENUINE REPLACEMENT PARTS www haywardflowcontrol com Hayward Flow Control TO PREVENT POTENTIAL INJURY DEATH OR DAMAGE TO PROPERTY READ THIS MANUAL CAREFULLY AND COMPLETELY Installation Operation and Maintenance Instructions RSR3 Series ...

Page 2: ...rty damage To reduce the risk of electric shock do NOT use an extension cord to connect unit to electric supply Provide a properly located electrical receptacle Before working on any electrical equipment turn off power supply to the equipment WARNING To reduce the risk of electric shock replace damaged wiring immediately WARNING Ground all electrical equipment before connecting to electrical power...

Page 3: ...k wise CW or counter clockwise CCW direction by selecting which SIDE of the actuator is mounted face up To change the direction of spring return travel simply remove the actuator from its mount flip it over and re install Spring return direction will now be reverse of what it was before the change was made Notice Hayward RSR actuators are installed onto valve assemblies oriented to fail CLOSED in ...

Page 4: ...al condensate build up 14 The actuator will NOT activate until the internal temperature reaches at least 8 deg F 20 deg C All functions are disabled until after this heating up period 15 The actuator must be operated with a load requirement of AT LEAST 27 lbs 3Nm 16 The initial inrush upon power up of the actuator regardless of voltage is roughly 2 0A for 1 second 17 The power consumption for the ...

Page 5: ...ee Default Mode Power Spring 133 lb 15Nm 30 sec 90 deg 133 lb 15Nm 10 sec 90 deg Actuator Specifications RSR3 Series WARNING the manual override allen key will NOT remain in position once you let go of the key the spring WILL drive the actuator back to its unwound position 1 888 HAY INDL 1 888 429 4635 RSR3IOM Rev B ECR 043V Page 4 of 9 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS www haywardflowcon...

Page 6: ...action recoil spring cast aluminum lower housing Spring CCW Side Spring CW Side wind spring Spring CW Side Stick port Wire sizing data is provided in the table below to assist in the selection of the proper wire size for Hayward RSR3 actuators using various wire sizes over distance Please make sure to reference the correct voltage and do not exceed the indicated length of the wire run for each mod...

Page 7: ...g low temperature applications Note 2 Option internal aux switches NOT available on proportional control models GND 1 2 3 4 heater 24 to 240 VAC DC If mounted CW side UP close a drive CCW ATTENTION If you use this type of wiring the heater does NOT work when a is open a GND 1 2 3 4 heater 24 to 240 VAC DC If mounted CCW side UP close a drive CW ATTENTION If you use this type of wiring the heater d...

Page 8: ... Function 2 potential free Form C Mech switches Max Current AC DC 3A 24V 0 25A 250V min current 4mA 5V Mechanical Life 2x10 6 switch cycles Cable Connection 1 3C20 cable for each sw 1M long Ambient Termp F C 58 F 140 F 50 C 60 C Accuracy 5 Switch Hysteresis approx 5 Switch Material Au plated Ag Contacts Technical Data cam tool HS1 90 90 CAMS SHOWN 0 ON CCW MOUNT CAMS SHOWN 90 ON CCW MOUNT R L BLK ...

Page 9: ... 2 Be sure the actuator has the correct side up after mounting to the valve 3 The lower end of the handwheel hex drive shaft fits directly into the override socket near the middle of the actuator 4 Mount the override bracket using the 2 supplied self threading screws RSR M23 Short is used without RSR EXT X and RSR M23 Long must be used when RSR EXT X is attached to the actuator 5 Slide the 3mm hex...

Page 10: ...oes not work LED indicator shows steady GREEN Actuator does not work LED indicator shows blinking RED A Modulating actuator reaches its electrical end of travel 0v 4mA and or 10v 20mA before reaching damper or valve mechanical end of travel 90 degrees or less of mechanical travel Actuator does not work LED indicator flashes irregularly Spring return function is 3 sec 90 degrees Should be 10 sec 90...