08/18 

      Model 8605WC 

Page 2 of 4 

 

LOCATION OF UNIT:  

The Model 8605WC Barrier Free Emergency Shower & 

Eye/Face Wash Booth should be installed in close proximity to potential accident 
areas. It should be clearly identified free from obstructions and easy to access. 
 

SUPPLY LINE:  

The minimum recommended line size is 1” IPS with 30-90 psi (2-6 

ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet filter 
is recommended. 
 

PLUMBING CONNECTIONS:  

Inlet supply is female 1” IPS. Waste outlet is 3” IC 

(Inside caulk). 

 

TROUBLESHOOTING

 

 

PROBLEM                                                     REPAIR CHECKLIST

 

1. 

No flow. 

1.   

Check the main shut-off valve. 

2. 

Insufficient water flow. 

2.   

Verify minimum 30 psi (2 ATM) 
flowing supply line pressure. 

3. 

Insufficient water flow. On 
eyewash, however, shower is 
sufficient. 

3.  a. 

 

 

 

Probable clogging of flow control 
due to inadequate line flushing. 
Unscrew eye/face wash head and 
remove the four screws to 
disassemble the head. Clean flow 
control and reassemble head. See 
SP65 Installation Drawing for details. 

4. 

Insufficient water flow at the 
showerhead, however, 
eyewash is sufficient. 

4.   

Probable clogging of flow control 
inside showerhead.  Unscrew 
showerhead off of elbow and clean 
rubber flow control. 

5. 

Eyewash stream does not meet 
desired eye level. 

5.   

Possible blocked flow control, see 
above solution.  Possible non-
leveled eyewash assembly. 

6. 

Water does not drain properly. 

6.   

Check the main waste line of your 
building to see if it does handle the 
capacity required for the entire 
drainage system. 

 

For more information on Haws products, see our website: 

www.hawsco.com

 

 

 

 
 
 
 
 
 
© 2018 Haws

®

 Corporation – All Rights Reserved 

HAWS

® 

and other trademarks used

 

in these materials are the exclusive property of Haws Corporation.

 

Summary of Contents for 8605WC

Page 1: ...pon written authority from HAWS Sparks Nevada HAWS will not be liable for any damages caused by defective materials or poor workmanship except for replacements as provided above Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not...

Page 2: ... is sufficient 3 a Probable clogging of flow control due to inadequate line flushing Unscrew eye face wash head and remove the four screws to disassemble the head Clean flow control and reassemble head See SP65 Installation Drawing for details 4 Insufficient water flow at the showerhead however eyewash is sufficient 4 Probable clogging of flow control inside showerhead Unscrew showerhead off of el...

Page 3: ...ghts Reserved HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation C R MODEL S 1455 KLEPPE LANE SPARKS NEVADA 89431 775 359 4712 FAX 775 359 7424 E MAIL HAWS HAWSCO COM WEBSITE WWW HAWSCO COM ITEM DESCRIPTION THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION CONTINUED PRODUCT IMPROVEMENTS MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITH...

Page 4: ...LICATION CONTINUED PRODUCT IMPROVEMENTS MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE RTM 8 10 01 13 0002080194 D 8605WC EMERGENCY SHOWER NA 1 1 MJ 08 07 18 FV 4 OF 4 INSTALLATION 5334 2018 NG 36 NOTES 1 WHEN INSTALLING THIS UNIT LOCAL STATE OR FEDERAL CODES SHOULD BE ADHERED TO FOR INSTALLATION DIMENSIONS LOCATIONS WASTE AND SUPPLY REQUIREMENTS OTHER THAN SHOWN 2 TO COMPLY...

Reviews: