-7-
C. Fault finding
Symptoms
Possible cause
Action
Valve does not open
One-way flow restrictor blocked Replace or unscrew the set
screw several times until the
valve functions properly
One-way flow restrictor closed
too far
Loosen the grub screw until the
valve functions properly
Valve does not close
One-way flow restrictor blocked Replace or screw the grub set
fully in and out several times,
and then reset
Filter in control circuit blocked
Clean the filter
Air in the control lines or valve
chamber
Vent system
Foreign matter in the main valve Carry out a service, and remove
any foreign matter
Diaphragm defective
Carry out a service, and replace
the diaphragm
Valve spindle jammed by
encrustation
Carry out service, and remove
any encrustation
Loud noises
Unsatisfactory operational
conditions
Change pressure conditions by
0.1 to 0.2 bar. Slightly open or
close the one-way flow
restrictor. Contact Hawle
customer service department.
Wrong valve diameter
Calculate correct valve
diameter. (If necessary contact
Hawle)
Erratic operation
One-way flow restrictor
incorrectly set
Reset (according to Chapter:
Resetting the reaction speed)
Original pressure values no
longer reached
Pressure gauge faulty
Check or replace pressure
gauge
Changed operating conditions
Reset accordingly (see Chapter:
Recommended installation)
Epoxy-coating damaged
Transportation damage,
installation damage
Repair using Hawle two-
component repair kit for
coatings
Summary of Contents for HAWIDO 1405
Page 1: ...manual Pressure retention valve DAV for monitoring third party pressure...
Page 14: ...11 3 1 Main valve with stainless steel connection ND 40 to ND 200 drawing 08 12 2011 pl...
Page 17: ...14 3 3 Control valve pressure sustaining INOX drawing 05 09 2017 pl...
Page 24: ...21 3 6 Position indicator drawing DN 40 DN 100 DN 125 DN 300 12 03 2014 pl...
Page 28: ...25...