USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
9
Adanced (Dealer) Setup Options
The CAT 1000 offers a host of advanced options to ensure compatibility with a wide variety of applications. The advanced programming menu contains
features which are usually implemented during initial dealer setup and do not need to be routinely changed by the operator.
Enhanced No-Flow Alarm
When the flow sensor reads that there is no flow, the controller goes into a No-Flow alarm. The no-flow alarm sounds an audible alarm and disables all
controller operation until flow has resumed. In addition, the LED display will flash the following prompt:
no Flo
Power on Display
At Power on, the controller displays the firmware version number. The firmware version number is displayed on the ORP channel LED display:
6.12
Firmware version number (or later)
Entering Advanced Setup Mode
Find the Hidden Button (#1) located behind the large ORP text over the ORP digital display.
1. Press and hold the Hidden Button (#1) for five seconds to enter the advanced setup mode.
2. Press the Up (#2) or Down (#3) arrow buttons to scroll through the programming options.
3. Press the Enter Button (#4) to make a selection.
ORP Proportional Feed
O.PF
ORP Proportional Feed. Selects either fixed setpoint or proportional control.
OFF
Off. The ORP feed output is activated based on a simple above or below setpoint decision. When the measured ORP value is greater than or
equal to the ORP setpoint the ORP feed output is turned off. When the measured ORP value is less than the ORP setpoint the ORP feed output is turned
on.
ON
On (Default). The ORP feed output is activated based on the difference between the ORP setpoint and measured ORP value. As the difference
increases, the duration the ORP feed output is turned on to increase to 20, 30, 40, and 50 seconds of the 60 second cycle, and then the ORP feed
output is turned on continuously.
ORP Overfeed Timer
O.OF
ORP Overfeed Timer. Selects whether a time limit will be imposed on the ORP feed output.
OFF
When ORP Overfeed Timer is set to OFF, the ORP feed output will remain activated as long as an ORP feed condition is indicated. When any
other selection is made, an overfeed limit timer is enabled on the ORP feed output. After the ORP feed output has been turned on for a period of time
greater than this limit, the ORP channel is turned off and placed into an overfeed alarm condition which must be manually reset.
On
When ORP Overfeed Timer is set to ON, the ORP feed output must be on continuously for the overfeed time limit, rather than in the part of
the proportional feed cycle in which the ORP feed output is on for only a portion of the 60 second proportional feed cycle.
After the ORP feed channel is placed into the overfeed alarm condition, the ORP channel is turned off and the ORP Feed Mode indicator flashes rapidly
to indicate the alarm. Press the ORP Feed Mode button (#5) to return the ORP channel to the off, manual or automatic feed mode. This will reset the
ORP overfeed alarm and restart the overfeed timer. The ORP overfeed alarm will also be reset if the controller is powered off and then back on.