USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
HRSLCSSPLMNTIOM Rev A
Page 8 of 42
Hayward Flow Control
1-888-HAY-INDL (1-888-429-4635)
www.haywardflowcontrol.com
HRCL and HRCD advanced stand-alone actuators are designed to be installed in new contruction sites or existing
sites where there are NO existing local control capabilities. These single phase and low voltage proportional control
actuators have several versions that continue to add more features and options than the standard actuator range.
These actuators generate a 24V control output that is connected to a remote PLC or BAS to control the actuator. This
24v output also serves as a status of the power connections and actuator operability. Any internal faults will disable
the 24v control output. Moreover, these units incorporate a Local Control Station (LCS) to facilitate operating the
actuator locally. Having this feature allows operation of the actuator WITHOUT having an existing PLC or BAS based
analog controller while also providing operability with existing external controls.
Inside the actuator/LCS package, you will find:
1 . Integral
Local Control Device
. This series is designed to operate in Local mode (control knobs located on the face
of the LCS which is an integral part of the actuator) or in Remote mode, which utilizes commands from a PLC, BAS
or other volt-free contact (dry contact) automation device.
WD165TS
WD135TS
Apply no external power
A. While in Local mode, the actuator
responds to the position of the
controls located on the face of the
integral LCS.
B. The Mode switch (CL and CD
Series) employs a padlockable
lever that locks the Mode switch
in any of its three positions,
preventing unauthorized changes
in the operating mode (Local, Off or
Remote).
24V~230V On/Off Control
LCS, XTS/TS
HRCL, HRCD 3A~6A
THEORY OF OPERATION
Back to TOC