Page 17 of 22
HEATPRO HEAT PUMP
HP13023772 Rev: D
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Pomona, CA Clemmons, NC Nashville, TN
Tel: 908.351.5400 www.haywardpool.com
Troubleshooting
Circuit Breakers:
If it is suspected that a circuit breaker is tripped, turn the breaker to the “Off” position and
then back to the “On” position.
NOTICE:
Service to be conducted
ONLY
by an EPA Certified Service Technician.
General Troubleshooting Guide for Hayward HeatPro Heat Pump
Problem
Possible Cause
Possible Solution(s)
No power to unit
Make sure power is on.
Breaker is tripped
Check the breaker / see note above
Thermostat not turned up high
enough
Turn thermostat up until unit comes on
5 minute delay timer still
running
Be sure the 5 minute delay has passed
Make sure filter, strainer basket and skimmer basket are
clean
Make sure filter pump is on
Low water flow
Unhook cleaning devices (skimmers, crawlers, etc.)
Outside temperature too low
Check outside ambient temperature or wait for warmer
temperatures to operate. (refer to Operating section)
Unit is not operating.
Fan not functioning
Call Pool Service Provider.
Check output air temperature
to input air temperature.
Differential should be between
5 and 12 ºF
Low ambient air temperature. Allow outside air
temperature to exceed 60ºF, and then re-check.
Heat pump is running but
is not heating “Run” light
does not come on.
System Component failure.
Call Pool Service Provider.
Thermostat set too high
Turn thermostat down
Heat pump runs
continually
Electrical component failure
Turn off the filter pump. If the unit is still running after 2
minutes, turn off the power to the unit and call Pool
Service Provider.
Bad valve or improper water
flow
Check valve settings and ensure water flow is sufficient
(is the filter pump running continually?) If heat pump
continues to cycle, turn unit off to prevent compressor
damage.
Check evaporator coil for severe frost. Turn unit off to
prevent compressor damage. Allow the evaporator to
thaw and restart. If issue continues, call a pool service
provider.
Heat pump is cycling
(on /
off too quickly)
Low refrigerant, low ambient
temp, or high humidity with
low ambient temp
If heat pump continues to cycle, turn unit off to prevent
compressor damage- and call Pool Service Provider.
Condensation
This is normal and there is no reason to be concerned
Water is coming from
bottom of unit
Possible water leak
Turn the unit off for several hours, but leave the filter
pump running continuously. If water discharge
ceases, then it is only condensation. Otherwise there is
a possible leak.