USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
HRSN4FSIOM Rev E ECR 132V
Page 9 of 32
Hayward Flow Control
1-888-HAY-INDL (1-888-429-4635)
www.haywardflowcontrol.com
Notes:
The enclosure, while NEMA 4X rated, should NOT
be installed in direct sunlight . If installed outdoors,
it should be installed in the shade under a rain hood
using rain-tight conduit fittings and connectors .
The Enclosure is a sealed NEMA 4X type stainless steel
type without conduit holes or knock-outs . This allows
complete flexibility when mounting . The enclosure can
be oriented in any direction, and can be mounted on
wall, floor, ceiling, uni-strut or any other fixed surface .
Conduit penetrations by others . Interconnect wiring
between transformer panel and actuator by others per
the supplied wiring diagram .
Power Supply:
The HRSN4 Series Battery Backup units require a
500VA 24vac / 20A 24vdc power supply directly into the
actuator terminal block .
To facilitate various site power availability, an optional
enclosure is offered which houses an appropriately sized
toroidal transformer to supply the 24V power to the
actuator . Mounted separately, the enclosure is a NEMA
4X / IP65 9 x 7 x 6 hinged door cabinet .
Mounted to a back plane, the transformer primary
and secondary are pre-wired to a six position dual
terminal block .
HRSN4 Series Transformer Enclosure
(120/230VAC Installations)
HRSN4 Series Transformer
(120/230VAC Installations)
HRSN4 Series Transformer Enclosure
Dimensional Data
Notice:
All HRSN4 Series Battery Backup units require
a
500VA 24vac / 20A 24vdc power supply directly
into the actuator terminal block .
9.0 /
228.6
6.0 /
152.4
7.0 /
177.8
Model
Line
Power
Size
in /
mm
Weight
lbs /
kg
HRSBBC120-100 120VAC 100VA
9.0 W x 7.0 H
x 6.0 D
228.6 W x 177.8 H
x 52.4 D
12 /
5.5
HRSBBC120-250 120VAC 250VA
14 /
6.4
HRSBBC120-500 120VAC 500VA
20 /
9.1
HRSBBC230-100 230VAC 100VA
12 /
5.4
HRSBBC230-250 230VAC 250VA
14 /
6.4
HRSBBC230-500 230VAC 500VA
20 /
9.1
POWER SUPPLIES
120/230V TRANSFORMER MOUNTING AND SETUP