USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
HRSN4FSIOM Rev E ECR 132V
Page 4 of 32
Hayward Flow Control
1-888-HAY-INDL (1-888-429-4635)
www.haywardflowcontrol.com
Control
Voltage
Torque Switches
Fail Safe
Local Control Station
IOM
Wiring Diagram Page
On/Off
24VDC/VAC
XTS/TS
FS
None
This IOM
Proportional
24VDC/VAC
XTS/TS
FS
None
This IOM
On/Off
120VAC *
XTS/TS
FS
None
This IOM
Proportional
120VAC *
XTS/TS
FS
None
This IOM
On/Off
230VAC *
XTS/TS
FS
None
This IOM
Proportional
230VAC *
XTS/TS
FS
None
This IOM
* Requires use of a transformer to convert supply voltage to 24V .
ACTUATOR OPTIONS
Below are Terms and Definitions used throughout this manual .
1 . XTS/TS
product manufactured without/with Torque Switches .
2 . FS
product manufactured with Fail Safe built-in .
3 . LCS
is an industry acronym for a Local Control Station .
4 . CW
is Clockwise and
CCW
is Counterclockwise .
CONVENTIONS USED IN THIS MANUAL
Use this table to efficiently select the actuator and wiring diagram you require .
ACTUATOR SPECIFICATIONS
(20 SERIES)
Supply
Torque Output (
lbf-in
/ Nm)
3540
/ 400
5310
/ 600
7080
/ 800
8850
/ 1000
24VAC
-
24VDC
Current Draw (Start / Run / LRA)
7.0A / 5.8A / 15A
7.0A / 5.8A / 15A
7.0A / 5.8A / 15A
10.5A / 7.8A / 22A
Speed (90°) DC-60Hz/50Hz, seconds
21 / 21
28 / 28
34 / 34
34 / 34
Motor - 24V DC Perm Magnet 2 Pole Brush
40W
40W
40W
90W
On/Off /
Proportional
Duty Cycle (IEC60034)
75% (S2-15 min) /
75% (S4-75%)
Motor Protection, Temp / Class
All - 130°C / Class B
Motor Starts, per hour, Max
All - 600
Requires 120:24 Transformer Pack, 500VA
HRSBBC120-500
HRSBBC120-500
HRSBBC120-500
HRSBBC120-500
120VAC
Transformer Current Draw (Inductive)
1.75A
1.75A
1.75A
2.63A
Speed (90°) 60Hz / 50Hz, seconds
21 / 21
28 / 28
34 / 34
32 / 34
Motor - 24V DC Perm Magnet 2 Pole Brush
40W
40W
40W
90W
On/Off /
Proportional
Duty Cycle (IEC60034)
75% (S2-15 min) /
75% (S4-75%)
Motor Protection, Temp / Class
All - 130°C / Class B
Motor Starts, per hour, Max
All - 600
Requires 230:24 Transformer Pack, 500VA
HRSBBC230-500
HRSBBC230-500
HRSBBC230-500
HRSBBC230-500
230VAC
Transformer Current Draw (Inductive)
0.55A
0.55A
0.55A
0.55A
Speed (90°) 60Hz / 50Hz, seconds
21 / 21
28 / 28
34 / 34
32 / 34
Motor - 24V DC Perm Magnet 2 Pole Brush
40W
40W
40W
90W
On/Off /
Proportional
Duty Cycle (IEC60034)
75% (S2-15 min) /
75% (S4-75%)
Motor Protection, Temp / Class
All - 130°C / Class B
Motor Starts, per hour, Max
All - 600
All
Environmental Rating
NEMA 4/4X & IP67
Electrical Entry (2)
3/4" EMT or Polyamide gland
Control
On/Off or Proportional
Auxiliary Switch - End of Travel
(2) Form A Volt-Free, Rated 10A @ 250vac
Ambient Operating Range
-22°F to +158°F / -30°C to +70°C
Humidity Range
0-95% RH
Altitude Limit
9850 ft / 3000 m
BATTERY
SPECIFICATIONS
Type
Lithium Ion 22.2v pack with charge / discharge control
Cell Arrangement
Bank of 8 (eight) x 2.8V w/ logic control
Service Life - @ Rated Torque Cycle Drain
10,000 cycles @ 5% Stored energy drain per cycle
Enclosure
Entire Battery System under Main Cover
HRSN4A
HRSN4B
HRSN4C
HRSN4D
HRSN4A~4D (20 SERIES)
TECHNICAL INFORMATION