VVP10 HART
HART
®
VALVE POSITIONER
INSTALLATION, OPERATION, CONFIGURATION AND MAINTENANCE MANUAL
______________________________________________________________________________________________________________________________
24
Change Counter
-
Informs the change counters for each of the following positioner parameters. User can also reset
the counters in this directory.
Setpoint Mode
Input Current Range
Actuator Type
Magnet Type
Input Air Configuration
Lower Position Trim
Upper Position Trim
Characterization Function
Characterization Table
Software Writing Protection
LCD Display Variables
Temperature Unit
Security Failure
HART Polling Address
Auto Calibrations/PID Tuning
PID Factor
PID Enable/Disable and Deadband
Setpoint Limits
Loop Current Enable/Disable
Setpoint Rate Open/Close
Setpoint Cutoff
Position Diagnostics
-
Enables/disables, configures and reports the Diagnostics of Reversals, Strokes, Mileage and
Position Histogram. For details on each of these diagnostics, see section 3.9 of this manual.
In addition, it performs the Actuator Opening and Closing Test procedures (for calculation of opening/closing times),
Partial Stroke Test (PST) and Full Stroke Test (FST). For details on each of these procedures, see section 3.9 of this
manual.
Temperature
-
Informs the maximum and minimum temperature values recorded by the positioner during its operation,
according to the user calibration.
In addition, it monitors the temperature according to the user-configured work limits,
offering occurrence counter and limit exceeded persistent alarm, also configurable.
Pressure
- Inform the maximum and minimum input pressure values recorded by the positioner during its operation,
according to the user calibration. In addition, it monitors the input pressure according to the user-configured work limits,
offering occurrence counter and exceeded limit persistent alarm, also configurable.
*This directory is only available for models with installed pressure sensors.
Digital I/O
–
Configures the position limits for activating digital outputs (lower and upper), the actuation of the digital
outputs (in relation to inputs or position limits) and enables/disables the alarms for digital inputs and outputs. See
following section 3.10 for more information.
*This menu is only available for complete model.
HART Communication
–
It informs the number of communication packets received by the equipment (
RX
), as well
as those answered by it (
TX
), displaying the communication loss rate per hour (
Loss/h
). It also informs the total
operating time of the equipment since the last default restoration (
Restore Default
).