MS-9
J. LIGHT FUEL OIL PIPING SYSTEM
1. Hauck recommends using a flexible connection to connect the oil line to the oil manifold
on the burner. A flexible connection will reduce vibration stress on the oil manifold.
Refer to Table 7 for recommended flex connection.
Table 7. Recommended Flexible Oil Hose Size
2. For recommended piping sizes see Table 8. Before attaching fuel lines, purge the
piping to remove scale and dirt that could clog and damage oil equipment. Follow Figure 5
for the suggested piping layout.
Discharge Piping, Light Oil
Up to 100 SSU
(Up to 2.1 x 10
-5
m
2
/sec)
Return Piping, Light Oil
Up to 100 SSU
(Up to 2.1 x 10
-5
m
2
/sec)
Return Piping
Heavy Oil
MegaStar
Model No.
Up to 25'
(Up to
7.6m)
25'– 49'
(7.6-
14.9m)
50' – 100'
(15.2-
30.5m)
Up to 25'
(Up to
7.6m)
25' – 49'
(7.6-
14.9m)
50' – 100'
(15.2-
30.5m)
Up to 25'
(Up to
7.6m)
25'– 49'
(7.6-
14.9m)
50' – 100'
(15.2-
30.5m)
50 1"
(DN25)
1"
(DN25)
1 ¼"
(DN32)
1"
(DN25)
1 ¼"
(DN32)
1 ¼"
(DN32)
1 ¼"
(DN32)
1 ½"
(DN40)
2"
(DN50)
75 1"
(DN25)
1"
(DN25)
1 ¼"
(DN32)
1"
(DN25)
1 ¼"
(DN32)
1 ¼"
(DN32)
1 ¼"
(DN32)
1 ½"
(DN40)
2"
(DN50)
100 1"
(DN25)
1"
(DN25)
1 ¼"
(DN32)
1 ¼"
(DN32)
1 ¼"
(DN32)
1 ¼"
(DN32)
1 ¼"
(DN32)
1 ½"
(DN40)
2"
(DN50)
125 1"
(DN25)
1 ¼"
(DN32)
1 ½"
(DN40)
1 ¼"
(DN32)
1 ¼"
(DN32)
1 ½"
(DN40)
1 ½"
(DN40)
2"
(DN50)
2"
(DN50)
150 1"
(DN25)
1 ¼"
(DN32)
1 ½"
(DN40)
1 ¼"
(DN32)
1 ¼"
(DN32)
1 ½"
(DN40)
1 ½"
(DN40)
2"
(DN50)
2"
(DN50)
Table 8. Minimum Pipe Size For Hauck Oil Supply Pumping Units
3. Adjust the bypass relief valve until required oil pressure is achieved. See Table 9 for
approximate settings. Final oil pressure will have to be adjusted to attain desired burner
output and stack exhaust gas analysis.
MegaStar™ Model No.
50
75-150
Flex Oil Hose Part No.
11078
20518
Size
1/2" (DN 15)
1" (DN 25)
NOTE
Hauck recommends the use of oil manifolds that meet
NFPA guidelines. NFPA requires two safety shutoff
valves piped in series in the burner’s main oil line. A
low/high oil pressure switch must be interlocked with
the burner’s safety shutoff valves. Hauck oil manifolds
have been designed to ensure compliance to NFPA
requirements.
WARNING
Adjustment of this equipment and its components by
unqualified personnel can result in fire, explosion,
severe personal injury, or even death.
Summary of Contents for Eco-StarII 100B
Page 11: ...Page 11 MS 9 Figure 3 Simplified Gas and Air Flow Chart Atmospheric Conditions GL86 ...
Page 12: ...Page 12 MS 9 Figure 4 MegaStar Gas Orifice Meters Graph ...
Page 30: ...Page 30 MS 9 Figure 14 Vapor Pressures of Propane Butane and Butane Propane Mixtures ...
Page 39: ...Page 39 MS 9 APPENDIX ...
Page 40: ...Page 40 MS 9 APPENDIX ...
Page 41: ...Page 41 MS 9 APPENDIX ...
Page 42: ...Page 42 MS 9 APPENDIX ...
Page 43: ...Page 43 MS 9 APPENDIX ...
Page 44: ...Page 44 MS 9 APPENDIX ...
Page 45: ...Page 45 MS 9 APPENDIX ...
Page 46: ...Page 46 MS 9 APPENDIX ...