Harman® • Absolute43 Installation Manual_R2 • 2015 - ___ • 03/15
13
3-90-00778i
12"
min. wall to outlet
36"
min. clear
anc
e to an
y
combustible ma
terial
#7 Installing through the ceiling (Figure 4.7)
Follow PL vent manufacturers recommendations when using
wall and ceiling pass through.
Seal pipe joints with silicone or aluminum tape in addition to
the sealing system used by the manufacturer.
Note: Do not place joints within wall pass-through.
Figure 4.7
Figure 4.8
Figure 4.9
Area within dotted circle represents the minimum clearance to
combustible materials such as shrubbery, mulch or tall grasses.
12"
min. abo
ve g
round lev
el
Minimum flue vent configuration
It is recommended that outside air be
installed with this venting configuration.
Smoke spillage may be possible during
a power outage.
PL vent manufacturer's
firestop spacer and support
1" MIN.
No insulation or other
combustible materials
are allowed within 3"
of the PL vent pipe.
flashing
storm collar
1" MIN.
1" MIN.
1” MIN.
12”
Min
12” Minimum
clearance to ceiling
DO NOT USE MAKESHIFT COMPROMISES wHEN
INSTALLING THIS APPLIANCE. DAMAGE AND/OR
INJURY MAY RESULT.
CAUTION
!