6
P61A Pellet Stove
3-90-05822R29_JR15_04/14
installing
Place the stove on a noncombustible floor or on a floor protector
that extends a minimum of 6 inches to the front, (measured from
the glass) 6 inches to the sides and 6 inches to the rear of the
pedestal. It is also recommended that floor protection be installed
under any horizontal venting and extending 2 inches beyond the
vent measurement.
note for canadian installation only:
Per ULC-S627-00,
If installed on a combustible floor, the need to provide a
noncombustible
floor protector
covering the area beneath the
space heater
and extending at least 17.72" (450mm) on the firing
side and at least 7.87" (200mm) on the other sides.
In Canada, you may follow smaller U.S. floor protection
requirements onlY if the user agrees to completely shut-
down the appliance, and allow it to cool to where all fire is
extinguished and the combustion blower and its indicator
light shuts off, prior to opening the firebox door or ash door.
Place the stove away from combustible walls at least as far
as shown in Figures 3 and 4. Note the difference in side wall
clearance with and without side shields.
Note that the clearances shown are minimum for safety but do
not leave much room for access when cleaning or servicing.
Connect the power cord to a 120 V.A.C. 60Hz grounded
receptacle. (A surge protector is recommended to protect the
circuit board.) Also be sure that the polarity of the outlet that the
stove is plugged into is correct.
Prior to installing the flue pipe, connect a draft meter. (The
draft meter must have a minimum range of 0-.5.) Record the
first reading. Connect flue pipe to stove and be sure all doors
and windows in the home are closed. Record the second draft
reading_______. If the second reading is more than .05" lower
than the first reading, check for possible restrictions or the need
for outside air (see page 9). For more information on the draft
test procedure, refer to Page 20.
Mobile home installation
When installing this unit in a mobile home, several requirements
must be followed:
1. The unit must be bolted to the floor. This can be done with
1/4" lag screws through the 2 holes in the base plate.
2. The unit must also be connected to outside air. See page 9.
3. Floor protection and clearances must be followed as shown.
4. Unit must be grounded to the metal frame of the mobile home.
caution: this appliance must be vented to the outside.
installation
Minimum size rectangular floor protection (USA) is
28
5/16
" Deep By 24
3/4
" Wide.
* Floor protection dimensions for the front and sides
are measured from the appliance door opening in
The United States. In Canada, the side dimension is
measured from the widest part of the appliance.
l
j
Floor Protection
requirements
US
Canada
Sides
Rear
6"
200mm
6"
200mm
k
Front
6"
450mm
Figure 3
9"(228mm)With Side Shields
13"(330mm) Without Side Shields
Figure 4
2"(51mm)
36"(914mm)
14" (355mm) with
side shields
20" (508mm)
without side shields
14" (355mm)
20" (508mm)
9"(228mm)-
13"(330mm)
9"(228mm)-
13"(330mm)
Alternate floor protector
dimension may be used
as long as they satisfy
t h e m e a s u r e m e n t
requirements shown
below.
Minumum size floor
protection for a corner
installation hearth pad
is 36" x 36". Clearance
shown as 9" with optional
side shields installed.
j
usa
k
l
j
canada
note:
Measurement "L"
is measured from
the pedestal base
in the US ONLY
note:
Measurement "K"
is measured from
the glass in the
US ONLY
F
loor
protector
do not install in sleePing rooM.
WARNING
!
the structural integritY oF the ManuFactured
hoMe Floor, wall, and ceiling/rooF Must be
Maintained.