background image

Listed 

Cap

Listed Gas 

Vent

H (minimum) - Minimum height from 

roof to lowest discharge opening

Lowest discharge opening

Roof pitch is x/12

 1.  If connected, turn pump, main gas valve, and heater 

      power off.

 2.  Locate the heater as close as practical to the gas vent 

      exit.  

 3.  Remove the countersunk phillips-head screws and 

      remove the flue cover panel on top of the heater and 

      discard.  Save the countersunk screws as they will be 

      re-used later.

 4.  Remove the screws that fasten the heat barrier to the 

      heater.  Remove the heat barrier and discard.  See 

      Figure 3.

 5.  Remove the screws that fasten the rain guard to the 

      heater.  Remove the rain guard and discard.  See 

      Figure 3.

 6.  Install the vent pipe adapter plate included in this kit 

      into the heater using the #10 screws included with this 

      kit.  Ensure the white gaskets are in place under the 

      vent pipe adapter plate before installing.  See Figure 4.

 7.  Install the new flue cover included with this kit over the 

      vent pipe adapter and secure with the countersunk 

      screws from step 3 above.  See Figure 5.

 8.  Remove heater front access door.

 9.  Install the vent pressure switch provided with this kit 

      inside the heater using 2 #10 screws as shown in 

      Figure 6.  If you are refitting a heater with an 

      FDXLRGK1xxx kit, you will need to drill these screw 

      holes.

10. Remove the rubber cap from the blower outlet 

      pressure tap and discard.  See Figure 7 for blower tap

      location.

11.  Attach the pressure switch tubing to the pressure tap 

      on the blower outlet.  See Figure 7 for blower tap 

      location.  On some older model heaters, the pressure 

      tap is located on the opposite side of the blower 

      housing as shown in Figure 7.

12. Unplug the in-line quick connect on the red wire in the 

      heater wire harness and attach the 2 wires to the vent 

      pressure switch.  See Figure 6.  If you are refitting a 

      heater with an FDXLRGK1xxx kit, you will need to 

      splice into the wire harness red wire which attaches to 

      the water pressure switch.  The vent pressure switch 

      should be in series with the water pressure switch.

1301666601 rev B

INSTALLATION PROCEDURE

Page 4 of 10

Vent Termination

Vent  extending  through  a  roof  or  wall  must  be  listed 

double-wall (Type B) vent, and pass through an approved 

roof jack, or roof thimble.  A listed vent cap must be used.  

Gas vents that are spaced less than 8 ft horizontally from 

a vertical wall or similar obstruction shall terminate not less 

than 2 ft above any portion of a building within 10 ft.  Gas 

vents  that  are  spaced  8  ft  or  more  horizontally  from  a 

vertical  wall  or  similar  obstruction  shall  terminate  above 

the roof a distance 

H

 based on the roof pitch.  Using the 

roof pitch, find the minimum value of 

H

 using Figure 2 and 

Table 6.

NOTES ON INDOOR INSTALLATIONS (continued)

TABLE 6

Roof Slope

Min. Height H from 

Roof to Lowest 

Discharge Opening

Flat to 6/12

1.0 ft

Over 6/12 to 7/12

1.25 ft

Over 7/12 to 8/12

1.5 ft

Over 8/12 to 9/12

2.0 ft

Over 9/12 to 10/12

2.5 ft

Over 10/12 to 11/12

3.25 ft

Over 11/12 to 12/12

4.0 ft

Over 12/12 to 14/12

5.0 ft

Over 14/12 to 16/12

6.0 ft

Over 16/12 to 18/12

7.0 ft

Over 18/12 to 20/12

7.5 ft

Over 20/12 to 21/12

8.0 ft

FIGURE 2

13. If installing the kit on models H250FDN, 

      H250FDP, or H400FDP, you must also replace 

      the existing blower air inlet restrictor with the 

      new one included in the kit.

       a)  Remove the 4 #10 hex head screws that 

            fasten the plate to the blower, and remove 

            the blower air plate and discard.  Save the 

            4 screws as they will be needed to install 

            the new plate.

EN

G

LIS

H

       b)  Install the new blower plate included in the kit 

            using the 4 screws.  It may be helpful to drive the 

            screws in and out of the plate outside of the 

            heater first to "thread" the holes before installing it 

            in the heater.  See Figure 7.

14. Re-install heater front door.

15. Connect vent piping system to heater vent adapter.

16. If connected, turn pump, main gas valve, and heater 

      power back on.

17. Activate heater and check for proper function.