
Page 5
BCS3000M-9
E. ADJUSTMENTS
1.
Adjust the purge timer, 1TR, for the required purge time (1/2 to 10 minutes).
IMPORTANT
Before igniting the burner, the dryer must be purged to remove possible
accumulation of combustible gases.
A minimum of four complete air changes
must be supplied.
Multiply the total system volume (dryer, baghouse and exhaust
ducts) in cubic feet by four. Divide this value by the burner air capacity in cubic feet
per minute. The result will be the required purge time in minutes
2.
Perform the fuel motor calibration procedure described in
Appendix A
.
Recalibrate annually or whenever a control motor is serviced or replaced.
3.
Verify that all low fire limit switch contacts are closed when the burner is at 0% and open
when the burner leaves low fire. Reference the burner operating instructions for switch
adjustment.
4.
Verify that all purge permissive contacts are closed after the air control valve drives open
for purge (Eco-Star and StarJet conversion burners only).
F. FINAL CHECKOUT
1.
Ensure sure that all equipment and components have been installed in accordance with the
manufacturer’s instructions.
2.
Verify all wiring and tighten connections.
3.
Confirm all linkage adjustments and insure that control arms and linkage rods are tight.
4.
Clean all traps and filters.
5.
Check all fuel and air supply lines for leaks.
6.
Verify all pressure settings.
G. PANEL OPERATION
1.
Open applicable manual shutoff valves to supply air and fuel to the system.
2.
Move the panel
POWER
switch to
ON
and verify that the
FUEL SELECTOR
switch is in the
desired position.
a.
The Temperature Controller, High Temp Limit and flame relay will perform their self-
test procedures.
b.
The burner fuel control motor will drive to its low fire position.
c. The
RESET
indicator will come on.
d. A
message will appear.
WARNING
Adjustment of this equipment, by unqualified personnel, can result in fire,
explosion, severe personal injury, or even death.