RSR3-0
RSR3-2
RSR3-P
Torque (motor) Minimum
133”lb/15Nm
Torque (spring) Minimum
133”lb/15Nm
Minimum Required Torque
27”lb/3Nm
Supply Voltage/Frequency
24...230vac/dc, +15% / -20% AC:50/60Hz
Current Draw
4.7A @ 3 sec Mode MAX
Wiring Class
Class 1 (grounded)
Angle of Rotation
95 deg including 5 deg pre-load
Runtime (Power)
30 seconds @ 90 deg
Motor Type
Brushless DC
Runtime (Spring)
10 seconds @ 90 deg
Life Cycles at 10 sec Spring
Minimum 10,000 Cycles at 10 sec Spring
Response Time (Spring)
Up to 1 second after power failure
Control Mode
On/Off/Jog
On/Off/Jog
4-20mA or 2-10vdc IN
Feedback
None
None
4-20mA or 2-10vdc OUT
Auxiliary Switch Rating
(2) - fixed @ 5° and 85°
None
0.1A @ 250vac / 3A @ 24vac
None
Drive Configuration
12mm Double Square, 100% Overload-Proof
Self-Locking up to 133”lbs/15Nm
Electrical Connections
1m Cable, Exits through 1/2” EMT Connector
Environmental Rating
NEMA 4X / IP66
Manual Override
Supplied Hex Key (Opt Handwheel)
Integral Heater
Thermostatically controlled
Housing Material
Aluminum die casting
Physical Dimensions
8.3”L x 3.7”W x 3.2”D / 210mm x 95mm x 80mm
Weight
7.8 lbs / 3.5Kg (no options installed)
Ambient Operating Range
Storage Temp: -40F/+158F (-40C/+70C)
Working Temp: -40F/+122F (-40C/+50C)
Duty Cycle (>14 sec Mode)
50%
50%
50%
Maintenance
Maintenance Free
Default Mode: Power:
Spring:
133”lb/15Nm - 30 sec @ 90 deg
133”lb/15Nm - 10 sec @ 90 deg
Actuator Specifications
RSR3 Series
WARNING –
the manual override allen key will NOT remain in position... once you let go of the key,
the spring WILL drive the actuator back to its unwound position.
1-888-HAY-INDL (1-888-429-4635)
RSR3IOM Rev B ECR 043V
Page 4 of 9
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
www.haywardflowcontrol.com
Hayward Flow Control
1-888-HAY-INDL (1-888-429-4635)
RSR3IOM Rev B ECR 043V
Page 4 of 9
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
www.haywardflowcontrol.com
Hayward Flow Control
The RSR has a manual override built into the geartrain. Inserting the supplied allen key into
the port (black arrow above), you can manually turn the spring mechanism to WIND the spring
system. However you CANNOT UNWIND the spring system if power is present. As shown
above, the RSR has a spring CW and a spring CCW side, identified by the “L” and “R” on
their respective sides of the actuator label. Notice that the override key rotates in OPPOSITE
directions depending on which side of the actuator you are accessing.
Note label identifier “R” (blue arrow). The
manual override key winds the spring in a
CCW direction, and the spring unloads in
a CW direction (default for Hayward valve
assemblies).
Note label identifier “L” (blue arrow). The
manual override key winds the spring in
a CW direction, and the spring unloads
in a CCW direction. (non-standard for
Hayward assemblies).