Appendix A - Upgrading the Firmware
66
Hardware Reference Manual – DXLink™ Twisted Pair 4K Transmitters/Receivers
Transferring KIT Files
The system will be non-operational during the upgrade procedure below.
The
Firmware Transfers
tool in NetLinx Studio is used to map KIT files to DXLink 4K Receivers. The instructions below assume that
the preparations on the previous pages have been completed.
To send a KIT file to a DXLink Receiver:
1.
In NetLinx Studio f
rom the Tools menu, select “Firmware Transfers > Send to NetLinx Device”
to open the Send to NetLinx Device
dialog box.
2.
Click Browse (...) to navigate to the target directory. The selected directory path is displayed in the Location text box. KIT files
in the target directory display under Files.
3.
Select the appropriate KIT file from the list.
4.
Enter the Device and System numbers (see FIG. 26 on page 64) for the target module in the Device and System text boxes.
5.
Review the File and Target Device information for accuracy before you send.
6.
Click Send to upgrade the firmware on the DXLink 4K Receiver.
The Power LED blinks during the process for upgrading the firmware (this is normal).
The progress of the upgrade displays in the Upload Status field. Status is also indicated in the Status bar at the bottom.
The success of the upgrade or any errors that occur will be reported.*
* If an incorrect file has been selected or if the upgrade has failed, the Power LED will briefly illuminate solid green then change to
a slow blink. To recover (in either case), reboot the Receiver and browse to select the correct file and then re-send.
7.
Close the window when the transfer is complete.
8.
When the process is complete, cycle power using the new image on the DXLink Module:
a.
Unplug the desktop power supply from the AC power source and plug it back in.
Or
b.
If the power source is the switcher, unplug the RJ-45 connector from the DXLink port on the module and plug it back in.
9.
Wait 60 seconds and refresh the System OnLine Tree, and check to be sure the firmware version matches the version selected
for the upgrade.
Reminders
When the file transfer is complete, remember to do the following:
Set the #1 Toggle on the DXLink Module to OFF.
If you set the PC to Static IP Mode for a Virtual NetLinx Master file transfer, return the setting to “Obtain an IP address
automatically” (see page 77).