31
Problem
Error codes
Description
Solution
Water inlet sensor defect.
P01
The sensor is open or presents a
short-circuit.
Verify or replace the sensor.
Water outlet sensor defect.
P02
The sensor is open or presents a
short-circuit.
Verify or replace the sensor.
De-icing sensor defect.
P05
The sensor is open or presents a
short-circuit.
Verify or replace the sensor.
Exterior temperature sensor defect.
P04
The sensor is open or presents a
short-circuit.
Verify or replace the sensor.
Compressor aspiration sensor defect
P07
The sensor is open or presents a
short-circuit.
Verify or replace the sensor.
The inlet and outlet difference in
water temperature is too high.
E06
Water flow volume is insufficient,
water pressure difference is too low/
too high.
Verify the water flow, or system
obstruction.
Antifreeze Protection
Cold mode
E07
Water outlet quantity is too weak.
Verify the water flow, or the outlet
water temperature sensor.
Level 1 antifreeze protection
E19
Air temperature or water inlet
temperature is too weak.
Level 2 antifreeze protection
E29
Air temperature or water inlet
temperature is still too weak.
High pressure protection
E01
Pressure of the refrigeration circuit
is too high, or the water flow is too
low, or the coil is obstructed or the
air flow is too weak.
Verify the high pressure switch and
the refrigeration circuit pressure.
Verify the water or air flow. Verify that
the flow switch is working correctly.
Verify the water inlet/outlet valve
openings.
Verify the by-pass setting.
Low pressure protection
E02
Refrigeration circuit pressure is too
weak, or air flow is too weak or the
coil is obstructed.
Verify the low pressure switch and
the refrigeration circuit pressure to
determine if there is a leak.
Clean the coil surface.
Verify the fan rotation speed.
Verify that there is free air flow to
the coil.
Flow detector defect
E03
Water flow is insufficient or the
detector is in short-circuit or
defective.
Verify the water flow, verify the
filtration pump and the flow detector
to see if they have any possible
problems.
Communication problem
E08
Problem with the LED controller or
the PCB connection.
Check the connection of the NET and
NET 1 cables.
The compressor will not start
E08
Phase missing or phase order
incorrect
check that the 3 phases are present
modify the phase order at the heat
pump’s electrical connection terminal
block
Summary of Contents for EnergyLine pro
Page 26: ...24 6 3 Vues clat es et pi ces d tach es ENP6MASC 6 ANNEXES suite...
Page 28: ...26 ENP6TASC 6 ANNEXES suite 41 42 43 44 45...
Page 30: ...28 ENP7TASC 6 ANNEXES suite 41 42 43 44 45...
Page 35: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual ENERGYLINE PRO ISENPASC Rev C...
Page 60: ...24 6 APPENDIX continued 6 3 Exploded view and spare parts ENP6MASC...
Page 62: ...26 6 APPENDIX continued ENP6TASC 41 42 43 44 45...
Page 64: ...28 6 APPENDIX continued ENP7TASC 41 42 43 44 45...
Page 68: ...32 6 APPENDIX continued 6 5 Warranty...
Page 94: ...24 6 ANEXOS continuaci n 6 3 Despiece y piezas de recambio ENP6MASC...
Page 96: ...26 6 ANEXOS continuaci n ENP6TASC 41 42 43 44 45...
Page 98: ...28 6 ANEXOS continuaci n ENP7TASC 41 42 43 44 45...
Page 102: ...32 6 ANEXOS continuaci n 6 5 Garant a...
Page 128: ...24 6 ANEXOS continua o 6 3 Vistas explodidas e pe as sobressalentes ENP6MASC...
Page 130: ...26 6 ANEXOS continua o ENP6TASC 41 42 43 44 45...
Page 132: ...28 6 ANEXOS continua o ENP7TASC 41 42 43 44 45...
Page 137: ...ENERGYLINE PRO ISENPASC Rev C HEIZPUMPENANLAGE F R EIN SCHWIMMBECKEN Einbau Anleitungshandbuch...
Page 162: ...24 6 ANHANG Fortsetzung 6 3 Explosionszeichnungen und Einzelteile ENP6MASC...
Page 164: ...26 6 ANHANG Fortsetzung ENP6TASC 41 42 43 44 45...
Page 166: ...28 6 ANHANG Fortsetzung ENP7TASC 41 42 43 44 45...
Page 170: ...32 6 ANHANG Fortsetzung 6 5 Garantie...
Page 171: ...ENERGYLINE PRO ISENPASC Rev C ZWEMBAD WARMTEPOMP Installatie en bedieningshandleiding...
Page 196: ...24 6 BIJLAGEN vervolg 6 3 Opengewerkte tekeningen en onderdelen ENP6MASC...
Page 198: ...26 6 BIJLAGEN vervolg ENP6TASC 41 42 43 44 45...
Page 200: ...28 6 BIJLAGEN vervolg ENP7TASC 41 42 43 44 45...
Page 230: ...24 6 APPENDICI segue 6 3 Esplosi e parti di ricambio ENP6MASC...
Page 232: ...26 6 APPENDICI segue ENP6TASC 41 42 43 44 45...
Page 234: ...28 6 APPENDICI segue ENP7TASC 41 42 43 44 45...
Page 238: ...32 6 APPENDICI segue 6 5 Garanzia...
Page 239: ...ENERGYLINE PRO ISENPASC Rev C VARMEPUMPE TIL SV MMEBASSENG Installerings og brukerveiledning...
Page 264: ...24 6 VEDLEGG fortsetter 6 3 Sprengskisse og reservedeler ENP6MASC...
Page 266: ...26 6 VEDLEGG fortsetter 6 3 Sprengskisse og reservedeler ENP6TASC 41 42 43 44 45...
Page 268: ...28 6 VEDLEGG fortsetter ENP7TASC 41 42 43 44 45...
Page 273: ...ENERGYLINE PRO ISENPASC Rev C...
Page 275: ...1 1 Hayward 3 4 1 R410A 1 1975...
Page 279: ...5 3 3 1 3 2 2500 700 700 300 500...
Page 280: ...6 3 3 3 50 50 15 30 Titane 50 mm 50 mm...
Page 283: ...9 7 8 3 6 2 1 2 C 9 5 10 10 03 11 0 5 C 03 6 4 3 3 3 L1 L2 L3 4 4...
Page 284: ...10 3 6 2 C 3 1 3 T T...
Page 286: ...12 4 1 1...
Page 287: ...13 4 20 4 2 1 2 3 4 4 3 ON1 ON2 OFF1 OFF2 1 D part 1 2 ON1 2 3 4 1 1 2 ON1 OFF1 2 3 4 ON2 2...
Page 288: ...14 4 1 2 ON1 2 3 4 5 2 ON1 6 7 2 1 4 2 1 2 1 ON2 2 4 4...
Page 289: ...15 4 4 5 0 5 C I 30 C 4 6 5 5...
Page 290: ...16 4 7 SILENCE 600 ENP6MASC 830 ENP6TASC 800 ENP7TASC 8 4 1 2 8 3 8 4 8 1 2 3...
Page 291: ...17 4 1 2 ON1 2 4 3 4 5 OFF...
Page 292: ...18 4 6 7 8 ON OFF 10 7...
Page 293: ...19 5 5 1 5 2...
Page 296: ...22 6 6 2 1 2 230V 50Hz 1 2 2 1 2 7 230V 50Hz OUT2...
Page 298: ...24 6 6 3 ENP6MASC...
Page 300: ...26 6 6 3 ENP6TASC 41 42 43 44 45...
Page 302: ...28 6 ENP7TASC 41 42 43 44 45...
Page 304: ...30 6 6 4...
Page 305: ...31 P01 P02 P05 P04 P07 E06 E07 1 E19 2 E29 E01 E02 E03 E08 NET NET 1 E08 3 6...
Page 306: ...32 6 6 5 HAYWARD HAYWARD HAYWARD HAYWARD HAYWARD...