-2-
A. Description
1. Function
The pressure relief valve maintains a pre-set inlet pressure (p1) constant. Any excess system pressure is
relieved by fast opening of the valve. The closing procedure is slow in order to avoid shock pressure loads.
Variable flow rates have no effect on the maintained pressure which is regulated by the control valve. The
overpressure or maintained pressure of the standard version can be set within the range of 1.5 bar to 12 bar.
Technical features:
Medium:
Drinking water
Pressure stages:
PN 10 (Standard DN 200 and upwards)
PN 16 (Standard up to and including DN 150)
PN 25
Flanges:
Connection dimensions acc. DIN EN 1092
– 2
Manometer:
EN 837-1, accuracy class 1.0
Main valve material:
EN-GJS-400-15
Temperature range:
2 to 40º C
2. General safety guidelines
The Hawle HAWIDO regulating valve is designed for use in drinking water supply systems. Please consult
the manufacturer before using it with other media.
Material damage or injury to persons can occur if the HAWIDO is not installed, commissioned, operated or
maintained according to these instructions or to codes of practice.
As a precondition, it is assumed that all technical regulations (e.g. SVGW, ÖVGW, DVGW...), codes of
practice (e.g. VDE, VDI ...), laws and standards are understood, and will be adhered to and applied.
Work on electrical installations (e.g. installation of magnetic position switches, solenoid valves, etc.) may only
be carried out by personnel authorised to carry out this work.
The responsibility for layout, installation position and commissioning of the fittings in the pipe work lies with
the designer, installer and/or user. Design or installation errors can adversely affect the operation of the
regulating valve and can create a significant risk. If in doubt, please consult us.
Summary of Contents for HAWIDO 1405
Page 1: ...manual Pressure retention valve DAV for monitoring third party pressure...
Page 14: ...11 3 1 Main valve with stainless steel connection ND 40 to ND 200 drawing 08 12 2011 pl...
Page 17: ...14 3 3 Control valve pressure sustaining INOX drawing 05 09 2017 pl...
Page 24: ...21 3 6 Position indicator drawing DN 40 DN 100 DN 125 DN 300 12 03 2014 pl...
Page 28: ...25...